Original Version
Rule 84.8-D2
84.8-D2) On Clearance Crossarms: Communication service
drops may be supported on a clearance crossarm at a vertical distance less
than as specified in Table 2, Case 9, Column C (48 inches), but not less
than 24 inches above or below supply circuits of 0-750 volts, or above supply
cables when treated as in Rule 57.8, provided the communication service drop
conductors are at least 25 inches horizontally from the center line of pole
or are attached to suitable brackets on each end of the clearance arm and
carried on the underside of the clearance arm from end to end in fiber conduit
or under wood protective covering.
Service drops installed in accordance with this rule will not entail any
change in the supply conductors supported on the pole.
Strikeout and Underline Version
Rule 84.8-D2
84.8-D2) On Clearance Crossarms: Communication
service drops may be supported on a clearance crossarm at a vertical distance
less than as specified in Table 2, Case 9, Column C (48 inches), but not
less than 24 inches above or below supply circuits of 0-750 volts, or above
supply cables when treated as in Rule 57.8, provided the communication service
drop conductors are at least 25 inches horizontally from the center line
of pole or are attached to suitable brackets on each end of the clearance
arm and carried on the underside of the clearance arm from end to end in
fiber or plastic conduit or under wood protective covering as specified
in Rule 54.6-C.
Service drops installed in accordance with this rule will not entail any
change in the supply conductors supported on the pole.
Final Version
Rule 84.8-D2
84.8-D2) On Clearance Crossarms: Communication
service drops may be supported on a clearance crossarm at a vertical distance
less than as specified in
Table 2, Case 9, Column C
(48 inches), but not less than 24 inches above or below supply circuits
of 0-750 volts, or above supply cables when treated as in
Rule 57.8
, provided the communication service drop conductors are at least 25 inches
horizontally from the center line of pole or are attached to suitable brackets
on each end of the clearance arm and carried on the underside of the clearance
arm from end to end in fiber or plastic conduit or under wood protective
covering as specified in
Rule 54.6-C
.
Service drops installed in accordance with this rule will not entail any
change in the supply conductors supported on the pole.