General Order 95
Section VIII
Detailed Construction Requirements
for Communication Lines
(Class C Circuits)
84.4 Clearances
Allowable variations in clearances due to temperature, loading, dead ending, etc., are given in Rules 37 and 38 .
A.
Above Ground
The minimum vertical clearances shall be those
specified in Rule
37 , Table
1 , with the
following modifications:
(1) Across Arid or Mountainous Areas: The clearance of 15 feet specified in Table 1, Case 4, Column B may be reduced to not less than 13 feet over arid or mountainous areas which are not under cultivation and over which there is no likelihood of vehicular travel.
(2) In Rural Districts: The clearance of Table 1, Case 4, Column B may be reduced to not less than 13 feet above ground along thoroughfares in rural districts where no part of the line overhangs any part of the thoroughfare which is ordinarily traveled and where it is unlikely that vehicles will be required to cross under the communication conductors.
(3) Accessible to Pedestrians Only: Communication conductors of not more than 160 volts which transmit not more than 50 watts and communication cables having grounded metal sheaths may have a clearance above ground accessible to pedestrians only less than as specified in Table 1, Case 5, Column B , (10 feet) but not less than 8 feet.
(4) Fenced Railway Rights–of–Way: Railway signal cables between line poles and signaling devices, which are entirely on fenced railway rights–of–way, and which are exposed to vehicular traffic but do not cross thoroughfares, may have clearances above ground less than as specified in Table 1, Column B, Case 4 (15 feet) but not less than 10 feet. Such cables which are entirely on fenced railway rights–of–way and which are in areas accessible to pedestrians only may have clearances above ground less than as specified in Table 1, Column B, Case 5 (10 feet) but not less than 7 feet.
(5) Over Swimming Pools (See Figure 84–1 ):
a) Line Conductors, Cables, Messengers and Span Wires: Crossings of communication line conductors over swimming pools shall be avoided where practicable. Line conductors shall have radial clearances from the top edge of the pool wall and vertical clearances above the highest water level of the pool of not less than 18 feet.Grounded metallic sheathed cables, plastic–jacketed cables with an inner grounded metallic sheath, and grounded messengers and grounded span wires which support cable may have minimum radial and vertical clearances as hereinabove stated of not less than 16 feet. Service drops installed over swimming pools and used in line cable construction may have minimum radial and vertical clearance as hereinabove stated of not less than 14 feet.
b)
Service Drops: Installation
over swimming pools shall be avoided where practicable. Service drops above
swimming pools shall have vertical clearances over the pool and radial
clearances from the edge of the pool wall of not less than 14 feet for public
and commercially operated pools and not less than 10 feet for residential
pools.
No service drop may be installed less than 14 feet vertically over the
horizontal plane through a diving board or platform, the area of such plane
being within 8 feet radially of the diving board or platform and over the water
surface of the pool.
No service drop may be installed less than 10 feet vertically over the
horizontal plane through a diving board or platform, the area of such plane
being the area within 3 feet radially of the diving board or platform and not
over the water surface of the pool.
c)
Communication Guys: Guys
shall have vertical clearances above the highest water level of the pool of not
less than 16 feet.
No communications guy may be installed less than 16 feet vertically over the
horizontal plane through a diving board or platform, the area of such plane
being within 8 feet radially of the diving board or platform and not over the
water surface of the pool.
No communications guy may be installed less than 8 feet vertically over the
horizontal plane through a diving board or platform, the area of such plane
being the area within 3 feet radially of the diving board or platform and not
over the water surface of the pool.
Note: Added January 2, 1962 by Resolution No. E–1109 and Revised November 21, 1990 by Resolution SU–6.
(6) Across or along Public Thoroughfares: Communication conductors over or across public thoroughfares shall have a clearance of 18 feet above ground (Table 1, Case 3, Column B ). A reduced clearance to 16 feet is permitted for the portions of communication conductors where no part of the line overhangs any part of the thoroughfare which is ordinarily traveled, or where the line is behind an established curb, ditch or berm that serves to protect such communication conductors from encroachment by vehicular traffic.
Note: This 16 foot clearance shall not be reduced because of temperature or wind loading as specified in Rule 43 .
Note:
Added November 21, 1990 by Resolution SU–6.
B. Above Railways and Trolley Lines
(1) Which Transport Freight Cars: The clearance specified in Table 1, Case 1, Column B (25 feet) is based upon the maximum height of standard freight cars, 15 feet 6 inches between top of rail and top of running board. This clearance shall in no case be reduced more than 5% because of temperature and loading as specified in Rule 43 .
(2)
Operated by Overhead Trolleys: The clearance specified in Table
1, Case 2, Column B
(26 feet) is based upon a trolley pole throw of 26 feet, the usual maximum
height of a free trolley pole above the rails or other traveled surfaces used
by trolley cars or coaches. Where trolley lines have a maximum trolley throw at
variance with 26 feet the specified clearance shall be increased or may be
reduced accordingly except that in no case shall the clearance be less than 25
feet. See Rule 87.4–B2
for the clearance of grounded cables and messengers.
