General Order 95
 Section VIII
 Detailed Construction Requirements for Communication Lines
 (Class C Circuits)
 
86.6    Sectionalizing and Grounding Requirements
   
The general requirements governing the sectionalizing of guys
 by means of insulators are based upon the exposure or proximity of the guys
 to supply conductors. For definition of guys exposed and guys in proximity
 to supply conductors see Rules 21.5–C and
D
 respectively (see also Appendix  G, Figures 
44
 and 45
). The following requirements shall apply to the treatment  and sectionalizing
of guys.
    
    
    
A.    Where Not Exposed to Supply Conductors
            
    
Guys attached to or passing poles or structures supporting
 only communication conductors need not be sectionalized or grounded, provided
 such guys are not exposed to supply conductors of 250 - 22,500 volts and
are not in proximity to supply conductors of 0 - 35,500 volts.
          
        
Note:    Revised
 March 29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094
 and November 20, 1979 by Decision No. 91030.
                                                                       
                                  
B.    Sectionalized Because of Exposure
 or Proximity to Supply Conductors
           
                        
            
 (1)    Overhead Guys Exposed to Supply Conductors of 250 - 22,500 Volts:
  Ungrounded overhead guys which are exposed to supply conductors of 250
- 22,500 volts, and which are not in proximity to supply conductors of 0
- 22,500 volts shall be sectionalized by means of insulators located as specified 
in Rule 86.7–A1
 (see Appendix G,
Figure 44
).
                
        
Note:    Revised March 29, 1966 by
Decision  No. 70489 and August 9, 1966 by Decision No. 71094.
                               
              
 (2)    Guys in Proximity: Every overhead or anchor guy, any portion of
which is in proximity to a wood pole and supply conductors of 0 - 35,500
volts (see Appendix G, Figures 
45
, 48
 and 49
) shall be sectionalized by means of insulators as specified in 
Rule 86.7–A2
 or Rule 86.7–B
, and no portion in proximity to such supply conductors shall be grounded.
Excepted from this requirement are anchor guys, and grounded overhead guys,
which are attached to poles at a level less than 8 feet but not less than
6 feet below the level of supply conductors provided the level of the guy
attachment is at or below the level of communication cable messenger attached
to the same pole (see Appendix G, Figures 
48a
 and 49f
).
                    
        
Also excepted from this requirement are anchor
 guys, and grounded overhead guys, which are attached to poles at a level
less than 6 feet but not less than 4 feet below the level of supply conductors
 of 0 - 750 volts provided such guys are extensions of or attached to a cable
 messenger, are in the same vertical plane (or extension thereof) as the
messenger,  and are below the guard arms required by 
Rule 87.7–B
 for such a messenger  (see 
Appendix G, Figure 48a
).
                        
        
Note:    Revised
 March 29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094
 and November 20, 1979 by Decision No. 91030.
                                                                       
                                  
 C.    Guys Exposed to Supply Conductors of 22,500 Volts or 
More 
                                                    
    
Portions of guys exposed to supply
conductors of 22,500 volts or more shall be securely grounded, and such guys
need not be sectionalized unless sectionalization is required by 
Rule 86.6–B2
 because of proximity to supply conductors of 0 - 35,500 volts (see 
Appendix G, Figure 52c
).
                              
        
Note:    Revised March
 29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094 and
November 20, 1979 by Decision No. 91030 and March 9, 1988 by Resolution E–3076.
                                                           
                            
D.    Guys Attached to Grounded Poles or Structures
                                                                
    
Guys attached to securely grounded
 metal pole or structures are not required to be sectionalized except as
required  by Rule 86.6–B2
 because of proximity to supply conductors of less than 35,500  volts supported
on wood poles.
                                    
        
Note:    Revised
 March 29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094
 and November 20, 1979 by Decision No. 91030.
                                                                       
                                  
E.    Anchor
 Guys through Supply Conductor Levels
An anchor guy which passes
 through the level of supply conductors at positions other than between pole
 pin positions or outside of the outer pin positions shall have insulators
 above and below the level of supply conductors at locations as specified
in Rule 86.7–B
 (see Appendix G, Figure 49d
).