Change List for this Rule

 

Original Version

Rule 83.4

 

83.4    Bonding

 

Where separate communication messengers, or guys, or both, of the same or different ownership, are attached tot the same pole, and they are in proximity to electric supply circuits (see Rule 21.3-D), railway signal circuits or Class T electric railway or trolley circuits, such messengers, or guys, or both, shall be bonded together at frequent intervals (See Rule 83.4-A).  For purpose of this rule, communication messengers and guys are those which support Major Class C circuits (see Rule 20.5) and those Minor Class C Circuits which are used for television transmission.

 

Where bonding is required, the bond wire or bond strap shall have a conductivity of not less than No. 6 AWG copper wire, and shall be securely attached to the messenger or guy.  Such a bond wire or bond strap may be attached tot eh surface of a pole or to the underside of a crossarm using metal staples, but shall in no case be attached to the top surface of any crossarm.  Bond wires or bond straps placed in the climbing space shall be covered by a suitable protective covering (see Rule 22.2).

 

Communication systems owned by electric utilities are exempt from these requirements.

 

A.    Messengers On The Same Pole

 

(1)    Bonds are required between separate communication messengers or guys, attached above or below electric supply circuits, railway signal circuits or Class T electric railroad or trolley circuits on same pole line system, at all dead-end poles and at intervals not to exceed 1,500 feet.

 

(2)    Bonds between separate communication messengers on the same pole line system are required at the first pole on either side of the location where such messengers cross over or under electric supply circuits, railway signal circuits or Class T electric railway or trolley circuits.

 

(3)    Bonds are not required between communication messengers or guys which are attached to the same pole by a common bolt.

 

B.    Messengers Of Different Pole Line Systems

 

Bonding is required between communication messengers or guys, or both, where the pole line systems intersect at a common pole.


Strikeout and Underline Version

Rule 83.4

 

83.4    Bonding

 

Where separate communication messengers, or guys, or both, of the same or different ownership, are attached tot the same pole, and they are in proximity to electric supply circuits (see Rule 21.3-D), railway signal circuits or Class T electric railway or trolley circuits, such messengers, or guys, or both, shall be bonded together at frequent intervals (See Rule 83.4-A).  For purpose of this rule, communication messengers and guys are those which support Major Class C circuits (see Rule 20.5) and those Minor Class C Circuits which are used for television transmission.

 

Where bonding is required, the bond wire or bond strap shall have a conductivity of not less than No. 6 AWG copper wire, and shall be securely attached to the messenger or guy.  Such a bond wire or bond strap may be attached tot eh surface of a pole or to the underside of a crossarm using metal staples, but shall in no case be attached to the top surface of any crossarm.  Bond wires or bond straps placed in the climbing space shall be covered by a suitable protective covering (see Rule 22.2).

Communication systems owned by electric utilities are exempt from these requirements.

 

NOTE:    Bonding of communication systems owned by electric utilities to other communication systems, while not required, is acceptable by mutual agreement between all parties.

 

A.    Messengers On The Same Pole

 

(1)    Bonds are required between separate communication messengers or guys, attached above or below electric supply circuits, railway signal circuits or Class T electric railroad or trolley circuits on same pole line system, at all dead-end poles and at intervals not to exceed 1,500 feet.

 

(2)    Bonds between separate communication messengers on the same pole line system are required at the first pole on either side of the location where such messengers cross over or under electric supply circuits, railway signal circuits or Class T electric railway or trolley circuits.

 

(3)    Bonds are not required between communication messengers or guys which are attached to the same pole by a common bolt.

 

B.    Messengers Of Different Pole Line Systems

 

Bonding is required between communication messengers or guys, or both, where the pole line systems intersect at a common pole.


Final Version

Rule 83.4

 

83.4    Bonding

 

Where separate communication messengers, or guys, or both, of the same or different ownership, are attached tot the same pole, and they are in proximity to electric supply circuits (see Rule 21.3-D), railway signal circuits or Class T electric railway or trolley circuits, such messengers, or guys, or both, shall be bonded together at frequent intervals (See Rule 83.4-A).  For purpose of this rule, communication messengers and guys are those which support Major Class C circuits (see Rule 20.5) and those Minor Class C Circuits which are used for television transmission.

 

Where bonding is required, the bond wire or bond strap shall have a conductivity of not less than No. 6 AWG copper wire, and shall be securely attached to the messenger or guy.  Such a bond wire or bond strap may be attached tot eh surface of a pole or to the underside of a crossarm using metal staples, but shall in no case be attached to the top surface of any crossarm.  Bond wires or bond straps placed in the climbing space shall be covered by a suitable protective covering (see Rule 22.2).

 

NOTE:    Bonding of communication systems owned by electric utilities to other communication systems, while not required, is acceptable by mutual agreement between all parties.

 

A.    Messengers On The Same Pole

 

(1)    Bonds are required between separate communication messengers or guys, attached above or below electric supply circuits, railway signal circuits or Class T electric railroad or trolley circuits on same pole line system, at all dead-end poles and at intervals not to exceed 1,500 feet.

 

(2)    Bonds between separate communication messengers on the same pole line system are required at the first pole on either side of the location where such messengers cross over or under electric supply circuits, railway signal circuits or Class T electric railway or trolley circuits.

 

(3)    Bonds are not required between communication messengers or guys which are attached to the same pole by a common bolt.

 

B.    Messengers Of Different Pole Line Systems

 

Bonding is required between communication messengers or guys, or both, where the pole line systems intersect at a common pole.