General Order 95
Section V
Detailed Construction Requirements
for Supply Lines
(Class H, L and T Circuits)
54.6 Vertical and Lateral Conductors
A.
Unprotected Conductors
(See Rule
20.9–E for
definition)
Unprotected conductors may pass laterally on a pole or structure or vertically
from one level on a pole or structure to another level, but shall not pass
within the climbing space; shall not pass within the working space, except as
permitted by Rule 54.7–B2
; shall not pass between conductors of any other circuit, except between
pole–pin conductor positions; and shall clear the conductors of other circuits
by distances not less than the following:
Highest Voltage Classification of Conductors Concerned |
Minimum Radial Distance between Conductors |
0 - 5,000 Volts |
11.5 inches |
5,000 - 7,500 Volts |
17.5 inches |
7,500 - 20,000 Volts |
24 inches |
20,000 Volts and above |
36 inches |
EXCEPTION: The minimum radial distances in this rule shall not apply to uncovered, grounded, non-dielectric fiber optic cables in transition on metallic structures, which must comply with Rule 38, Table 2, Case 16a.
Where
unprotected vertical conductors are in excess of 12 feet in length, additional
supports shall be installed so that the maximum length of conductor between
supports is not more than 12 feet.
The clearances in the above tabulation do not apply between taps in buckarm construction, the clearances specified in Table
2, Case 16 , being
directly applicable.
For clearances between street light drop wires and cables, other conductors and
metal boxes, see Rules 58.5–B3 and 92.1–F5 .
Unprotected conductors, installed as specified in this rule (54.6–A) and in Rule
54.4–D9 are not
vertical or lateral runs as defined in Rule 22.6 .
In lieu of the foregoing, vertical and lateral conductors may be installed as
specified in Rules 54.6–C and 54.6–D .
Note: Revised January 6, 1968 by Decision No. 73455 and October 9, 1996 by Resolution SU–40.
B.
Ground Wires
Ground wires shall have a conductivity and mechanical strength at least equal
to that of No. 8 AWG medium–hard–drawn copper wire; they shall not be installed
on the top surfaces of crossarms; and they shall have
clearances of not less than 1.5 inches from hardware in accordance with the
provisions of Rules 52.7–B and 52.7–C .
Note: Revised October 9, 1996
by Resolution SU–40.
That
portion of the ground wires attached on the face or back of wood crossarms or on the surface of wood poles and structures
shall be covered by a suitable protective covering (see Rule
22.8)
EXCEPTION: Ground wires of 0 - 750 volt circuits or equipment are not required to be covered where installed on crossarms supporting 0 - 750 volt conductors.
Minor separation, warping, and/or cracking of the protective covering is allowed, provided the ground wire is not exposed.
Ground
wires of common neutral systems are specially required to comply with the
provisions of Rules 59.3–C and 59.4 in addition to the provisions of
this Rule
54.6–B .
Ground wires installed on the surface of service and meter poles (see Rule
22.6–E for
definition) which terminate in effectively grounded meter or equipment
enclosures not more than eight feet above ground are not required to be covered
by a suitable protective covering (see Rule 22.8 for definition), provided they are
encased in rigid steel conduit or No. 8 AWG minimum armored copper ground wire
is used.
Note: Last paragraph
added July 26, 1966 by Decision No. 71009.
C. Lateral Conductors
(1) Lateral Runs: Lateral conductors installed as specified in this Rule 54.6–C are known as Lateral Runs.
(2) Conductors of 0 - 750 Volts: Lateral conductors of 0 - 750 volts may be installed with less than the radial clearances between conductors, specified in Table 2, Cases 16 and 17 , and with less than the clearance from the center line and surface of pole, and from the surface of crossarm, as specified in Table 1, Cases 8 and 9 , provided such conductors are suitably insulated and placed along the bottom surface of crossarms. Such conductors when installed along the bottom surface of crossarms and protected by plastic conduit having the properties of the material specified in Rule 22.8–B shall be considered to be suitably protected and allowed in the climbing space.
