Original Version
Rule 86.4-E
86.4-E. From Poles
Where guys passing poles supporting supply conductors are less
than 15 inches from surface of pole and less than 8 feet below supply conductors
of less than 20,000 volts supported on such pole, the guys shall be sectionalized,
in addition to the normal sectionalization required by Rule 86.6, by means
of insulators in accordance with Rule 86.6-B2 as though attached to the pole
or structure.
Strikeout and Underline Version
Rule 86.4-E
86.4-E. From Poles
Where guys passing poles supporting supply conductors are less
than 15 inches from surface of pole and less than 8 feet below supply conductors
of less than 21,000 20,000 volts supported on such
pole, the guys shall be sectionalized, in addition to the normal sectionalization
required by Rule 86.6, by means of insulators in accordance with Rule 86.6-B2
as though attached to the pole or structure.
Final Version
Rule 86.4-E
86.4-E. From Poles
Where guys passing poles supporting supply conductors are
less than 15 inches from surface of pole and less than 8 feet below supply
conductors of less than 21,000 volts supported on such pole, the guys shall
be sectionalized, in addition to the normal sectionalization required by
Rule 86.6, by means of insulators in accordance with Rule 86.6-B2 as though
attached to the pole or structure.