Original Version
Rule 91.3
91.3 Stepping
All jointly used poles which support supply conductors shall
be provided with pole steps if vertical runs or risers of supply or communication
conductors are attached to the surface of such poles; except that those jointly
used poles which carry circuits operated only by one party are not required
to be stepped provided any vertical runs or risers on the surface of such
poles are covered by a suitable protective covering of wood throughout their
length above a point 8 feet from the ground line. The lowest step shall
be not less than 7 feet 6 inches from the ground line and above this point
steps shall be placed, with spacing between steps on the same side of pole
not exceeding 36 inches, at least to the height of the upper end of the topmost
run or riser attached to the surface of pole. Steps shall be so placed
that the runs or risers do not interfere with their free use.
Strikeout and Underline Version
Rule 91.3
91.3 Stepping
A.
Use Of Steps
(1) Poles with Vertical Runs or Risers:
All jointly used poles which support supply conductors shall be provided
with pole steps if vertical runs or risers of supply or communication
conductors are attached to the surface of such poles, except
that those jointly used unless the conditions described in the
following subparagraphs (a), (b) or (c) are met:
a) One–Party Poles: Poles
which carry circuits operated and maintained by only one party are not required
to be stepped, provided any vertical runs or risers on the surface of such
poles are covered by a suitable protective covering of wood throughout
their length above a point 8 feet from the ground line. (Refer
to Rule 54.6–E and Rule 84.6–E ) from the ground line to a level not less
than 8 ft. above the ground line, or provided that such poles comply with
the conditions of Rule 91.3–A1b .
b) Communications Runs:
Joint poles with vertical communications runs are not required to be stepped,
provided all of the following conditions are met:
1) The pole has
no pole mounted communication terminals, no risers and no vertical runs (including
ground wires) located within the climbing space, and not more than three
levels of communication line conductors;
2) The
communications levels consist only of drop wire in line cable construction,
span wire supported cables, and messenger–supported cables;
3) The maximum vertical separation between the highest
and lowest line communications levels is not more than 30 inches;
4) The vertical runs other than ground wires consist entirely
of drop wire cables for service drops which extend vertically no more than
one foot above and below the communication line levels.
c) Supply Runs: Joint poles with supply vertical runs are not required to be
stepped provided all of the following conditions are met:
1) All supply circuits on the pole are operated and maintained by only one party.
2) All supply vertical runs other than ground wires are
located entirely above the communication levels.
3) No ground wire runs are located within the climbing
space except those portions which are located above the communications level.
B. Location of Steps
The lowest
step shall be not less than 7 feet 6 inches from the ground line and above
this point steps shall be placed, with spacing between steps on the same
side of the pole not exceeding 36 inches, at least to the height of
the upper end of the topmost run or riser attached to the surface of pole
that conductor level above which only circuits operated and maintained
by one party remain. Steps shall be so placed that runs or risers do not
interfere with the free use of the steps.
Final Version
Rule 91.3
91.3 Stepping
A. Use Of Steps
(1)
Poles with Vertical Runs or Risers: All jointly used poles which support
supply conductors shall be provided with pole steps if vertical runs or risers
are attached to the surface of such poles, unless the conditions described
in the following subparagraphs (a), (b) or (c) are met:
a) One–Party Poles: Poles which carry circuits operated
and maintained by only one party are not required to be stepped, provided
any vertical runs or risers on the surface of such poles are covered by a
suitable protective covering (Refer to Rule 54.6–E and Rule 84.6–E ) from
the ground line to a level not less than 8 ft. above the ground line, or provided
that such poles comply with the conditions of Rule 91.3–A1b .
b) Communications Runs: Joint poles with vertical communications
runs are not required to be stepped, provided all of the following conditions
are met:
1) The pole has no pole mounted communication terminals,
no risers and no vertical runs (including ground wires) located within the
climbing space, and not more than three levels of communication line conductors;
2) The communications levels consist only of drop wire
in line cable construction, span wire supported cables, and messenger–supported
cables;
3) The maximum vertical separation between the highest
and lowest line communications levels is not more than 30 inches;
4) The vertical runs other than ground wires consist entirely
of drop wire cables for service drops which extend vertically no more than
one foot above and below the communication line levels.
c) Supply Runs: Joint poles with supply vertical runs
are not required to be stepped provided all of the following conditions are
met:
1) All supply circuits on the pole are operated and maintained
by only one party.
2) All supply vertical runs other than ground wires are
located entirely above the communication levels.
3) No ground wire runs are located within the climbing
space except those portions which are located above the communications level.
B. Location of Steps
The lowest step shall be not less than 7 feet 6 inches from the ground line
and above this point steps shall be placed, with spacing between steps on
the same side of the pole not exceeding 36 inches, at least to that conductor
level above which only circuits operated and maintained by one party remain.
Steps shall be so placed that runs or risers do not interfere with the free
use of the steps.