Change List for this Rule

 

Original Version
Rule 86.4-E

 

86.4-E.    From Poles

 

Where guys passing poles supporting supply conductors are less than 15 inches from surface of pole and less than 8 feet below supply conductors of less than 20,000 volts supported on such pole, the guys shall be sectionalized, in addition to the normal sectionalization required by Rule 86.6, by means of insulators in accordance with Rule 86.6-B2 as though attached to the pole or structure.


Strikeout and Underline Version
Rule 86.4-E

 

86.4-E.    From Poles

 

Where guys passing poles supporting supply conductors are less than 15 inches from surface of pole and less than 8 feet below supply conductors of less than 21,000 20,000 volts supported on such pole, the guys shall be sectionalized, in addition to the normal sectionalization required by Rule 86.6, by means of insulators in accordance with Rule 86.6-B2 as though attached to the pole or structure.


Final Version
Rule 86.4-E

 

86.4-E.    From Poles

 

Where guys passing poles supporting supply conductors are less than 15 inches from surface of pole and less than 8 feet below supply conductors of less than 21,000 volts supported on such pole, the guys shall be sectionalized, in addition to the normal sectionalization required by Rule 86.6, by means of insulators in accordance with Rule 86.6-B2 as though attached to the pole or structure.