Original Version
Rule 54.7-A
54.7-A. Climbing Space
Climbing space, measured from centerline of pole, shall
be provided on one side or in one quadrant of all poles or structures, with
dimensions as specified in Rules 54.7-A1, 54.7-A2 and 54.7-A3.
The climbing space shall be maintained in the same position for a distance
of not less than 4 feet vertically both above and below each conductor level
through which it passes. Compliance with this requirement necessitates that
the position of the climbing space shall not be changed through conductor
levels which are less than 4 feet apart. Where the vertical distance
between consecutive conductor levels is 4 feet or more, and less than 8 feet
the position of the climbing space through such consecutive levels may be
shifted not more than one-quarter of the distance around the pole.
Where a conductor is installed at the top of a pole under the provisions
of Rule 54.4-D8, the climbing space shall extend up to the level of such
pole-top conductor but need not be provided through and above such level.
Allowable obstruction of these climbing spaces, where necessary, are specified
in Rule 54.7-A4
This Rule 54.7-A need not apply to non-climbable metal poles in partial underground
distribution, provided the regular written operating rules of the utility
concerned specify that all work on conductors and equipment supported by
such poles shall be performed only from aerial lifts and (1) in the case
of primary conductors, shall be done with live-line tools after installing
adequate insulating and protective devices or barriers in order to (a) prevent
accidental contact by the workman with the energized conductors other than
the conductor being worked on and (b) to minimize the possibility of simultaneous
contact of the metal parts of live-line tools with the grounded pole and
the energized conductor and (2) in the case of secondary conductors shall
be done after suitably covering all energized primary conductors with adequate
insulating and protective devices or barriers.
1) Dimensions Where Crossarms are Not Involved:
Climbing space through the levels of conductors deadended on poles in vertical
configuration shall be a square of the horizontal dimensions tabulated below;
and one side of such climbing space shall be bounded by the vertical plane
of the dead-ended conductors with the centerline of pole bisecting such side
(see App. G, Fig, 15)
Voltage of Conductors |
Dimensions of Square |
750-7500 volts |
30inches |
7500-46,000 volts |
36 inches |
More than 46,000 volts |
36 inches plus ½ inchPer kV in excess |
For climbing space dimensions for low voltage rack construction see Rule
54.9-F.
2) Dimensions Where Line Arms Only Are Involved:
The climbing space through levels where line arms without related buck arms
are present on poles or structures shall be on one side or face of the pole,
with the center line of pole approximately midway on one side of the climbing
space (see App. G Fig. 16), and shall have the following dimensions:
For conductors of 0-7500 volts, the climbing space shall be not less than
30 inches square except that for combination arm construction the climbing
space shall be not less than 36 inches square. (see Rule 54.8-E for
additional requirements where service drops from combination line arms are
involved.)
For conductors of 750-46,000 volts the climbing space shall not be less
than 36 inches square.
For conductors of more than 46,000 volts the climbing space shall be a square
the sides of which shall be not less than 36 inches plus ½ inch per
kV in excess of 46 kV.
The above dimensions may be reduced not more than 2 percent because of line
angles.
The climbing space required by this rule may be shifted laterally not more
than 5 inches under the condition that (a) the mid-point of the side of the
climbing space coinciding with the center line of, the pole shall be not
more than 5 inches from the center line of the pole, and (b) that full climbing
space dimensions shall be maintained, but without the use of the 2% reduction
where the shift is more than 2 inches.
3) Dimensions Where Buck Arms Are Involved: The climbing
space where line arms and related buck arms are involved on pole or structures
shall be in a quadrant and shall have at least the dimensions, determined
according to voltage classification as given below. These dimensions
are based on the minimum clearance from center line of pole (Table 1, Case
8) and minimum pin spacings (Table 2, Case 15) for the voltages involved,
with the pin position numbered outward from the pole on the climbing side.
Where metal back braces are used they shall be considered as one of the
arms of double arm construction.
a) For Conductors of 0-750 Volts: Where single line arm
and buck arm construction is involved and the climbing space is left open
opposite the single arm, the No. 1 pin Position shall be left vacant in the
single arm. (See App G, Fig 18.)
Where double line arm and double buck arm construction is involved, the
No. 1 pin position shall be left vacant in each arm. (see App. G, Fig.