Note: Revised
February 13, 1980 by Resolution No. E–1863,
May 22, 1990 by Resolution No. SU–5
and January 19, 1994 by Resolution SU–25.
(3) Conductors of More than 750 Volts: Lateral conductors of more than 750 volts may be installed with less than the radial clearances between conductors, specified in Table 2, Cases 16 and 17 , and with less than the clearances from centerline and surface of pole, and from the surface of crossarm, as specified in Table 1, Cases 8 and 9 , provided such conductors are suitably insulated and are protected by the plastic conduit specified in Rule 54.6–C2 , such conduit being placed along and attached to the bottom surface of crossarm.
Note:
Revised
January 19, 1994 by Resolution SU–25.
(4) Extent of Run: The suitable protective covering (see Rule 22.8) required for protection by this Rule 54.6–C shall extend on the bottom surface of the crossarm and in no case shall the covering be terminated at clearances from the centerline of pole less than specified for conductors in Table 1, Case 8 .
Note: Revised November 21, 1990 by Resolution No. SU–6.
(5) Option: In Lieu of the foregoing lateral conductors may be installed as specified in Rules 54.6–A and 54.4–D9.
Note: Revised May 1, 1961 by Resolution No. E–1088; June 7, 1965 by Decision No. 69071 and January 6, 1968 by Decision No. 73455.
D. Vertical Runs
(1) Vertical Runs: Vertical conductors installed as specified in this Rule 54.6–D are known as Vertical Runs.
(2) Runs Less than 18 Inches from Pole Centerline: Vertical conductors may be installed with less than the radial clearances between conductors, specified in Table 2, Cases 16 and 17 , and on the surface of poles or less than 18 inches from centerline of pole provided such conductors are suitably insulated and covered throughout by a suitable protective covering (see Rule 22.8 for the definition of suitable protective covering). This protective covering is not required over suitably insulated vertical conductors in metal conduit attached to metal poles, towers, or other structures provided conduit and structure are metallically connected and effectively grounded.
Note:
Revised
January 19, 1994 by Resolution SU–25.
(3) Runs 18 Inches from Pole Centerline: Vertical conductors may be installed with less than the radial clearances between conductors, specified in Table 2, Cases 16 and 17 , and at a distance of more than 18 inches from the centerline of any pole provided that such conductors are suitably insulated and covered by suitable protective covering. Such conductors shall be located outside of the climbing and working spaces and shall not pass between conductors of different ownership except between the pole pair and at a clearance therefrom of no less than 6 inches.
Note:
Revised
January 19, 1994 by Resolution SU–25.
(4) Option: In lieu of the foregoing, vertical conductors may be installed as unprotected conductors, specified in Rules 54.6–A and 54.4–D9 .
(5) Runs within 8 Feet of Ground: Vertical conductors installed as specified in Rule 54.6–D2 and 54.6–D3 , and which extend within 8 feet of the ground shall be treated as risers. Runs which terminate in the top of enclosures which afford ample mechanical protection to the runs may extend within 8 feet of the ground but not less than 6 feet of the ground without being treated as risers.
(6) Runs Encased in Grounded Metal Covering: Vertical conductors where encased in grounded metal conduit, sheath, or shield, shall be treated as risers.
Note: Revised February 7, 1964 by Decision No. 66707; June 7, 1965 by Decision No. 69071; January 6, 1968 by Decision No. 73455 and July 22, 1968 by Decision No. 74342.
E. Risers
(1) Encased from Ground Level to 8 Feet above the Ground: Risers from underground cables or other conductors shall be encased from the ground level to a level not less than 8 feet above the ground (see Figure 54–4 A & B ) in:
a) Securely or effectively grounded iron or steel pipe (or other covering at least of equal strength); or
b) Nonmetallic conduit, provided that risers of circuits in excess of 750 volts shall have an effectively grounded metallic shield. Such conduit shall be of material as specified in Rule 22.8–B ; or
c) Nonmetallic U–shaped moulding, provided that risers of circuits in excess of 750 volts shall have an effectively grounded metallic shield. Such U–shaped moulding shall be of a material as specified in Rule 22.8–B , and the U–shaped moulding shall be installed with a backup plate (to effectively encase the cable or conductors) of similar type material.
