Rule 92.4-A
92.4-A. General
The following rules cover the grounding or isolating of communication cable systems, as defined herein. Systems include cables, messengers, and guys, or a combination of these facilities at the supply or communication level.
The term “cable” means stranded conductor or a combination of conductors that includes Fiber Optic Supply Cable, Fiber Optic Communication Cable, or Non–Dielectric Fiber Optic Cable as defined in Rule 20.3.
The term “messenger” is defined in Rule 21.11.
The term “guy” is defined in Rule 21.3. The definition of “exposed” as applied to a guy in Rule 21.3–C shall also apply to cables and messengers.
Strikeout and Underline Version
Rule 92.4-A
92.4-A. General
The following rules cover the grounding or isolating of communication cable systems, as defined herein. Systems include cables, messengers, and guys, or a combination of these facilities at the supply or communication level.
The term
“cable” means stranded conductor or a combination of conductors that includes
Fiber Optic Supply Cable, Fiber Optic Communication Cable, or Non–Dielectric
Fiber Optic Cable as defined in Rule
20.3
20.4.
The term
“messenger” is defined in Rule
21.11 22.3.
The term “guy”
is defined in Rule 21.3
21.5. The definition of “exposed” as applied to a guy in
Rule 21.3-C
21.5-C shall also apply to cables and messengers.
Final Version
Rule 92.4-A
92.4-A. General
The following rules cover the grounding or isolating of communication cable systems, as defined herein. Systems include cables, messengers, and guys, or a combination of these facilities at the supply or communication level.
The term “cable” means stranded conductor or a combination of conductors that includes Fiber Optic Supply Cable, Fiber Optic Communication Cable, or Non–Dielectric Fiber Optic Cable as defined in Rule 20.4.
The term “messenger” is defined in Rule 22.3.
The term “guy” is defined in Rule 21.5. The definition of “exposed” as applied to a guy in Rule 21.5–C shall also apply to cables and messengers.