General Order 95
Section IX
Joint Poles or Poles Jointly Used
91.4 Hardware
Riser
standoff brackets on supporting structures shall be arranged so that there is
not less than 8 ft between either:
(1) The lowest bracket and ground or
other easily climbable surface, or
(2) The two lowest brackets.
Exception:
Does not apply when a fence or wall is used as a suitable barrier. See Rule 61.6-B.
For grounded hardware requirements see Rule 54.4–G .
Note:
Revised January 19, 1994 by Resolution SU–25 and January 15,
2015 by Decision No. 15-01-005