(2) Covered from 8 Feet above the Ground Level and above: All risers from underground cables or other conductors which pass through an unrelated conductor or cable level shall be covered or encased by material as described in Rule 54.6–E1 or by a suitable protective covering as described in Rule 22.8 from a distance of 8 feet above the ground to:
a) Not less than 18 inches above supply conductors.
b) Not less than 36 inches above communication conductors for supply risers of 750 volts or less; and
c) Not less than 48 inches above communication conductors for supply risers of 750 - 7500 volts; and
d) Not less than 60 inches above communication conductors for supply risers of more than 7500 volts.
When iron or steel pipe, or other material not meeting the minimum insulating efficiency as specified in Rule 22.8–B is used it shall be terminated or covered by suitable protective covering where within a vertical distance of 8 feet from communication conductors or cables, or unprotected supply conductors.
(3) Covering Joints: Where two sections of suitable protective covering join together (at joints) they shall be covered to prevent exposing the underground cables or other conductors by:
a) The extension of either or both such coverings; or
b) A coupling of equal material; or
c) A strap of equal material.
(4) Climbing Space: Protective coverings for risers, other than wood meeting the requirements of Rule 22.8 , are not allowed in the climbing space.
(5) Clearance between Insulated Conductors: The radial clearances between conductors, specified in Table 2, Cases 16 and 17 , are not required between suitably insulated conductors or cables in the same riser.
(6) Clearance from Centerline and Surface of Poles: Suitably insulated riser conductors or cables can be installed with less than the centerline and surface of pole clearances specified in Table 1, Cases 8 and 9 respectively.
(7)
Metal Poles, Towers and Other Metallic Structures: Protective covering (suitable) is
not required over risers encased in effectively grounded nonclimbable
metal poles or in iron or steel pipe attached to a steel pole, steel tower or
other metallic structure provided the iron or steel pipe is effectively grounded
and is metallically connected to such metal structure.
(8) Hardware (See Rule 91.4)
Note: Revised February 7, 1964 by Decision No. 66707; June 7, 1965 by Decision No. 69071 and September 12, 1973 by Decision No. 81872; February 13, 1980 by Resolution E–1863; March 9, 1988 by Resolution E–3076; January 19, 1994 by Resolution SU–25 and January 15, 2015 by Decision No. 15-01-005.
F.
Termination of Risers and Runs Encased in Metal Conduit
Where risers and runs are covered or encased with
suitable protective covering (Rule 22.8 ) see Rule 54.6–G .
Where risers and runs are encased in metal conduit or other materials not
meeting the minimum insulating efficiency as specified in Rule
22.8–B (suitable
protective covering), e.g. lead risers encased in metal conduit, and such metal
conduit or other conducting material extends within 4 feet of any supply
conductor level the following rules shall apply.
(1) Terminals, Terminal Fittings, and Weather Heads: Grounded portions of terminals, grounded terminal fittings, and grounded weather heads of risers or runs shall not extend above the level of line conductors to which their terminal leads are connected except:
a) Where the line conductors are installed in vertical configuration in partial underground distribution; or
b) Where the line conductors are deadended on the same crossarms that the grounded portions of the terminal, grounded terminal fitting, or grounded weather head is attached and no line conductors supported on those crossarms extend past the grounded portions of the terminals, terminal fitting, or weather head, and no buck arm construction is involved; or
c) Where conductors in excess of 7,500 volts are installed in vertical configuration on crossarms, and the grounded portions of terminals, grounded terminal fittings, or grounded weather heads are mounted on the same crossarms which support the conductors to which the terminal leads are connected.
(2) Climbing Space Obstructions: Terminals, terminal fittings, and weather heads of risers or runs are not allowed in the climbing space.
(3) Clearance from Centerline of Pole: For clearance of energized portions of terminals and their unprotected leads from centerline of pole, see Table 1, Case 8 .
