Rule 54.8-C2
54.8-C2) On Clearance Crossarms: Supply service drops
may be supported on a clearance crossarm at a vertical distance less than
48 inches (specified in Table 2, Case 8, Column D, and Case 9, Column C)
but not less than 24 inches above or below either supply circuits of 0-750
volts or communication circuits not supported on a messenger, or above communication
or supply circuits which are supported on a messenger, provided the supply
service drop unprotected conductors are at least 25 inches horizontally from
the center line of a pole or are attached to suitable brackets (at least
25 inches from center line of pole) on each end of the clearance arm and
carried on the underside of the clearances arm from end to end in fiber conduit
or under wood protective covering.
The installation of service drops in accordance with this rule
will not entail any change in the communication conductors supported on the
pole. (See App. G, Fig 40)
Strikeout and Underline Version
Rule 54.8-C2
54.8-C2) On Clearance Crossarms: Supply service
drops may be supported on a clearance crossarm at a vertical distance less
than 48 inches (specified in Table 2, Case 8, Column D, and Case 9, Column
C) but not less than 24 inches above or below either supply circuits of 0-750
volts or communication circuits not supported on a messenger, or above communication
or supply circuits which are supported on a messenger, provided the supply
service drop unprotected conductors are at least 25 inches horizontally from
the center line of a pole or are attached to suitable brackets (at least
25 inches from center line of pole) on each end of the clearance arm and
carried on the underside of the clearances arm from end to end in fiber
or plastic conduit or under wood protective covering as specified
in Rule 54.6-C.
The installation of service drops in accordance with this
rule will not entail any change in the communication conductors supported
on the pole. (See App. G, Fig 40)
Final Version
Rule 54.8-C
54.8-C2) On Clearance Crossarms: Supply service
drops may be supported on a clearance crossarm at a vertical distance less
than 48 inches (specified in
Table 2, Case 8, Column D, and Case 9, Column C
) but not less than 24 inches above or below either supply circuits of 0-750
volts or communication circuits not supported on a messenger, or above communication
or supply circuits which are supported on a messenger, provided the supply
service drop unprotected conductors are at least 25 inches horizontally from
the center line of a pole or are attached to suitable brackets (at least
25 inches from center line of pole) on each end of the clearance arm and
carried on the underside of the clearances arm from end to end in fiber or
plastic conduit or under wood protective covering as specified in
Rule 54.6-C
.
The installation of service drops in accordance with
this rule will not entail any change in the communication conductors supported
on the pole. (See
App. G, Fig 40
)