Where railways operated by overhead trolleys transport freight cars, the
clearance requirements of Rule
84.4–B1 also apply.
C.
Between Conductors
The minimum clearances shall be those specified in Rule
38 , Table
2 (see also Rule
32.2–D ) with the
following modifications:
(1) Open Wire
a) On Related Line and Buck Arms: The clearance of 6 inches specified in Table 2, Case 14, Column C is not required between conductors on line arm and related buck arm where the conductors supported by such arms do not cross.
b)
On Brackets Attached to Crossarms: The radial clearance for
communication line conductors supported on brackets or extensions attached to crossarms at, or outside of, the outer pin or dead–end
positions shall not be less than 3 inches from any other communication line
conductor supported by the same crossarm as specified in Table
2, Case 15, Column C
. Not more than two conductors on the same side of the pole on any crossarm may
be supported on brackets within the outer pin position and below conductors
normally supported on pins.
There shall not be less than a 12 inches vertical separation between
communication conductors supported on brackets within the outer pin positions
on one crossarm and the communication conductors on another crossarm. The vertical
clearances specified in Table 2, Cases 1 to 14, Column C shall be provided between the
conductor on a bracket and the conductor level of any other conductors not
supported on the crossarm to which the bracket is attached.
EXCEPTION: This rule shall not apply to clearances between conductors of the same or similar circuits at points of transposition.
Note:
Revised November 21, 1990 by Resolution SU–6.
c)
Attached Directly to Poles: On poles which carry no crossarms, open wire conductors which are attached to the sides
of poles by means of hooks, knobs or brackets may be placed in any position
within the 3 feet next below the topmost conductor on the pole.The
vertical separation between conductor supports on the same side of pole in this
space of 3 feet shall be not less than 6 inches. Below this point (3 feet below
the topmost conductor) conductors shall be attached to one side of pole only,
not more than 6 conductors shall be so attached, and the vertical separation
between these conductors shall be not less than 12 inches.
On poles which carry communication crossarms only,
one pair of open wire conductors may be attached to opposite sides of the pole
by means of hooks, knobs, or brackets, at a point not less than 2 feet below
the lowest level of conductors supported on crossarms.
Below this point (2 feet below conductors on crossarm) other conductors which
are attached to surface of pole shall be attached to one side of pole only, not
more than six conductors shall be so attached, and their vertical separation
shall be not less than 12 inches.
Branch or tap lines and service drops from conductors attached to poles may be
similarly attached to the face or back of a pole, but not both.
(2)
Duplex, Triplex and Cables: Insulated single conductors, duplex, triplex
and paired conductors are considered cables (see definition, Rule
20.4) and the
clearances for such conductors are specified in Rule
87.4 .
Note: Revised January 15, 2015 by Decision No. 15-01-005.
D.
From Poles and Crossarms
Table
1, Case 8, Column B
specifies a minimum clearance of 15 inches from center line of pole which is
applicable to communication conductors including cables and service drops.
Modifications of this basic 15 inches clearance are specified in Rule
37 and by the
following provisions where conductors are not on poles jointly used for
supporting supply conductors excepting supply service drop clearance
attachments (see Rules 54.8–C2 and 54.8–C3 ).
The clearance of 3 inches specified in Table 1, Case 9, Column B is not intended to apply to
communication conductors.
(1)
Conductors Supported on Crossarms: The 15 inches minimum clearance from
the center line of the pole specified for communication conductors supported on
crossarms may be reduced under the following
condition:
For communication conductors the clearance from center line of pole shall not
be less than 9 inches. This clearance shall apply only to communication
conductors under the following conditions:
a) When supported on a crossarm in the pole top position, and
b)
When
no conductors are supported below such crossarms
except supply service drops on clearance crossarms.
This provision is intended to permit the use of a related buck arm, in which
the climbing space shall conform to the requirements of Rule
84.7–B .
To maintain climbing space, cables or messengers may have clearances less than
15 inches from center line of pole under the following conditions:
1) When placed between crossarms, or
2)
When
placed less than 2 feet below the level of the lowest communication conductor
supported on crossarms.
These cables or messengers are to be placed on one side of the pole only. Any
conductor on a crossarm on the opposite side of the pole that is within 36
inches vertically of the cable or messenger shall be at least 18 inches
horizontally from the vertical plane of such cable or messenger (see Figure
84–2).
Note:
Revised November 21, 1990 by Resolution SU–6.
(2) Conductors Not Supported on Crossarms: Communication conductors which are not supported on crossarms may be attached to poles by means of hooks, knobs, or brackets and thus are not required to be any specified distance from center line of poles provided the clearance between conductors complies with the requirements of Rule 84.4–C1c .The minimum clearance of such conductors from the surface of poles shall be such that suitable insulation is maintained.