19)
b) For conductors of More than 750 Volts: Where single
arm and single buck arm construction is involved and the climbing space is
left open on the opposite side of the pole from the arms, the No. 1 pin position
shall be left vacant in both line arm and buck arm (see App. G, Fig. 20).
As an alternative, where the conductors are of 750-7500 volts, the No. 1
and No. 2 pin positions in one arm may be left vacant provided the arms involved
are in top positions on the pole.
Where double line arm and single buck arm, or vice versa, construction is
involved and the climbing space is left open on the side of the pole opposite
the single arm, the No. 1 pin position shall be left vacant in both line arm
and buck arm (see App. G, Fig. 21). AS an alternative, where the conductors
are of 750-7500 volts the No. 1 and No. 2 pin positions may be left vacant
in the single arm provided the arm involved are in top positions on the pole.
Where double line arm and double buck arm construction is involved the No.
1 pin position shall be left vacant in one double arm and the No. 1 and No.
2 pin positions shall be left vacant in the other double arm. (See
App. G, Fig 22.)
Where a single circuit of more than 7,500 volts is in horizontal configuration
at the top of the pole, climbing space has to be provided only up to and
not through the top level and the No. 1 pin position need not be left vacant.
c) For Combination Arm Construction with Line Arm and
Line Buck Arm or Service Buck Arm: (See Rule 54.8-E for additional
requirements where service drops are involved.)
Where the vertical separation
between conductor levels on line and buck arms is not less than 4 feet and the
climbing space is in a 0-750 volt quadrant, the climbing space dimensions shall
be not less than those prescribed in Rule 54.7-A3a for 0-750 volt conductors
provided that the required vacant pin conductors provided that the required
vacant pin spaces shall be in addition to the 36-inch horizontal conductor
separation required in Rule 54.4-C2b.
(See App. G, Figs 23, 24 and 25.)
Where the vertical separation
between conductor levels on line and buck arms is not less than 4 feet and the
climbing space is in a 750-7500 volt conductors provided that the required
vacant volt conductors provided that the required vacant pin spaces shall be in
addition to the 36-inch horizontal conductor separation required in Rule 54.4-C2b. (See App. G, Figs 26, 27 and
28.)
Where the vertical separation
between conductor levels the vertical separation between conductor levels on
line and buck arms is less than 4 feet such separation shall not be less than 2
feet and the climbing space dimensions, in any quadrant, shall be not less than
those prescribed in Rule 54.7-A3b for 750-7500 volt conductors, provided that
the required vacant pin spaces shall be in addition to the 42-inch horizontal
conductor separation required in Rule 54.4-C2b. (See App. G Figs 29, 30 and 31.)
d) Alternatives: Where a single line arm or single buck
arm is involved and it is impractical to locate the climbing space in the
quadrant on the opposite side of the pole from the single arm, it may be
located in another quadrant provided that any single arm or arms within the
climbing space shall be treated as a double arm.
In applying the pin position
spacings as prescribed in Rule 54.7 not less than the minimum spacings of Table
2, Case 15 shall be used. In the event
the crossarms used are not bored for the minimum spacings, a spacing of
conductors to give equivalent dimensions will be considered as meeting the
requirements.
4) Allowable Climbing Space Obstructions: Crossarms and
their supporting members are allowed in climbing spaces provided that, where
buck arms are involved, any arms within climbing spaces are treated as double
arms.
Suitably protected vertical
conductors attached tot eh surfaces of poles, and guys, (except those guys
contacting metal pins or dead-end hardware as specified in Rule 52.7-D) are
allowed in climbing spaces provided that not more than one guy and one vertical
riser, run, or ground wire are installed in any 4-foot vertical section of
climbing space.
Pin-type insulators which support line conductors of 20,000 volts or less
may extend not more than one-half of their diameter into the climbing space.
Dead-end or strain type insulators which support line conductors of 0-750
volts may extend not more than one-half of their diameter into the climbing
space.
Space bolts used for the attachment of dead-end hardware of a circuit of
any voltage located below a circuit at the top of the pole may project into
the climbing space provided they are protected with a suitable insulating
cover, having an insulating value equal to the insulators on the associated
circuit, and further that the area of the climbing space on a horizontal
plane is not reduced by more than 10%.
Modifications of these
requirements for rack construction are specified in Rule 54.9-F.
