General Order 95
 Section VIII
 Detailed Construction Requirements for Communication Lines
 (Class C Circuits)
 
84.6    Vertical and Lateral Conductors
     
A.    Open Wire
         
    
Open wire conductors from one level to another level on a 
 pole or structure shall not pass within the climbing space (see 
rule 84.7
),  and shall not pass between conductors of any other circuit except between 
 pole–pin conductor positions.
         
        
B.    Ground Wires 
         
                     
    
Ground wires, other than lightning protection wires 
 not attached to equipment or ground wires on grounded structures, shall be
 covered by metal pipe or suitable covering of wood or metal, or of plastic 
 conduit material as specified in Rule 22.8–A
, for a distance above ground  sufficient to protect against mechanical injury,
but in no case shall such  distance be less than 7 feet. Such covering may
be omitted providing the ground wire in this 7 foot section has a mechanical
strength at least equal to the strength of No. 6 AWG medium–hard–drawn copper.
               
        
        
Portions of ground wires which are on the surface 
 of wood poles and within 6 feet vertically of unprotected supply conductors 
 supported on the same pole, shall be covered with a suitable protective covering
 (see Rule 22.8
   ).
                   
        
Note: Revised May 1, 1961 by Resolution No. E–1088, February 13, 1980 by Resolution No. E–1863 and January 19, 1994 by Resolution SU–25.
C.    Lateral Conductors
                   
                                         
    
Lateral runs of suitably insulated communication 
 conductors on poles which support supply conductors may cross the pole or 
 run laterally from the pole at a clearance less than the 15 inches from center
 line specified in Table 1,
Case 8
, provided those portions of such runs less  than 15 inches from center line
of pole and located less than 6 feet below  the level of unprotected supply
conductors are supported by and underneath  the bottom surface of crossarm
or guard arm, or are supported on the side  of such crossarm or guard arm
not less than 2 inches below the top surface  thereof.
                         
        
D.    Vertical Runs
                                                     
    
Vertical runs of communication wires 
 or cables supported on the surface of wood poles or structures, shall be 
covered by a suitable protective covering (see 
  Rule 22.8
   ) where within a vertical distance of 3 feet above or 6 feet below unprotected 
 supply conductors supported on the same pole or structure.Vertical runs of
 communication wires or cables on the surface of a wood pole shall be covered
 by a suitable protective covering where within a 6 foot radius of any other
 pole supporting supply conductors except that those portions of such runs
 which are more than 3 feet above or 6 feet below the level of unprotected
 supply conductors need not be covered. Cable and drop wire runs to or from
 terminal boxes are exempted from these requirements for covering, under
the  following conditions:
                               
        
        
Where guard arms are installed above
messengers or longitudinal cables which are less than 6 feet below but not
less than 4 feet below unprotected supply conductors of 0 - 750 volts, or
where cables are supported on crossarms at not less than 15 inches from center
line of pole, in which cases any portion of metal sheathed cable runs on
the surface of pole below the guard arm and in the same quadrant as the longitudinal
cable (see Appendix G, Figure 87
), or below and on the same side of the pole with a crossarm which supports
a longitudinal cable, need not be covered.
                                   
        
        
Runs of bridled conductors, 
 attached to surface of pole, need not be covered provided such runs are below
 the guard arm and in the same quadrant as the longitudinal cable, or where
 such runs are below and on the same side of pole with a cable arm and are
 not in the climbing space, or are connected to service drops which are placed
 in accordance with the provisions of 
Rule 84.8–B2b
.
                                       
        
        
Where bridled runs are not
required to be covered by these rules, they shall be supported by bridle hooks
or rings spaced at intervals of not more than 24 inches.
                                           
        
        
Vertical runs shall 
 be treated as risers (see Rule 87.7–D
) where within a distance of 8 feet from the ground line.
                                               
        
        
Runs which terminate 
 in the top of enclosures which afford ample mechanical protection to the 
runs may extend within 8 feet of the ground but not less than 6 feet of the 
ground without being treated as risers.
                                                   
        
        
EXCEPTION: Fiber optic cable transitions shall meet the requirements of Rule 87.10.
Note:    
 Revised June 7, 1965 by Decision No. 69071, January 19, 1994 by Resolution 
 SU–25, October 9, 1996 by Resolution SU–40 
  and January 13, 2006 
by Decision 
            No.  
            05-01-030.
                                                                        
                                                                        
  
E.    Intentionally Left Blank (Note: Risers revised
and moved to 87.7–D
)
                                                                        
                                
 Note:     Deleted
October 9, 1996 by Resolution SU–40.
                                                                        
                                                                        
         
                                                
F.    Protective Covering
                                                       
    
    
Protective 
covering shall be attached to poles, crossarms and structures by means of 
 corrosion–resistant straps, lags or staples which are adequate to maintain 
 such covering in a fixed position.
                                                         
    
    
Where such 
 covering consists of hardwood or rigid plastic moulding, the distance between 
 straps, lags or staples shall not exceed three feet on each side and due 
care shall be exercised to avoid the possibility of nails protruding through 
any inner surface.
                                                           
    
    
When U–shaped
moulding is utilized appropriate gaps between sections shall be provided
to permit expansion due to temperature variations and such gaps shall be
covered by corrosion resistant straps to prevent contact with conductors covered
by moulding.