Change List for this Rule

 

Original Version

Rule 35

 

35    Tree Trimming

 

Where overhead wires pass through trees, safety and reliability of service demand that a reasonable amount of tree trimming be done in order that the wires may clear branches and foliage.

 

Trees so located that they can fall into a crossing span or into any span that could communicate the trouble to a crossing span shall be removed wherever practicable. (see Appendix E, page 2)

 

Strikeout and Underline Version

Rule 35

 

35    Tree Trimming

 

Where overhead wires pass through trees, safety and reliability of service demand that a reasonable amount of tree trimming be done in order that the wires may clear branches and foliage.  Trees so located that they can fall into a crossing span or into any span that could communicate the trouble to a crossing span shall be removed wherever practicable. (see Appendix E, page 2)  The minimum clearances established in Table 1, Case 13, measured between line conductors and vegetation under normal conditions, shall be maintained. (Also see Appendix E for tree trimming guidelines).

When a utility has actual knowledge, obtained either through normal operating practices or notification to the utility, dead, rotten and diseased trees or portions thereof, that overhang or lean toward and may fall into a span, should be removed.

Communication and electric supply circuits, energized at 750 volts or less, including their service drops, should be kept clear of limbs and foliage, in new construction and when circuits are reconstructed or repaired, whenever practicable. When a utility has actual knowledge, obtained either through normal operating practices or notification to the utility, that any circuit energized at 750 volts or less shows strain or evidences abrasion from tree contact, the condition shall be corrected by slacking or rearranging the line, trimming the tree or placing mechanical protection on the conductor(s).

EXCEPTIONS:

 

(1)    Rule 35 requirements do not apply to conductors, or aerial cable that complies with Rule 57.4-C, energized at less than 60,000 volts, where trimming or removal is not practicable and the conductor is separated from the tree with suitable materials or devices to avoid conductor damage by abrasion and grounding of the circuit through the tree.

 

(2)    Rule 35 requirements do not apply where the utility has made a "good faith" effort to obtain permission to trim or remove vegetation but permission was refused or unobtainable. A "good faith" effort shall consist of current documentation of a minimum of an attempted personal contact and a written communication, including documentation of mailing or delivery. However, this does not preclude other action or actions from demonstrating "good faith". If permission to trim or remove vegetation is unobtainable and requirements of exception 2 are met, the utility is not compelled to comply with the requirements of exception 1.

 

(3)    The Commission recognizes that unusual circumstances beyond the control of the utility may result in non-conformance with the rules. In such cases, the utility may be directed by the Commission to take prompt remedial action to come into conformance.

 

Final Version

Rule 35

 

35    Tree Trimming

 

Where overhead wires pass through trees, safety and reliability of service demand that a reasonable amount of tree trimming be done in order that the wires may clear branches and foliage.  The minimum clearances established in Table 1, Case 13, measured between line conductors and vegetation under normal conditions, shall be maintained. (Also see Appendix E for tree trimming guidelines).

 

When a utility has actual knowledge, obtained either through normal operating practices or notification to the utility, dead, rotten and diseased trees or portions thereof, that overhang or lean toward and may fall into a span, should be removed.

 

Communication and electric supply circuits, energized at 750 volts or less, including their service drops, should be kept clear of limbs and foliage, in new construction and when circuits are reconstructed or repaired, whenever practicable. When a utility has actual knowledge, obtained either through normal operating practices or notification to the utility, that any circuit energized at 750 volts or less shows strain or evidences abrasion from tree contact, the condition shall be corrected by slacking or rearranging the line, trimming the tree or placing mechanical protection on the conductor(s).

 

EXCEPTIONS:

 

(1)    Rule 35 requirements do not apply to conductors, or aerial cable that complies with Rule 57.4-C, energized at less than 60,000 volts, where trimming or removal is not practicable and the conductor is separated from the tree with suitable materials or devices to avoid conductor damage by abrasion and grounding of the circuit through the tree.

 

(2)    Rule 35 requirements do not apply where the utility has made a "good faith" effort to obtain permission to trim or remove vegetation but permission was refused or unobtainable. A "good faith" effort shall consist of current documentation of a minimum of an attempted personal contact and a written communication, including documentation of mailing or delivery. However, this does not preclude other action or actions from demonstrating "good faith". If permission to trim or remove vegetation is unobtainable and requirements of exception 2 are met, the utility is not compelled to comply with the requirements of exception 1.

 

(3)    The Commission recognizes that unusual circumstances beyond the control of the utility may result in non-conformance with the rules. In such cases, the utility may be directed by the Commission to take prompt remedial action to come into conformance.