Rule 54.8-C2

 

54.8-C2)    On Clearance Crossarms: Supply service drops may be supported on a clearance crossarm at a vertical distance less than 48 inches (specified in Table 2, Case 8, Column D, and Case 9, Column C) but not less than 24 inches above or below either supply circuits of 0-750 volts or communication circuits not supported on a messenger, or above communication or supply circuits which are supported on a messenger, provided the supply service drop unprotected conductors are at least 25 inches horizontally from the center line of a pole or are attached to suitable brackets (at least 25 inches from center line of pole) on each end of the clearance arm and carried on the underside of the clearances arm from end to end in fiber conduit or under wood protective covering.

The installation of service drops in accordance with this rule will not entail any change in the communication conductors supported on the pole.  (See App. G, Fig 40)


Strikeout and Underline Version
Rule 54.8-C2


54.8-C2)    On Clearance Crossarms: Supply service drops may be supported on a clearance crossarm at a vertical distance less than 48 inches (specified in Table 2, Case 8, Column D, and Case 9, Column C) but not less than 24 inches above or below either supply circuits of 0-750 volts or communication circuits not supported on a messenger, or above communication or supply circuits which are supported on a messenger, provided the supply service drop unprotected conductors are at least 25 inches horizontally from the center line of a pole or are attached to suitable brackets (at least 25 inches from center line of pole) on each end of the clearance arm and carried on the underside of the clearances arm from end to end in fiber or plastic conduit or under wood protective covering as specified in Rule 54.6-C.

The installation of service drops in accordance with this rule will not entail any change in the communication conductors supported on the pole.  (See App. G, Fig 40)

 

Final Version
Rule 54.8-C


54.8-C2)    On Clearance Crossarms: Supply service drops may be supported on a clearance crossarm at a vertical distance less than 48 inches (specified in Table 2, Case 8, Column D, and Case 9, Column C ) but not less than 24 inches above or below either supply circuits of 0-750 volts or communication circuits not supported on a messenger, or above communication or supply circuits which are supported on a messenger, provided the supply service drop unprotected conductors are at least 25 inches horizontally from the center line of a pole or are attached to suitable brackets (at least 25 inches from center line of pole) on each end of the clearance arm and carried on the underside of the clearances arm from end to end in fiber or plastic conduit or under wood protective covering as specified in Rule 54.6-C .

The installation of service drops in accordance with this rule will not entail any change in the communication conductors supported on the pole.  (See
App. G, Fig 40 )