Original Version
Rule 84.6-E
84.6-E. Risers
Risers of wires or underground cables shall be covered from the ground line to a level not less than 8 feet above the ground line by one of the following:
(1) Grounded (see definition 21.2) iron or steel pipe, metal U-guard or other metallic covering of equal strength or;
(2) Conduit or U-shaped molding meeting the
requirements as specified in Rule
22.2.
Risers shall be covered by a suitable protective covering as defined in Rule 22.2, for a vertical distance of 3 feet above to 6 feet below the level of unprotected supply conductors supported on the same pole or structure, or within a 6-foot radius of another pole supporting unprotected supply conductors.
Strikeout and Underline Version
Rule 84.6-E
84.6-E.
Risers Intentionally
Left Blank
(Note: Risers revised and moved to 87.7-D)
Risers of wires or underground cables shall be covered from the ground line to a
level not less than 8 feet above the ground line by one of the
following:
(1) Grounded (see definition 21.2) iron or steel
pipe, metal U-guard or other metallic covering of equal strength or;
(2) Conduit or U-shaped molding meeting the
requirements as specified in Rule
22.2.
Risers shall be covered by a suitable protective covering as
defined in Rule
22.2, for a vertical distance of 3
feet above to 6 feet below the level of unprotected supply conductors supported
on the same pole or structure, or within a 6-foot radius of another pole
supporting unprotected supply conductors.
Final Version
Rule 84.6-E
84.6-E. Intentionally Left Blank
(Note: Risers revised and moved to 87.7-D)