58.3-B3e)    From 7,500-22,500 Volt Conductors Above: The clearance between un-energized metal parts of transformers and 7,500-22,500 volt conductors above shall be not less than 18 inches vertically or 18 inches horizontally except that the vertical clearance shall be not less than 30 inches from a conductor at the top of pole as in Rule 54.4-D8b.

 

Strikeout and Underline Version

Rule 58.3-B3e

 

58.3-B3e)    From 7,500-22,500 Volt Conductors Above: The clearance between un-energized metal parts of transformers and 7,500-22,500 volt conductors above shall be not less than 18 inches vertically or 18 inches horizontally except that the vertical clearance shall be not less than 30 inches from a conductor at the top of pole as in Rule 54.4-D8b.

EXCEPTION: The vertical clearance shall not be less than 30 inches from a conductor at the top of pole as in Rule 54.4-D8.

 

Final Version

Rule 58.3-B3e

 

58.3-B3e)    From 7,500-22,500 Volt Conductors Above: The clearance between un-energized metal parts of transformers and 7,500-22,500 volt conductors above shall be not less than 18 inches vertically or 18 inches horizontally.

EXCEPTION: The vertical clearance shall not be less than 30 inches from a conductor at the top of pole as in
Rule 54.4-D8.