Strikeout and Underline Version
Rule 54.7-A
54.7-A. Climbing Space
Climbing space, measured from centerline of pole, shall
be provided on one side or in one quadrant of all poles or structures, with
dimensions as specified in Rules 54.7-A1, 54.7-A2 and 54.7-A3. For climbing space
dimensions where post insulators are utilized see Rule 54.11-F.
The climbing space shall be maintained in the same position for a distance
of not less than 4 feet vertically both above and below each conductor level
through which it passes. Compliance with this requirement necessitates that
the position of the climbing space shall not be changed through conductor
levels which are less than 4 feet apart. Where the vertical distance
between consecutive conductor levels is 4 feet or more, and less than 8 feet
the position of the climbing space through such consecutive levels may be
shifted not more than one-quarter of the distance around the pole.
Where a conductor is installed at the top of a pole under the provisions
of Rule 54.4-D8, the climbing space shall extend up to the level of such
pole-top conductor but need not be provided through and above such level.
Allowable obstruction of these climbing spaces, where necessary, are specified
in Rule 54.7-A4
This Rule 54.7-A need not apply to non-climbable metal poles in partial underground
distribution, provided the regular written operating rules of the utility
concerned specify that all work on conductors and equipment supported by
such poles shall be performed only from aerial lifts and (1) in the case
of primary conductors, shall be done with live-line tools after installing
adequate insulating and protective devices or barriers in order to (a) prevent
accidental contact by the workman with the energized conductors other than
the conductor being worked on and (b) to minimize the possibility of simultaneous
contact of the metal parts of live-line tools with the grounded pole and
the energized conductor and (2) in the case of secondary conductors shall
be done after suitably covering all energized primary conductors with adequate
insulating and protective devices or barriers.
1) Dimensions Where Crossarms are Not Involved:
Climbing space through the levels of conductors deadended on poles in vertical
configuration shall be a square of the horizontal dimensions tabulated below;
and one side of such climbing space shall be bounded by the vertical plane
of the dead-ended conductors with the centerline of pole bisecting such side
(see App. G, Fig, 15)
Voltage of Conductors |
Dimensions of Square |
750-7500 volts |
30inches |
7500-46,000 volts |
36 inches |
More than 46,000 volts |
36 inches plus ½ inchPer kV in excess |
For climbing space dimensions for low voltage rack construction see Rule
54.9-F.
2) Dimensions Where Line Arms Only Are Involved:
The climbing space through levels where line arms without related buck arms
are present on poles or structures shall be on one side or face of the pole,
with the center line of pole approximately midway on one side of the climbing
space (see App. G Fig. 16), and shall have the following dimensions:
For conductors of 0-7500 volts, the climbing space shall be not less than
30 inches square except that for combination arm construction the climbing
space shall be not less than 36 inches square. (see Rule 54.8-E for
additional requirements where service drops from combination line arms are
involved.)
For conductors of 750-46,000 volts the climbing space shall not be less
than 36 inches square.
For conductors of more than 46,000 volts the climbing space shall be a square
the sides of which shall be not less than 36 inches plus ½ inch per
kV in excess of 46 kV.
The above dimensions may be reduced not more than 2 percent because of line
angles.
The climbing space required by this rule may be shifted laterally not more
than 5 inches under the condition that (a) the mid-point of the side of the
climbing space coinciding with the center line of, the pole shall be not
more than 5 inches from the center line of the pole, and (b) that full climbing
space dimensions shall be maintained, but without the use of the 2% reduction
where the shift is more than 2 inches.
3) Dimensions Where Buck Arms Are Involved: The climbing
space where line arms and related buck arms are involved on pole or structures
shall be in a quadrant and shall have at least the dimensions, determined
according to voltage classification as given below. These dimensions
are based on the minimum clearance from center line of pole (Table 1, Case
8) and minimum pin spacings (Table 2, Case 15) for the voltages involved,
with the pin position numbered outward from the pole on the climbing side.
Where metal back braces are used they shall be considered as one of the
arms of double arm construction.
a) For Conductors of 0-750 Volts: Where single line arm
and buck arm construction is involved and the climbing space is left open
opposite the single arm, the No. 1 pin Position shall be left vacant in the
single arm. (See App G, Fig 18.)
Where double line arm and double buck arm construction is involved, the
No. 1 pin position shall be left vacant in each arm. (see App. G, Fig.
