Rule 86.6-C

 

86.6-C.    Exposed To Supply Conductors Of More Than 22,500 Volts

 

Portions of guys exposed to supply conductors of more than 22,500 volts shall be securely grounded and such guys need not be sectionalized, unless sectionalization is required by Rule 86.6-B2 because of proximity to supply conductors of 0-35,500 volts. (See App. G, Fig. 52c.)

 

Strikeout and Underline Version

Rule 86.6-C

 

86.6-C.    Guys Exposed To Supply Conductors Of More Than 22,500 Volts

 

Portions of guys exposed to supply conductors of more than 22,500 volts shall be securely grounded and such guys need not be sectionalized, unless sectionalization is required by Rule 86.6-B2 because of proximity to supply conductors of 0-35,500 volts. (See App. G, Fig. 52c.)

 

Final Version

Rule 86.6-C

 

86.6-C    Guys Exposed To Supply Conductors Of More Than 22,500 Volts

 

Portions of guys exposed to supply conductors of more than 22,500 volts shall be securely grounded and such guys need not be sectionalized, unless sectionalization is required by Rule 86.6-B2 because of proximity to supply conductors of 0-35,500 volts. (See App. G, Fig. 52c