(3)
Colinear, Conflicting or Crossing
Lines (See Rule
32.3 ):Where two
communication lines are colinear or otherwise in
conflict or where a pole of one line is interset in
another line at crossings, the clearances of Rule
32.3 and Rule
37 , Table
1, Case 8, Column B
may be modified as follows:
In applying any of the provisions of Rule 84.4–D3 an unobstructed climbing space on
each pole concerned shall be maintained with horizontal dimensions of not less
than 18 inches wide and 30 inches deep for communication conductors.
a) Where Clearance Arms Are Used: Where clearance arms are used to support the conductors of a colinear or conflicting communication line on poles which support only communication conductors, the clearance of such conductors from the center line of pole shall not be less than 15 inches.
Note:
Revised November 21, 1990 by Resolution SU–6.
b) Where Clearance Arms Are Not Used: Communication conductors which in passing another communication pole unattached would be less than 15 inches from the center line of pole or less than 5 inches from the surface of pole shall be attached to the pole in accordance with the provisions of Rules 84.4–C1c and 84.4–D2 .
(4) Conductors Passing Supply Poles and Unattached Thereto: The center line clearance between poles supporting supply conductors and any communication conductors which pass such poles unattached shall be not less than 22 1/2 inches (1 1/2 times the clearance specified in Table 1, Case 8 ), except where the supply pole is within 10 feet of the pole on which the communication conductors are supported.Where poles of the two lines are less than 10 feet apart, clearances not less than as specified in Table 1, Case 8 , shall be maintained.
Note: Resolution E–999
effective October 7, 1958, is rescinded and replaced by new Rule 84.4–D(4)(a); deleted and
revised January 8, 1980 by Decision No. 91186.
a) From Nonclimbable Street Lighting or Traffic Signal Poles or Standards (including mastarms, brackets and lighting fixtures): When passing street lighting, traffic signal poles or standards (including mastarms, brackets and lighting fixtures) a clearance of 12 inches, as specified in Table 1, Case 10, Column B , may be reduced when suitable insulation for the highest voltage of open wire involved and mechanical protection from abrasion is provided where necessary.Such mechanical protection shall extend not less than 15 inches in each direction from centerline of pole, standard, attaching mastarm or fixture, whether passing above, below or alongside.There shall be no interference with light distribution from lighting fixtures and workers shall not be hampered or endangered in the performance of their duties.
Note: Added January
8, 1980 by Decision No. 91186; Revised
March 9, 1988 by Resolution E–3076 and November 6, 1992 by
Resolution SU–15.
(5) Center Line Clearance at Angles in Lines and at Transpositions: The clearance of 15 inches from center line of pole specified in Table 1, Case 8, Column B (and the reduced clearance of 9 inches permitted by Rules 84.4–D1 and 84.4–D3a ) may be reduced at angles in lines and at transposition supports provided that at angles in lines the reductions of the 30 inches and 18 inches widths of climbing spaces shall not exceed the reduction specified in Rule 84.7–A1 , and further provided that the 30 and 18 inches widths of climbing space shall not be reduced at transposition supports (see Figure 84–3 ).
E.
Above alongside or in Immediate Proximity to Buildings, Bridges and Other
Structures
Conductors should be arranged so as not to hamper or endanger firefighters and
workers in performing their duties.The basic
clearances of communication conductors from buildings are specified in Table
1, Cases 6 and 7, Column B
. The horizontal clearance ( Table 1, Case 7 ) shall be maintained until the
vertical clearance ( Table 1, Case 6 ) is attained (see Figure
84–5 ). The
requirements of Table 1, Case 7
, Column B also apply at fire escapes, windows, doors,
and other points at which entrance or exit might be reasonably expected.
Communication cables are not required to be any specified distance from the
sides of buildings, bridges and other structures, but they shall be installed
so that they do not interfere with the free use of fire escapes, windows, doors
and other points at which entrance or exit might be reasonably expected.
The vertical clearance of communication conductors (including cables) above
buildings specified in Table 1, Case 6, Column
B may be reduced to
not less than 2 feet under either of the following conditions:
(1) Over roofs whose slope exceeds 9 inches of rise per 12 inches of run (see Sketch), or
(2)
Over
roofs where the conductor does not overhang the building by more than 6 feet.
See Rule 84.8–C4 for service drop
clearance requirements.
Note: Revised November 21, 1990 by Resolution SU–6; November 6, 1992 by Resolution No. SU–15 and October 9, 1996 by Resolution SU–40.
Note: Revised November 6, 1992 by
Resolution No. SU–15.
G. From Guys and Messengers (See Table 2, Cases 18 and 19, Column C ; also Rules 86.4–C and 87.4 )