EXCEPTION: In partial underground distribution ( Rule 22.5) energized portions of the terminals may be less than the clearances from centerline of pole specified in Table 1, Case 8, Column E (15 or 18 inches) but shall not be less than 6 inches from the surface of the nonclimbable metal pole and grounded metal surface associated therewith.
(4) Vertical and Radial Clearance from Conductor below: All exposed grounded surfaces of terminals, terminal fittings, weather heads, cables or conduit bends, or suitably insulated cable surfaces of risers and runs shall be at least 18 inches vertically and 18 inches radially from the next unprotected conductor level below. (See Figure 54–4 A & B ).
(5) Protection from the Grounded Metal Conduit, Terminal Fitting, or Weather Head at the Upper End of Vertical Runs or Risers on Wood Poles: Any exposed grounded metal conduit, grounded terminal fitting, or grounded weather head at the upper end of the vertical run or riser on wood poles within distances from the centerline of pole less than as specified in Table 1, Case 8, shall be protected by a wood crossarm or wood block placed above it at a distance not exceeding 4 inches.
EXCEPTIONS: The wood block may be omitted if the exposed grounded metal conduit, grounded terminal fitting, or grounded weather head at the upper end of a vertical run or riser of 750 volts or less is:
a) On the same side of a pole as, and not more than one foot below a transformer; or
b) Not more than 6 inches and not less than 3 inches below the lowest conductor of a rack, and such conduit, fitting, or weather head is approximately centered in the vertical plane under the rack.
(6) Exposed Suitably Insulated or Grounded Surfaces: Exposed suitably insulated or grounded portions of cable, conduit bends, terminal fittings, terminals, and weather heads, located at the upper end of vertical runs or risers supported on climbable poles or structures should be arranged with as little exposed surface as practicable. Such cable or conduit bends are not required to be covered by a suitable protective covering (See Figure 54–4 A & B ) provided that no portion of their exposed surfaces are within the climbing space.
(7) 0 - 750 Volt Terminal Fittings and Weather Heads: The grounded terminal fittings, grounded weather heads, and unprotected cables or leads to and from risers or runs of 0 - 750 volts installed on the surfaces of poles shall not be or pass within the climbing space, but may have a clearance of less than 15 inches from centerline of pole ( Table 1, Case 8 ) and less than 3 inches from the surface of pole or crossarm ( Table 1, Case 9 ). It is recommended that cables from such terminal fittings and weather heads be suitably insulated and, where practicable, carried as protected lateral runs on the bottom surface of crossarms (See Rule 54.6–C ).
(8) Vertical Clearances from Lead Wires and Drip Loops to Other Conductors: The vertical clearances between the lowest point of lead wires (See unprotected conductor Figure 54–4 A & B ) of a riser or run (vertical or lateral) and the next conductor level below shall conform to the requirements specified in Rule 54.4–C6 . For the vertical clearances between supply drip loops and a communication conductor level below see Rule 92.1–F3 .
Note: Revised February
7, 1964 by Decision No. 66707; March 29, 1966
by Decision No. 70489; July 26, 1966 by
Decision No. 71009; August 9, 1966
by Decision No. 71094; September 18,
1967 by Decision No. 72984; May 22, 1990 by Resolution SU–5
and January 19, 1994
by Resolution SU–25.
G.
Termination of Risers and Runs Covered with Suitable Protective Covering
For termination of risers and runs encased in metal conduit or other materials
not meeting the minimum insulating efficiency as specified in Rule
22.8–B (suitable
protective covering) and which extend within 4 feet of any supply conductor
level see Rule
54.6–F .
Where risers and runs are covered or encased with suitable protective covering
(Rule
22.8 ) the following
rules shall apply.
(1) Grounded Portions of Termination Apparatus (Terminals, Potheads, Stress Cones, etc.): Grounded portions of the termination apparatus of risers or runs shall not extend above the level of line conductors to which their terminal leads are connected except:
a) where line conductors are deadended on the same crossarm or bracket that the termination apparatus is attached, and no line conductors supported on that crossarm or bracket extend past the grounded portion of the termination apparatus, and no buck arm construction is involved; or
b) where line conductors are installed in vertical or triangular configuration and the grounded portions of the termination apparatus are mounted on the same crossarms, or other supports, which support the line conductors to which the terminal leads are connected.
