Change List for this Rule

 

General Order 95

 

Section V

 

Detailed Construction Requirements for Supply Lines
(Class H, L and T Circuits)

58.6    Time Switches, Meters, Metal Boxes, Other Apparatus and Associated Antennas

 

A.    Grounded (See Rule 54.4–G )

 

B.    Ungrounded

Time switches, meters, metal boxes, other apparatus and associated antennas are not allowed in the climbing space.

 

C.    Within 8 Feet of the Ground

Boxes or enclosures containing switches, meters, or other apparatus having accessible live parts, which are located 8 feet or less above the ground shall be effectively locked or sealed.

Metal boxes which contain supply or control equipment or conductors and are located 8 feet or less above the ground shall be effectively grounded.

 

Note:    Revised January 19, 1994 by Resolution SU–25.