58.3-B3e)    New Rule

Strikeout and Underline Rule
Rule 58.3-B3e


58.3-B3e)    From 7500-21,000 Volt conductor Above:  The clearance between unergized metal parts of transformers and 7500-21,000 volt conductors above shall be not less than 18 inches vertically or 18 inches horizontally except that the vertical clearance shall be not less than 30 inches from a conductor at the top of pole as in Rule 54.4-Db8.


Final Rule
Rule 58.3-B3e


58.3-B3e)    From 7500-21,000 Volt conductor Above:  The clearance between unergized metal parts of transformers and 7500-21,000 volt conductors above shall be not less than 18 inches vertically or 18 inches horizontally except that the vertical clearance shall be not less than 30 inches from a conductor at the top of pole as in Rule 54.4-Db8.