Original Version
Rule 56.4-E
56.4-E) From Poles
Where passing guys are less than 15 inches from surface of pole
and less than 8 feet below supply conductors of less than 20,000 volts supported
on the same pole, such guys shall be sectionalized, in addition to the normal
sectionalization required by Rule 56.6, by means of insulators in accordance
with Rule 56.6-A as though attached to the pole or structure.
Strikeout and Underline Version
Rule 56.4-E
56.4-E) From Poles
Where passing guys are less than 15 inches from surface of
pole and less than 8 feet below supply conductors of less than 20,000
21,000 volts supported on the same pole, such guys shall be sectionalized,
in addition to the normal sectionalization required by Rule 56.6, by means
of insulators in accordance with Rule 56.6-A as though attached to the pole
or structure.
Final Version
Rule 56.4-E
56.4-E) From Poles
Where passing guys are less than 15 inches from surface of
pole and less than 8 feet below supply conductors of less than 21,000 volts
supported on the same pole, such guys shall be sectionalized, in addition
to the normal sectionalization required by Rule 56.6, by means of insulators
in accordance with Rule 56.6-A as though attached to the pole or structure.