19)
b) For conductors of More than 750 Volts: Where single
arm and single buck arm construction is involved and the climbing space is
left open on the opposite side of the pole from the arms, the No. 1 pin position
shall be left vacant in both line arm and buck arm (see App. G, Fig. 20).
As an alternative, where the conductors are of 750-7500 volts, the No. 1
and No. 2 pin positions in one arm may be left vacant provided the arms involved
are in top positions on the pole.
Where double line arm and single buck arm, or vice versa, construction is
involved and the climbing space is left open on the side of the pole opposite
the single arm, the No. 1 pin position shall be left vacant in both line arm
and buck arm (see App. G, Fig. 21). AS an alternative, where the conductors
are of 750-7500 volts the No. 1 and No. 2 pin positions may be left vacant
in the single arm provided the arm involved are in top positions on the pole.
Where double line arm and double buck arm construction is involved the No.
1 pin position shall be left vacant in one double arm and the No. 1 and No.
2 pin positions shall be left vacant in the other double arm. (See
App. G, Fig 22.)
Where a single circuit of more than 7,500 volts is in horizontal configuration
at the top of the pole, climbing space has to be provided only up to and
not through the top level and the No. 1 pin position need not be left vacant.
c) For Combination Arm Construction with Line Arm and
Line Buck Arm or Service Buck Arm: (See Rule 54.8-E for additional
requirements where service drops are involved.)
Where the vertical separation
between conductor levels on line and buck arms is not less than 4 feet and the
climbing space is in a 0-750 volt quadrant, the climbing space dimensions shall
be not less than those prescribed in Rule 54.7-A3a for 0-750 volt conductors
provided that the required vacant pin conductors provided that the required
vacant pin spaces shall be in addition to the 36-inch horizontal conductor
separation required in Rule 54.4-C2b.
(See App. G, Figs 23, 24 and 25.)
Where the vertical separation
between conductor levels on line and buck arms is not less than 4 feet and the
climbing space is in a 750-7500 volt conductors provided that the required
vacant volt conductors provided that the required vacant pin spaces shall be in
addition to the 36-inch horizontal conductor separation required in Rule 54.4-C2b. (See App. G, Figs 26, 27 and
28.)
Where the vertical separation
between conductor levels the vertical separation between conductor levels on
line and buck arms is less than 4 feet such separation shall not be less than 2
feet and the climbing space dimensions, in any quadrant, shall be not less than
those prescribed in Rule 54.7-A3b for 750-7500 volt conductors, provided that
the required vacant pin spaces shall be in addition to the 42-inch horizontal
conductor separation required in Rule 54.4-C2b. (See App. G Figs 29, 30 and 31.)
d) Alternatives: Where a single line arm or single buck
arm is involved and it is impractical to locate the climbing space in the
quadrant on the opposite side of the pole from the single arm, it may be
located in another quadrant provided that any single arm or arms within the
climbing space shall be treated as a double arm.
In applying the pin position
spacings as prescribed in Rule 54.7 not less than the minimum spacings of Table
2, Case 15 shall be used. In the event
the crossarms used are not bored for the minimum spacings, a spacing of
conductors to give equivalent dimensions will be considered as meeting the
requirements.
4) Allowable Climbing Space Obstructions: Crossarms and
their supporting members are allowed in climbing spaces provided that, where
buck arms are involved, any arms within climbing spaces are treated as double
arms.
Suitably protected vertical
conductors attached tot eh surfaces of poles, and guys, (except those guys
contacting metal pins or dead-end hardware as specified in Rule 52.7-D) are
allowed in climbing spaces provided that not more than one guy and one vertical
riser, run, or ground wire are installed in any 4-foot vertical section of
climbing space.
Pin-type insulators which support line conductors of 20,000 volts or less
may extend not more than one-half of their diameter into the climbing space.
Dead-end or strain type insulators which support line conductors of 0-750
volts may extend not more than one-half of their diameter into the climbing
space.
Space bolts used for the attachment of dead-end hardware of a circuit of
any voltage located below a circuit at the top of the pole may project into
the climbing space provided they are protected with a suitable insulating
cover, having an insulating value equal to the insulators on the associated
circuit, and further that the area of the climbing space on a horizontal
plane is not reduced by more than 10%.
Modifications of these
requirements for rack construction are specified in Rule 54.9-F.
