Previous Code

Next Code

 

General Order 64

 

Section X

 

Joint Poles Or Poles Jointly Used

 

103    Clearance And Relarive Position Of Circuits.

The conductor clearances to be observed in joint pole construction are covered in the general rules of Section IV.  (See Appendix E, Figs. 10, 37 and 38.)

The different circuits on joint poles generally should be arranged in the order of their operating voltages, those of the highest voltage occupying the highest position, except that Class “T” attachments, if present, shall occupy the lowest position on the pole.
  Thus on poles on which these are Classes “L,” “S” and “T” circuits, these classes of circuits shall occupy respectively the highest, intermediate and lowest positions.

Where railway feeder circuits have only infrequent tap connections to the trolley contact wire the foregoing rule need not apply, and such railway feeders may be located and classed as ordinary supply conductors of equal voltage.
  Tap connections from feeder to trolley wire should not be run close to signal conductors, and the taps should be given ample clearance or else protected by proper conduit where signal lines are below trolley feeders and taps are made.  (See Rule 63 (d).)