54.10-B6) From Non-climbable Street Lighting or Traffic Signal Poles Standards:
Multi-conductor cables passing unattached shall clear non- climbable street lighting and traffic signal poles, or standards, including mastarms brackets, and lighting fixtures; a radial distance of 15 inches as specified in Table 1, Case 10, Column D; except when the conductors are mechanically protected from abrasion by materials specified in Rule 22.2. Such mechanical protection shall extend 15 inches in each direction along the cable from center line of pole, standard, attaching mastarms or fixture; whether passing above, below or alongside. The conductors shall be installed in such a manner so as not to interfere with light distribution from lighting fixtures and shall not hamper workmen changing lamps or maintaining equipment.
Final Version
Rule 54.10-B6
54.10-B6) From Non-climbable Street Lighting or Traffic Signal Poles Standards:
Multi-conductor cables passing unattached shall clear non- climbable street lighting and traffic signal poles, or standards, including mastarms brackets, and lighting fixtures; a radial distance of 15 inches as specified in Table 1, Case 10, Column D; except when the conductors are mechanically protected from abrasion by materials specified in Rule 22.2. Such mechanical protection shall extend 15 inches in each direction along the cable from center line of pole, standard, attaching mastarms or fixture; whether passing above, below or alongside. The conductors shall be installed in such a manner so as not to interfere with light distribution from lighting fixtures and shall not hamper workmen changing lamps or maintaining equipment.