81.3-A. | Replacement of Wood Poles in Grade F Construction | |||||
Wood poles in Grade F construction shall be replaced or reinforced before the safety factor has been reduced to less than one, except that the circumference of sound solid wood within 18 inches above and below the ground line on such poles before replacement or reinforcement shall not be less than as follows: | ||||||
|
Strikeout and Underline Version
Rule 81.3-A
81.3-A. | Replacement of Wood Poles in Grade FC Construction | |||||
Wood poles in Grade FC construction shall be replaced or reinforced before the safety factor has been reduced to less than one, except that the circumference of sound solid wood within 18 inches above and below the ground line on such poles before replacement or reinforcement shall not be less than as follows: | ||||||
|
Final Version
Rule 81.3-A
81.3-A. | Replacement of Wood Poles in Grade C Construction | |||||
Wood poles in Grade C construction shall be replaced or reinforced before the safety factor has been reduced to less than one, except that the circumference of sound solid wood within 18 inches above and below the ground line on such poles before replacement or reinforcement shall not be less than as follows: | ||||||
|