(2) Climbing Space Obstructions: Termination apparatus (terminals, potheads, stress cones, etc.) of risers or runs are not allowed in the climbing space.
(3) Clearance from Centerline of Pole: For clearance of energized portions of terminals (see Figure 54–4 A and B ) and their unprotected leads from centerline of pole, see Table 1, Case 8 .
(4) Vertical and Radial Clearance from Conductors below: All exposed grounded surfaces of termination apparatus (terminals, potheads, stress cones, etc.), cables or conduit bends, or suitably insulated cable surfaces of risers and runs, shall be at least 18 inches vertically and 18 inches radially from the next unprotected conductor level below (see Figure 54–4 A and B ).
(5) Exposed Suitably Insulated or Grounded Cable: Exposed suitably insulated or grounded portions of cable located at the upper end of vertical runs or risers (see Figure 54–4 A and B ) supported on climbable poles or structures are not required to be covered by a suitable protective covering provided that no portion of their exposed surfaces are within the climbing space.
(6)
Vertical Clearance from Lead Wires and Drip Loops to Other
Conductors: The
vertical clearances between the lowest point of lead wires (see unprotected
conductor Figure 54–4 A and B ) of a riser or run (vertical or lateral) and the next
conductor level below shall conform to the requirements specified in Rule
54.4–C6 . For the
vertical clearances between supply drip loops and a communication conductor
level below see Rule 92.1–F3 .
The suitably insulated cables at the upper end of vertical runs and risers can
be installed with less than the radial clearances between conductors specified
in Table
2, Cases 16 and 17 ,
and with less than the centerline and surface of pole clearances specified in Table
1, Cases 8 and 9
respectively.
Note: Added January 19, 1994
by Resolution SU–25.
H.
Clearances from Hardware on Wood Poles or Wood Structures
On wood poles or wood structures, all ground wires, conductor or cable sheaths
(concentric wire, metallic braids and tapes, or other metallic coverings),
metallic conduits of risers or runs and the metallic hardware used for
attaching such conduits, and metallic hardware used for attaching wood and
U–shaped plastic ground moulding (excluding plastic conduit) to wood poles or
wood structures shall have a clearance of not less than 1.5 inches from guy
hardware, bolts, braces, pole steps, and other metallic hardware not associated
with the risers or runs. In cases where it is not practicable to obtain at
least 1.5 inches of air–gap and creepage distance,
suitable insulating material (sheeting, conduit, etc.) meeting the minimum
insulating efficiency, as required by Rule 22.8–B , of 1100 kV/in (1.1 kV/mil) shall
be used to provide the necessary creepage distance of
1.5 inches.
Note: Revised
February 7, 1964 by Decision No. 66707; March 29, 1966
by Decision No. 70489; July 26, 1966 by
Decision No. 71009; August 9, 1966
by Decision No. 71094; September 18,
1967 by Decision No. 72984; May 22, 1990 by Resolution
SU–5 and Renumbered
January 19, 1994 by Resolution SU–25.
I. Attachment of Protective Covering
Protective covering shall be attached to poles, structures, crossarms, and other supports by means of corrosion–resistant materials (straps, plumbers tape, lags, nails, staples, screws, bolts, etc.) which are adequate to maintain such covering in a fixed position.
Where such covering consists of wood moulding, rigid plastic moulding, or other suitable protective moulding, the distance between the attachment materials (straps, plumbers tape, lags, nails, staples, screws, bolts, etc.) shall not exceed 36 inches on either side of the moulding.
When moulding is utilized that is subject to expansion due to temperature variation, a gap shall be provided between each section (at joints). All gaps between sections shall be covered by material equal to the moulding being utilized to prevent contact with conductors or cables covered by such moulding.
When building wood box moulding, to prevent damage to the covered cable or conductor, due care shall be exercised to avoid the possibility of nails protruding through any inner surface of such covering.
Note: Revised January 6, 1968 by Decision No. 73455 and January 19, 1994 by Resolution SU–25.