Original General Order
95
Section
V
Detailed Construction Requirements for Supply Lines
(Class H, L
and T Circuits)
54.7 Climbing and Working Space
Climbing space, measured from centerline of pole, shall be provided on one side or in one quadrant of all poles or structures, with dimensions as specified in Rules 54.7-A1, 54.7-A2 and 54.7-A3.
The climbing space shall be maintained in the same position for a distance of not less than 4 feet vertically both above and below each conductor level through which it passes. Compliance with this requirement necessitates that the position of the climbing space shall not be changed through conductor levels which are less than 4 feet apart. Where the vertical distance between consecutive conductor levels is 4 feet or more, and less than 8 feet the position of the climbing space through such consecutive levels may be shifted not more than one-quarter of the distance around the pole. Where a conductor is installed at the top of a pole under the provisions of Rule 54.4-D8, the climbing space shall extend up to the level of such pole-top conductor but need not be provided through and above such level.
Allowable obstruction of these climbing spaces, where necessary, are specified in Rule 54.7-A4
(1)
Dimensions Where Crossarms are Not
Involved:
Climbing space through the levels
of conductors deadended on poles in vertical configuration shall be a square of
the horizontal dimensions tabulated below; and one side of such climbing space
shall be bounded by the vertical plane of the dead-ended conductors with the
centerline of pole bisecting such side (see App. G, Fig, 15)
Voltage of Conductors |
Dimensions of Square |
750-7500 volts |
30inches |
7500-46,000 volts |
36 inches |
More than 46,000 volts |
36 inches plus ½ inch Per kV in excess Of 46kV. |
For climbing space dimensions for low voltage rack construction see Rule 54.9-F.
(2)
Dimensions Where Line Arms Only Are
Involved:
The climbing space through levels
where line arms without related buck arms are present on poles or structures
shall be on one side or face of the pole, with the center line of pole
approximately midway on one side of the climbing space (see App. G Fig. 16),
and shall have the following dimensions:
For conductors of 0-7500
volts, the climbing space shall be not less than 30 inches square except that
for combination arm construction the climbing space shall be not less than 36
inches square. (see Rule 54.8-E for
additional requirements where service drops from combination line arms are
involved.)
For conductors of 750-46,000
volts the climbing space shall not be less than 36 inches square.
For conductors of more than
46,000 volts the climbing space shall be a square the sides of which shall be
not less than 36 inches plus ½ inch per kV in excess of 46 kV.
The above dimensions may be
reduced not more than 2 percent because of line angles.
(3)
Dimensions Where Buck Arms Are Involved:
The climbing space where line arms and related buck arms are involved on pole
or structures shall be in a quadrant and shall have at least the dimensions,
determined according to voltage classification as given below. These dimensions are based on the minimum
clearance from center line of pole (Table 1, Case 8) and minimum pin spacings
(Table 2, Case 15) for the voltages involved, with the pin position numbered
outward from the pole on the climbing side.
Where metal back braces are used
they shall be considered as one of the arms of double arm construction.
a)
For Conductors of 0-750 Volts: Where
single line arm and buck arm construction is involved and the climbing space is
left open opposite the single arm, the No. 1 pin Position shall be left vacant
in the single arm. (See App G, Fig 18.)
Where
double line arm and double buck arm construction is involved , the No. 1 pin
position shall be left vacant in each arm.
(see App. G, Fig. 19)
b)
For conductors of More than 750 Volts:
Where single arm and single buck arm construction is involved and the climbing
space is left open on the opposite side of the pole from the arms, the No. 1
pin position shall be left vacant in both line arm and buck arm (see App. G,
Fig. 20). As an alternative, where the
conductors are of 750-7500 volts, the No. 1 and No. 2 pin positions in one arm
may be left vacant provided the arms involved are in top positions on the pole.
Where double line arm and single
buck arm, or vice versa, construction is involved and the climbing space is
left open on the side of the pole opposite the single arm, the No. 1 pin
position shall be left vacant in both line arm and buck arm (see App. G, Fig.
21). AS an alternative, where the
conductors are of 750-7500 volts the No. 1 and No. 2 pin positions may be left
vacant in the single arm provided the arm involved are in top positions on the
pole.
Where double line arm and double
buck arm construction is involved the No. 1 pin position shall be left vacant
in one double arm and the No. 1 and No. 2 pin positions shall be left vacant in
the other double arm. (See App. G, Fig
22.)
c)
For Combination Arm Construction with
Line Arm and Line Buck Arm or Service Buck Arm: (See Rule 54.8-E for additional requirements where service drops
are involved.)
