Rule 54.4-D6b
54.4-D6b) More Than 750 Volts supported on climbable poles:
Where conductors are supported
on a climbable pole in vertical
configuration, the energized portions of such conductors shall have clearances
of not less than 15 inches from the surface of pole for voltages between 750
and 7500 volts and 18 inches from the surface of pole for voltages in excess of
7500 volts.
Not more than two conductors
of a circuit of 750-5000 volts shall be attached directly to a pole in vertical
configuration without the use of crossarms.
The number of conductors of a circuit of more than 5000 volts so
supported on a pole is not limited.
Branch circuits may be taken from such construction without the use of
crossarms provided a climbing and working space as specified in Rules 54.7 and
54.11 is maintained.
Strikeout and Underline Version
Rule 54.4-D6b
54.4-D6b) More Than 750 Volts supported on climbable poles:
Where conductors are supported
on a climbable pole in vertical
configuration, the energized portions of such conductors shall have clearances
of not less than 15 inches from the surface of pole for voltages between 750
and 7500 volts and 18 inches from the surface of pole for voltages in excess of
7500 volts.
Not more than two conductors
of a circuit of 750-5000 volts shall be attached directly to a pole in vertical
configuration without the use of crossarms.
The number of conductors of a circuit of more than 5000 volts so
supported on a pole shall is not be limited to four. Branch circuits may be taken from such
construction without the use of crossarms provided a climbing and working space
as specified in Rules 54.7 and 54.11 is maintained.
Final Version
Rule 54.4-D6b
54.4-D6b) More Than 750 Volts supported on climbable poles:
Where conductors are supported
on a climbable pole in vertical
configuration, the energized portions of such conductors shall have clearances
of not less than 15 inches from the surface of pole for voltages between 750
and 7500 volts and 18 inches from the surface of pole for voltages in excess of
7500 volts.
Not more than two conductors
of a circuit of 750-5000 volts shall be attached directly to a pole in vertical
configuration without the use of crossarms.
The number of conductors of a circuit of more than 5000 volts so
supported on a pole shall be limited to four.
Branch circuits may be taken from such construction without the use of
crossarms provided a climbing and working space as specified in Rules 54.7 and 54.11 is maintained.