Rule 86.4-A3


86.4-A3    New Rule

Strikeout and Underline Version
Rule 86.4-A3


86.4-A3)    Above Swimming Pools: Guys shall have vertical clearances above the highest water level of the pool of not less than 16 feet.

No communications guy may be installed less than 16 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being within 8 feet radially of the diving board or platform and over the water surface of the pool.

No communications guy may be installed less than 8 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being the area within 3 feet radially of the diving board or platform and not over the water surface of the pool.


Final Version
Rule 86.4-A3


86.4-A3)    Above Swimming Pools: Guys shall have vertical clearances above the highest water level of the pool of not less than 16 feet.

No communications guy may be installed less than 16 feet vertically above the horizontal plane through a diving board or platform, the area of such plane being within 8 feet radially of the diving board or platform and over the water surface of the pool.