Change List for this Rule

 

Original Version
Rule 56.4-E

 

56.4-E.    From Poles

 

Where passing guys are less than 15 inches from surface of pole and less than 8 feet below supply conductors of less than 21,000 volts supported on the same pole, such guys shall be sectionalized, in addition to the normal sectionalization required by Rule 56.6, by means of insulators in accordance with Rule 56.6-A as though attached to the pole or structure.

 

Strikeout and Underline Version
Rule 56.4-E

 

56.4-E.    From Poles

 

Where passing guys are less than 15 inches from surface of pole and less than 8 feet below supply conductors of less than  21,00022,500 volts supported on the same pole, such guys shall be sectionalized, in addition to the normal sectionalization required by Rule 56.6, by means of insulators in accordance with Rule 56.6-A as though attached to the pole or structure.

 

Final Version
Rule 56.4-E

 

56.4-E.    From Poles

 

Where passing guys are less than 15 inches from surface of pole and less than 8 feet below supply conductors of less than 22,500 volts supported on the same pole, such guys shall be sectionalized, in addition to the normal sectionalization required by Rule 56.6, by means of insulators in accordance with Rule 56.6-A as though attached to the pole or structure.