Where the vertical separation
between conductor levels on line and buck arms is not less than 4 feet and the
climbing space is in a 0-750 volt quadrant, the climbing space dimensions shall
be not less than those prescribed in Rule 54.7-A3a for 0-750 volt conductors
provided that the required vacant pin conductors provided that the required
vacant pin spaces shall be in addition to the 36-inch horizontal conductor
separation required in Rule 54.4-C2b.
(See App. G, Figs 23, 24 and 25.)
Where the vertical separation
between conductor levels on line and buck arms is not less than 4 feet and the
climbing space is in a 750-7500 volt conductors provided that the required
vacant volt conductors provided that the required vacant pin spaces shall be in
addition to the 36-inch horizontal conductor separation required in Rule 54.4-C2b. (See App. G, Figs 26, 27 and
28.)
Where the vertical separation
between conductor levels the vertical separation between conductor levels on
line and buck arms is less than 4 feet such separation shall not be less than 2
feet and the climbing space dimensions, in any quadrant, shall be not less than
those prescribed in Rule 54.7-A3b for 750-7500 volt conductors, provided that
the required vacant pin spaces shall be in addition to the 42-inch horizontal
conductor separation required in Rule 54.4-C2b. (See App. G Figs 29, 30 and 31.)
d)
Alternatives: Where a single line arm or
single buck arm is involved and it is impractical to locate the climbing space
in the quadrant on the opposite side of the pole from the single arm, it may be
located in another quadrant provided that any single arm or arms within the
climbing space shall be treated as a double arm.
In applying the pin position
spacings as prescribed in Rule 54.7 not less than the minimum spacings of Table
2, Case 15 shall be used. In the event
the crossarms used are not bored for the minimum spacings, a spacing of
conductors to give equivalent dimensions will be considered as meeting the
requirements.
(4)
Allowable Climbing Space Obstructions:
Crossarms and their supporting members are allowed in climbing spaces provided
that, where buck arms are involved, any arms within climbing spaces are treated
as double arms.
Suitably protected vertical
conductors attached tot eh surfaces of poles, and guys, (except those guys
contacting metal pins or dead-end hardware as specified in Rule 52.7-D) are
allowed in climbing spaces provided that not more than one guy and one vertical
riser, run, or ground wire are installed in any 4-foot vertical section of
climbing space. The terminals or
terminal fittings of risers or runs shall not be installed within climbing
spaces.
Pin-type insulators which support
line conductors of 20,000 volts or less may extend not more than one-half of
their diameter into the climbing space.
Dead-end or strain type insulators which support line conductors of
0-750 volts may extend not more than one-half of their diameter into the
climbing space.
Modifications of these
requirements for rack construction are specified in Rule 54.9-F.
Working Spaces, unobstructed by conductors or other equipment except as provided in Rule 54.7-B2, of the dimensions as specified in Rule 54.7-B1, shall be provided dimensions as specified in Rule 54.7-B1, Shall be provided between conductor levels on all poles in such positions that the working levels on all poles and in such positions that the working space include the climbing space.
(1)
Dimensions of Working Space: Dimensions of Working Space: The vertical dimensions of the working space
above and below any conductor level shall be equal to the vertical clearances
between conductors specified in Table 2, Cases 8 to 14 inclusive, for the
voltages involved.
The width of the working space
where crossarms are involved shall be the distance between outside pin
positions of the crossarms involved.
The depth of the working space where crossarms are involved shall be
equal to the width of the climbing space and shall be measured perpendicularly
from the face of crossarm.
(2)
Allowable Working Space Obstructions:
Taps from conductors on line arms to conductors on related buck arms may pass
through the working space between the levels of conductors on related line and
buck arm.
Service drops of 0-750 volts may
pass through the working space of conductors and may pass through working space
of 750-7500 volt conductors provided not less than the clearance between
service drop and line conductors specified in Rule 54.8-C6 are maintained.
Cutouts and their leads may be
installed in the working space (but not the climbing space).
Switches and their leads may
extend into the working space (but not the working space).
Lead wires to transformers or
capacitors may pass through the working space adjacent to the line conductors
to which such leads are attached.
Terminal fittings of risers and
runs, and their taps, may extend into the working space provided these fittings
are the only obstruction of the working space at their level on the same side
of the climbing space.