Rule 54.6-E
54.6-E. Risers
Risers from underground cables or other conductors shall be
encased in grounded iron or steel shall (or other metal covering of equal
strength) from the ground line to a level not less than 8 feet above ground
line (see App. G, Fig. 61)
Any riser on the surface of a pole or not more than 18 inches from the center
line of a pole shall be covered by a suitable protective covering where within
a vertical distance of 8 feet from the level of communication conductors
(including cables) or unprotected supply conductors (including the leads
from the terminal) supported by the same pole or where within a radial distance
of 6 feet from conductors not supported by the same pole.
The portion of any riser between the insulating covering required on the
upper section and the covering required on the lower section by the foregoing
shall be covered by the extension of either metal pipe is used as a protective
covering, the fiber conduit shall not extend within 8 feet of the ground
line and shall be installed in a workmanlike manner and securely supported
in order to prevent it from slipping downward and exposing any upper section
of the metal pipe.
The radial clearances between conductors, specified in Table 2, Cases 16
and 17, are not required between suitably insulated conductors in the same
riser.
Protective covering (suitable) is not required over risers encased in effectively
grounded non-climbable metal poles or iron or steel pipe attached to a steel
pole, tower or other metal structure, provided the iron or steel pipe is
effectively grounded and is metallically connected to such metal structure.
Strikeout and Underline Version
Rule 54.6-E
54.6-E. Risers
Risers from underground cables or other conductors shall
be encased in grounded iron or steel shall (or other metal covering of equal
strength) from the ground line to a level not less than 8 feet above ground
line (see App. G, Fig. 61)
Risers from underground cables may be encased in plastic pipes
in lieu of the grounded iron or steel pipe required by this rule, provided
that risers of circuits in excess of 750 volts shall have an effectively
grounded metallic shield. Such plastic pipe shall be of material 8.S specified
in Rule 22.2-C, designated as Schedule 80, with a minimum nominal pipe size
of 2 ½ inches, or Schedule 120 with a minimum nominal pipe size of
2 inches.
Any riser on the surface of a pole or not more than 18 inches from the center
line of a pole shall be covered by a suitable protective covering where within
a vertical distance of 8 feet from the level of communication conductors
(including cables) or unprotected supply conductors (including the leads
from the terminal) supported by the same pole or where within a radial distance
of 6 feet from conductors not supported by the same pole.
Any riser more than 18 inches from the center line of a pole shall
be covered by a suitable protective covering, or by securely supported impregnated
fiber conduit without metal pipe, where within a vertical distance of 8 feet
from the level of communication conductors (including cables) or unprotected
supply conductors (including the leads from the terminal) supported by the
same pole or within a radial distance of 6 feet from conductors not supported
by the same pole.
The portion of any riser between the insulating covering required on the
upper section and the metal or plastic covering required on the lower
section by the foregoing shall be covered by the extension of either or
both of such coverings. Where metal pipe is used as a protective covering,
the fiber conduit shall not extend within 8 feet of the ground line and shall
be installed in a workmanlike manner and securely supported in order to prevent
it from slipping downward and exposing any upper section of the metal pipe.
The radial clearances between conductors, specified in Table 2, Cases 16
and 17, are not required between suitably insulated conductors in the same
riser.
Protective covering (suitable) is not required over risers encased in effectively
grounded non-climbable metal poles or iron or steel pipe attached to a steel
pole, tower or other metal structure, provided the iron or steel pipe is
effectively grounded and is metallically connected to such metal structure.
Final Version
Rule 54.6-E
54.6-E. Risers
Risers from underground cables or other conductors
shall be encased in grounded iron or steel shall (or other covering of equal
strength) from the ground line to a level not less than 8 feet above ground
line (see
App. G, Fig. 61
)
Risers from underground cables may be encased in plastic pipes in lieu of
the grounded iron or steel pipe required by this rule, provided that risers
of circuits in excess of 750 volts shall have an effectively grounded metallic
shield. Such plastic pipe shall be of material 8.S specified in
Rule 22.2-C
, designated as Schedule 80, with a minimum nominal pipe size of 2 ½
inches, or Schedule 120 with a minimum nominal pipe size of 2 inches.
Any riser on the surface of a pole or not more than 18 inches from the center
line of a pole shall be covered by a suitable protective covering where within
a vertical distance of 8 feet from the level of communication conductors
(including cables) or unprotected supply conductors (including the leads
from the terminal) supported by the same pole or where within a radial distance
of 6 feet from conductors not supported by the same pole.
Any riser more than 18 inches from the center line of a pole shall be covered
by a suitable protective covering, or by securely supported impregnated fiber
conduit without metal pipe, where within a vertical distance of 8 feet from
the level of communication conductors (including cables) or unprotected supply
conductors (including the leads from the terminal) supported by the same
pole or within a radial distance of 6 feet from conductors not supported
by the same pole.
The portion of any riser between the insulating covering required on the
upper section and the metal or plastic covering required on the lower section
by the foregoing shall be covered by the extension of either or both of such
coverings. Where metal pipe is used as a protective covering, the fiber conduit
shall not extend within 8 feet of the ground line and shall be installed
in a workmanlike manner and securely supported in order to prevent it from
slipping downward and exposing any upper section of the metal pipe.
The radial clearances between conductors, specified in
Table 2, Cases 16 and 17
, are not required between suitably insulated conductors in the same riser.
Protective covering (suitable) is not required over risers encased in effectively
grounded non-climbable metal poles or iron or steel pipe attached to a steel
pole, tower or other metal structure, provided the iron or steel pipe is
effectively grounded and is metallically connected to such metal structure.