Final Version
Rule 54.7-A
54.7-A. Climbing Space
Climbing space, measured from centerline of pole, shall
be provided on one side or in one quadrant of all poles or structures, with
dimensions as specified in Rules 54.7-A1, 54.7-A2 and 54.7-A3. For climbing space
dimensions where post insulators are utilized see Rule 54.11-F.
The climbing space shall be maintained in the same position for a distance
of not less than 4 feet vertically both above and below each conductor level
through which it passes. Compliance with this requirement necessitates that
the position of the climbing space shall not be changed through conductor
levels which are less than 4 feet apart. Where the vertical distance
between consecutive conductor levels is 4 feet or more, and less than 8 feet
the position of the climbing space through such consecutive levels may be
shifted not more than one-quarter of the distance around the pole.
Where a conductor is installed at the top of a pole under the provisions
of Rule 54.4-D8, the climbing space shall extend up to the level of such
pole-top conductor but need not be provided through and above such level.
Allowable obstruction of these climbing spaces, where necessary, are specified
in Rule 54.7-A4
This Rule 54.7-A need not apply to non-climbable metal poles in partial underground
distribution, provided the regular written operating rules of the utility
concerned specify that all work on conductors and equipment supported by
such poles shall be performed only from aerial lifts and (1) in the case
of primary conductors, shall be done with live-line tools after installing
adequate insulating and protective devices or barriers in order to (a) prevent
accidental contact by the workman with the energized conductors other than
the conductor being worked on and (b) to minimize the possibility of simultaneous
contact of the metal parts of live-line tools with the grounded pole and
the energized conductor and (2) in the case of secondary conductors shall
be done after suitably covering all energized primary conductors with adequate
insulating and protective devices or barriers.
1) Dimensions Where Crossarms are Not Involved:
Climbing space through the levels of conductors deadended on poles in vertical
configuration shall be a square of the horizontal dimensions tabulated below;
and one side of such climbing space shall be bounded by the vertical plane
of the dead-ended conductors with the centerline of pole bisecting such side
(see App. G, Fig, 15)
Voltage of Conductors |
Dimensions of Square |
750-7500 volts |
30inches |
7500-46,000 volts |
36 inches |
More than 46,000 volts |
36 inches plus ½ inchPer kV in excess |
For climbing space dimensions for low voltage rack construction see Rule
54.9-F.
2) Dimensions Where Line Arms Only Are Involved:
The climbing space through levels where line arms without related buck arms
are present on poles or structures shall be on one side or face of the pole,
with the center line of pole approximately midway on one side of the climbing
space (see App. G Fig. 16), and shall have the following dimensions:
For conductors of 0-7500 volts, the climbing space shall be not less than
30 inches square except that for combination arm construction the climbing
space shall be not less than 36 inches square. (see Rule 54.8-E for
additional requirements where service drops from combination line arms are
involved.)
For conductors of 750-46,000 volts the climbing space shall not be less
than 36 inches square.
For conductors of more than 46,000 volts the climbing space shall be a square
the sides of which shall be not less than 36 inches plus ½ inch per
kV in excess of 46 kV.
The above dimensions may be reduced not more than 2 percent because of line
angles.
The climbing space required by this rule may be shifted laterally not more
than 5 inches under the condition that (a) the mid-point of the side of the
climbing space coinciding with the center line of, the pole shall be not
more than 5 inches from the center line of the pole, and (b) that full climbing
space dimensions shall be maintained, but without the use of the 2% reduction
where the shift is more than 2 inches.
3) Dimensions Where Buck Arms Are Involved: The climbing
space where line arms and related buck arms are involved on pole or structures
shall be in a quadrant and shall have at least the dimensions, determined
according to voltage classification as given below. These dimensions
are based on the minimum clearance from center line of pole (Table 1, Case
8) and minimum pin spacings (Table 2, Case 15) for the voltages involved,
with the pin position numbered outward from the pole on the climbing side.
Where metal back braces are used they shall be considered as one of the
arms of double arm construction.
a) For Conductors of 0-750 Volts: Where single line arm
and buck arm construction is involved and the climbing space is left open
opposite the single arm, the No. 1 pin Position shall be left vacant in the
single arm. (See App G, Fig 18.)
Where double line arm and double buck arm construction is involved, the
No. 1 pin position shall be left vacant in each arm. (see App. G, Fig.
