General Order 95
Section VIII
Detailed Construction Requirements for Communication Lines
(Class C Circuits)
86.5
Fastenings
Guy wires shall be protected by the use of guy thimbles or their
equivalent where attached to anchor rods or through bolts.
Cedar and other soft–wood poles, around which any guy having
an ultimate strength of 5,000 pounds or more is wrapped, shall be protected
by suitable guy shims. Hooks, lag screws or other equivalent means shall
be used where necessary to prevent the guy from slipping along the pole.