Change List for this Rule


Original Version
Rule 54.9-E1


54.9-E1)    With Guard Arm Below Conductors of 750-20,000 Volts:  The vertical clearance between the top conductor in a rack group and conductors of 750-20,000 volts at the next conductor level above, may be less than 6 feet but shall be not less than 4 feet.  If a clearance of less than 6 feet is used, all of the following requirements:

 

A wood guard arm not less than 48 inches long shall be installed directly above and parallel to the top line conductor of such a rack group;

Conductors in such a rack group, which are so guarded, shall not be attached to more than one side (there being four sides) of any pole; and

No service drop conductors supported on such rack shall pass between the surface of pole and the vertical plane of the line conductors.  Any service drop conductors attached to and supported by the line conductors shall have a clearance of not less than 15 inches from surface of pole.  (See App. G, Fig 43.)

 

Each guard arm and its pole attachments are required by Rule 46 to withstand a vertical load of 200 pounds at either end.

 

Strikeout and Underline Version
Rule 54.9-E1

54.9-E1)    With Guard Arm Below Conductors of 750- 20,000 21,000 Volts:  The vertical clearance between the top conductor in a rack group and conductors of 750-20,000 21,000  volts at the next conductor level above, may be less than 6 feet but shall be not less than 4 feet.  If a clearance of less than 6 feet is used, all of the following requirements:

 

A wood guard arm not less than 48 inches long shall be installed directly above and parallel to the top line conductor of such a rack group;

Conductors in such a rack group, which are so guarded, shall not be attached to more than one side (there being four sides) of any pole; and

No service drop conductors supported on such rack shall pass between the surface of pole and the vertical plane of the line conductors.  Any service drop conductors attached to and supported by the line conductors shall have a clearance of not less than 15 inches from surface of pole.  (See App. G, Fig 43.)

 

Each guard arm and its pole attachments are required by Rule 46 to withstand a vertical load of 200 pounds at either end.

 

Final Version
Rule 54.9-E1


54.9-E1)    With Guard Arm Below Conductors of 750-21,000 Volts:  The vertical clearance between the top conductor in a rack group and conductors of 750-21,000  volts at the next conductor level above, may be less than 6 feet but shall be not less than 4 feet.  If a clearance of less than 6 feet is used, all of the following requirements:

 

A wood guard arm not less than 48 inches long shall be installed directly above and parallel to the top line conductor of such a rack group;

Conductors in such a rack group, which are so guarded, shall not be attached to more than one side (there being four sides) of any pole; and

No service drop conductors supported on such rack shall pass between the surface of pole and the vertical plane of the line conductors.  Any service drop conductors attached to and supported by the line conductors shall have a clearance of not less than 15 inches from surface of pole.  (See
App. G, Fig 43.)

 

Each guard arm and its pole attachments are required by Rule 46 to withstand a vertical load of 200 pounds at either end.