Original Version
Rule 56.6-E
56.6-E. Guys Attached To Grounded Poles or Structures
Guys attached to securely grounded metal poles or structures are not required to be sectionalized except as required by Rule 56.6-A because of proximity to supply conductors of less than 22,500 volts supported on wood poles, or by Rule 56.6-B.
Strikeout and Underline Version
Rule 56.6-E
56.6-E. Guys Attached To Grounded Poles or Structures
Guys attached to securely
grounded metal poles or structures are not required to be sectionalized except
as required by Rule 56.6-A because of proximity to supply conductors of less
than 22,500 35,500 volts
supported on wood poles, or by Rule 56.6-B.
Strikeout and Underline Version
Rule 56.6-E
56.6-E. Guys Attached To Grounded Poles or Structures
Guys attached to securely grounded metal poles or structures are not required to be sectionalized except as required by Rule 56.6-A because of proximity to supply conductors of less than 33,500 volts supported on wood poles, or by Rule 56.6-B.