General Order 95
Section VIII
Detailed Construction Requirements for Communication Lines
(Class C Circuits)
86.6 Sectionalizing and Grounding Requirements
The general requirements governing the sectionalizing of guys
by means of insulators are based upon the exposure or proximity of the guys
to supply conductors. For definition of guys exposed and guys in proximity
to supply conductors see Rules 21.5–C and
D
respectively (see also Appendix G, Figures
44
and 45
). The following requirements shall apply to the treatment and sectionalizing
of guys.
A. Where Not Exposed to Supply Conductors
Guys attached to or passing poles or structures supporting
only communication conductors need not be sectionalized or grounded, provided
such guys are not exposed to supply conductors of 250 - 22,500 volts and
are not in proximity to supply conductors of 0 - 35,500 volts.
Note: Revised
March 29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094
and November 20, 1979 by Decision No. 91030.
B. Sectionalized Because of Exposure
or Proximity to Supply Conductors
(1) Overhead Guys Exposed to Supply Conductors of 250 - 22,500 Volts:
Ungrounded overhead guys which are exposed to supply conductors of 250
- 22,500 volts, and which are not in proximity to supply conductors of 0
- 22,500 volts shall be sectionalized by means of insulators located as specified
in Rule 86.7–A1
(see Appendix G,
Figure 44
).
Note: Revised March 29, 1966 by
Decision No. 70489 and August 9, 1966 by Decision No. 71094.
(2) Guys in Proximity: Every overhead or anchor guy, any portion of
which is in proximity to a wood pole and supply conductors of 0 - 35,500
volts (see Appendix G, Figures
45
, 48
and 49
) shall be sectionalized by means of insulators as specified in
Rule 86.7–A2
or Rule 86.7–B
, and no portion in proximity to such supply conductors shall be grounded.
Excepted from this requirement are anchor guys, and grounded overhead guys,
which are attached to poles at a level less than 8 feet but not less than
6 feet below the level of supply conductors provided the level of the guy
attachment is at or below the level of communication cable messenger attached
to the same pole (see Appendix G, Figures
48a
and 49f
).
Also excepted from this requirement are anchor
guys, and grounded overhead guys, which are attached to poles at a level
less than 6 feet but not less than 4 feet below the level of supply conductors
of 0 - 750 volts provided such guys are extensions of or attached to a cable
messenger, are in the same vertical plane (or extension thereof) as the
messenger, and are below the guard arms required by
Rule 87.7–B
for such a messenger (see
Appendix G, Figure 48a
).
Note: Revised
March 29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094
and November 20, 1979 by Decision No. 91030.
C. Guys Exposed to Supply Conductors of 22,500 Volts or
More
Portions of guys exposed to supply
conductors of 22,500 volts or more shall be securely grounded, and such guys
need not be sectionalized unless sectionalization is required by
Rule 86.6–B2
because of proximity to supply conductors of 0 - 35,500 volts (see
Appendix G, Figure 52c
).
Note: Revised March
29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094 and
November 20, 1979 by Decision No. 91030 and March 9, 1988 by Resolution E–3076.
D. Guys Attached to Grounded Poles or Structures
Guys attached to securely grounded
metal pole or structures are not required to be sectionalized except as
required by Rule 86.6–B2
because of proximity to supply conductors of less than 35,500 volts supported
on wood poles.
Note: Revised
March 29, 1966 by Decision No. 70489; August 9, 1966 by Decision No. 71094
and November 20, 1979 by Decision No. 91030.
E. Anchor
Guys through Supply Conductor Levels
An anchor guy which passes
through the level of supply conductors at positions other than between pole
pin positions or outside of the outer pin positions shall have insulators
above and below the level of supply conductors at locations as specified
in Rule 86.7–B
(see Appendix G, Figure 49d
).