19)
b) For conductors of More than 750 Volts: Where single
arm and single buck arm construction is involved and the climbing space is
left open on the opposite side of the pole from the arms, the No. 1 pin position
shall be left vacant in both line arm and buck arm (see App. G, Fig. 20).
As an alternative, where the conductors are of 750-7500 volts, the No. 1
and No. 2 pin positions in one arm may be left vacant provided the arms involved
are in top positions on the pole.
Where double line arm and single buck arm, or vice versa, construction is
involved and the climbing space is left open on the side of the pole opposite
the single arm, the No. 1 pin position shall be left vacant in both line arm
and buck arm (see App. G, Fig. 21). AS an alternative, where the conductors
are of 750-7500 volts the No. 1 and No. 2 pin positions may be left vacant
in the single arm provided the arm involved are in top positions on the pole.
Where double line arm and double buck arm construction is involved the No.
1 pin position shall be left vacant in one double arm and the No. 1 and No.
2 pin positions shall be left vacant in the other double arm. (See
App. G, Fig 22.)
Where a single circuit of more than 7,500 volts is in horizontal configuration
at the top of the pole, climbing space has to be provided only up to and
not through the top level and the No. 1 pin position need not be left vacant.
c) For Combination Arm Construction with Line Arm and
Line Buck Arm or Service Buck Arm: (See Rule 54.8-E for additional
requirements where service drops are involved.)
Where the vertical separation
between conductor levels on line and buck arms is not less than 4 feet and the
climbing space is in a 0-750 volt quadrant, the climbing space dimensions shall
be not less than those prescribed in Rule 54.7-A3a for 0-750 volt conductors
provided that the required vacant pin conductors provided that the required
vacant pin spaces shall be in addition to the 36-inch horizontal conductor
separation required in Rule 54.4-C2b.
(See App. G, Figs 23, 24 and 25.)
Where the vertical separation
between conductor levels on line and buck arms is not less than 4 feet and the
climbing space is in a 750-7500 volt conductors provided that the required
vacant volt conductors provided that the required vacant pin spaces shall be in
addition to the 36-inch horizontal conductor separation required in Rule 54.4-C2b. (See App. G, Figs 26, 27 and
28.)
Where the vertical separation
between conductor levels the vertical separation between conductor levels on
line and buck arms is less than 4 feet such separation shall not be less than 2
feet and the climbing space dimensions, in any quadrant, shall be not less than
those prescribed in Rule 54.7-A3b for 750-7500 volt conductors, provided that
the required vacant pin spaces shall be in addition to the 42-inch horizontal
conductor separation required in Rule 54.4-C2b. (See App. G Figs 29, 30 and 31.)
d) Alternatives: Where a single line arm or single buck
arm is involved and it is impractical to locate the climbing space in the
quadrant on the opposite side of the pole from the single arm, it may be
located in another quadrant provided that any single arm or arms within the
climbing space shall be treated as a double arm.
In applying the pin position
spacings as prescribed in Rule 54.7 not less than the minimum spacings of Table
2, Case 15 shall be used. In the event
the crossarms used are not bored for the minimum spacings, a spacing of
conductors to give equivalent dimensions will be considered as meeting the
requirements.
4) Allowable Climbing Space Obstructions: Crossarms and
their supporting members are allowed in climbing spaces provided that, where
buck arms are involved, any arms within climbing spaces are treated as double
arms.
Suitably protected vertical
conductors attached tot eh surfaces of poles, and guys, (except those guys
contacting metal pins or dead-end hardware as specified in Rule 52.7-D) are
allowed in climbing spaces provided that not more than one guy and one vertical
riser, run, or ground wire are installed in any 4-foot vertical section of
climbing space.
Pin-type insulators which support line conductors of 20,000 volts or less
may extend not more than one-half of their diameter into the climbing space.
Dead-end or strain type insulators which support line conductors of 0-750
volts may extend not more than one-half of their diameter into the climbing
space.
Space bolts used for the attachment of dead-end hardware of a circuit of
any voltage located below a circuit at the top of the pole may project into
the climbing space provided they are protected with a suitable insulating
cover, having an insulating value equal to the insulators on the associated
circuit, and further that the area of the climbing space on a horizontal
plane is not reduced by more than 10%.
Modifications of these
requirements for rack construction are specified in Rule 54.9-F.