General Order 128
Appendix A
Summary of Dimensions, Clearances, and Depth Requirements
Table 2 Miscellaneous Dimensions and Clearance
Requirements for Supply and Communication Systems
Case No. |
Nature of Clearance or Depth |
Requirements‡ |
Reference Rules |
1 |
From railroad tracks, of risers and other above-ground terminations |
||
2 |
Size and shape of manholes |
Minimum inside dimension shall be 4 feet by 5 feet high. See Public Utilities Code, Section 8051 for specific requirements |
|
3 |
Manhole openings |
Not less than 26” in diameter or 26” x 24” rectangular |
|
4 |
Manhole location |
Manhole openings shall not be less than 3 feet from any railroad rail |
|
5 |
Sectionalizing Switches |
Maximum height of operating handles and viewing windows: 6–1/2 feet |
|
6 |
Oil filled equipment |
From building surface: 3 feetFrom non-combustible building surface: 2 feet |
‡ Dimensions and clearances shown may be reduced under certain conditions - see referenced rules.