Rule 58.3-B4b


58.3-B4b)    Line conductors less than 10 inches below cases: Where a transformer case is unusually long, a crossarm supporting line conductors of 0-750 volts may be used as a heel arm or such conductors on an arm may be less than 10 inches below the transformer case or the hangers) provided all of the following conditions are met:

 

No more than a single transformer with lower voltage of 0-750 volts is supported on the pole at the same level;

The vertical clearances between conductors on the hanger arm and such line arm below shall not be less than as specified in Table 2, Cases 9 to 13;

It is not practicable to obtain the clearance of at least 10 inches specified in Rule 58.3-B3;

Such 0-750 volt conductors clear the transformer case by not less than 15 inches horizontally;

Service drops are not run from the crossarm supporting 0-750 volts conductors at that location; and

The vertical clearance of 0-750 volt conductors below the lowest point of the transformer primary leads is not less than

 

18 inches for primary leads of 750-7500 volts,
24 inches for primary leads of 7500-20,000 volts,
36 inches for primary leads of 20,000-35,000 volts.

 


Strikeout and Underline Rule
Rule 58.3-B4b


58.3-B4b)    Line conductors less than 10 inches below cases: Where a transformer case is unusually long, a crossarm supporting line conductors of 0-750 volts may be used as a heel arm or such conductors on an arm may be less than 10 inches below the transformer case or the hangers) provided all of the following conditions are met:

 

No more than a single transformer with lower voltage of 0-750 volts is supported on the pole at the same level;

The vertical clearances between conductors on the hanger arm and such line arm below shall not be less than as specified in Table 2, Cases 9 to 13;

It is not practicable to obtain the clearance of at least 10 inches specified in Rule 58.3-B3;

Such 0-750 volt conductors clear the transformer case by not less than 15 inches horizontally;

Service drops are not run from the crossarm supporting 0-750 volts conductors at that location; and

The vertical clearance of 0-750 volt conductors below the lowest point of the transformer primary leads is not less than

 

18 inches for primary leads of 750-7500 volts,
24 inches for primary leads of 7500-
20,00021,000 volts,
36 inches for primary leads of
20,000 21,000-35,000 volts.

 

Final Rule
Rule 58.3-B4b


58.3-B4b)    Line conductors less than 10 inches below cases: Where a transformer case is unusually long, a crossarm supporting line conductors of 0-750 volts may be used as a heel arm or such conductors on an arm may be less than 10 inches below the transformer case or the hangers) provided all of the following conditions are met:

 

No more than a single transformer with lower voltage of 0-750 volts is supported on the pole at the same level;

The vertical clearances between conductors on the hanger arm and such line arm below shall not be less than as specified in
Table 2, Cases 9 to 13;

It is not practicable to obtain the clearance of at least 10 inches specified in
Rule 58.3-B3;

Such 0-750 volt conductors clear the transformer case by not less than 15 inches horizontally;

Service drops are not run from the crossarm supporting 0-750 volts conductors at that location; and

The vertical clearance of 0-750 volt conductors below the lowest point of the transformer primary leads is not less than

 

18 inches for primary leads of 750-7500 volts,
24 inches for primary leads of 7500-21,000 volts,
36 inches for primary leads of 21,000-35,000 volts.