Original Version
Rule 89.2-A
89.2-A. Private Communication Circuits And Supply
Circuits On The Same Crossarms (see Rule 32.4-C)
(1) Supply Conductors Of 7500-20,000 Volts,
Same Ownership: Where private communication conductors are supported on the
same crossarms with supply conductors of 7500-20,000 volts, the private communication
circuits shall have the strengths and clearances required for Class L circuits
of 750-5000 volts. The private communication conductors shall be on opposite
ends of the arms from the supply conductors and shall be separated a horizontal
distance of not less than 36 inches from the nearest supply conductor. Where
buck arms are used in connection with such circuit arrangement, the minimum
vertical separation between related line and buck arms shall be 4 feet and
the horizontal separation between the nearest conductors of the two classes
of circuits on the same arm shall be not less than 36 inches plus any horizontal
space provided by vacant pin positions which are required by climbing space
rules.
(2) Supply Conductors Of 750-7500 Volts, Same Ownership:
Where private communication conductors are supported on the same crossarms
with supply conductors of 750-7500 volts, the private communication circuits
shall have the strengths and clearances required for Class L circuits of
0-750 volts. The private communication conductors shall be on opposite ends
of the arms from the supply conductors with conductor clearances and the
spacing between related line and buck arms in conformity with the requirements
for combination arm construction. (See Rules 32.4-A3, 54.4-C2b, and 54.7-A.)
(3) Supply Conductors Of 0-750 Volts, Same Ownership: Where
private communication conductors are supported on the same crossarms with
supply conductors of 0-750 volts, the private communication circuits shall
have strengths and clearances as required for Class C conductors except that
the clearances from supply conductors of the same ownership shall conform
to the requirements for Class L circuits of 0-750 volts. The communication
conductors shall preferably be located in the outer pin positions.
(4) Supply Conductors Of 0-750 Volts, Different Ownership:
Supply circuits of 0-750 volts and private communication circuits of different
ownership may be supported on the same crossarm, provided the two classifications
of circuits are installed on opposite ends of the arm and the nearest conductor
of the two classifications are separated a horizontal distance of not less
than 36 inches. Services direct from such a crossarm are not permitted to
cross conductors of other classification supported on the same crossarm.
(5) Change In Location With Respect To Supply Conductors:
At both ends of any section of private communication circuits supported on
the same crossarms with supply conductors in accordance with Rules 89.2-Al
or 89.2-A2, suitable equipment shall be provided to pre- vent effectively
the transmission, from one section of the line to another, of voltages exceeding
400 volts to ground or 750 volts between any two points of the circuit, including
voltages caused under transient or fault conditions, by induction from or
contact with the supply conductors supported on the same arms with the private
communication conductors.
Strikeout and Underline Version
Rule 89.2-A
89.2-A. Private Communication Circuits And Supply
Circuits On The Same Crossarms (see Rule 32.4-C)
(1) Supply Conductors Of 7500-
20,00021,000 Volts, Same Ownership: Where private communication
conductors are supported on the same crossarms with supply conductors of
7500-20,000 21,000 volts, the private communication
circuits shall have the strengths and clearances required for Class L circuits
of 750-5000 volts. The private communication conductors shall be on opposite
ends of the arms from the supply conductors and shall be separated a horizontal
distance of not less than 36 inches from the nearest supply conductor. Where
buck arms are used in connection with such circuit arrangement, the minimum
vertical separation between related line and buck arms shall be 4 feet and
the horizontal separation between the nearest conductors of the two classes
of circuits on the same arm shall be not less than 36 inches plus any horizontal
space provided by vacant pin positions which are required by climbing space
rules.
(2) Supply Conductors Of 750-7500 Volts, Same Ownership:
Where private communication conductors are supported on the same crossarms
with supply conductors of 750-7500 volts, the private communication circuits
shall have the strengths and clearances required for Class L circuits of
0-750 volts. The private communication conductors shall be on opposite ends
of the arms from the supply conductors with conductor clearances and the
spacing between related line and buck arms in conformity with the requirements
for combination arm construction. (See Rules 32.4-A3, 54.4-C2b, and 54.7-A.)
(3) Supply Conductors Of 0-750 Volts, Same Ownership: Where
private communication conductors are supported on the same crossarms with
supply conductors of 0-750 volts, the private communication circuits shall
have strengths and clearances as required for Class C conductors except that
the clearances from supply conductors of the same ownership shall conform
to the requirements for Class L circuits of 0-750 volts. The communication
conductors shall preferably be located in the outer pin positions.
(4) Supply Conductors Of 0-750 Volts, Different Ownership:
Supply circuits of 0-750 volts and private communication circuits of different
ownership may be supported on the same crossarm, provided the two classifications
of circuits are installed on opposite ends of the arm and the nearest conductor
of the two classifications are separated a horizontal distance of not less
than 36 inches. Services direct from such a crossarm are not permitted to
cross conductors of other classification supported on the same crossarm.
(5) Change In Location With Respect To Supply Conductors:
At both ends of any section of private communication circuits supported on
the same crossarms with supply conductors in accordance with Rules 89.2-Al
or 89.2-A2, suitable equipment shall be provided to pre- vent effectively
the transmission, from one section of the line to another, of voltages exceeding
400 volts to ground or 750 volts between any two points of the circuit, including
voltages caused under transient or fault conditions, by induction from or
contact with the supply conductors supported on the same arms with the private
communication conductors.
Final Version
Rule 89.2-A
89.2-A. Private Communication Circuits And
Supply Circuits On The Same Crossarms (see
Rule 32.4-C
)
(1) Supply Conductors Of 7500-21,000
Volts, Same Ownership: Where private communication conductors are supported
on the same crossarms with supply conductors of 7500-21,000 volts, the private
communication circuits shall have the strengths and clearances required for
Class L circuits of 750-5000 volts. The private communication conductors
shall be on opposite ends of the arms from the supply conductors and shall
be separated a horizontal distance of not less than 36 inches from the nearest
supply conductor. Where buck arms are used in connection with such circuit
arrangement, the minimum vertical separation between related line and buck
arms shall be 4 feet and the horizontal separation between the nearest conductors
of the two classes of circuits on the same arm shall be not less than 36
inches plus any horizontal space provided by vacant pin positions which are
required by climbing space rules.
(2) Supply Conductors Of 750-7500 Volts, Same Ownership:
Where private communication conductors are supported on the same crossarms
with supply conductors of 750-7500 volts, the private communication circuits
shall have the strengths and clearances required for Class L circuits of
0-750 volts. The private communication conductors shall be on opposite ends
of the arms from the supply conductors with conductor clearances and the
spacing between related line and buck arms in conformity with the requirements
for combination arm construction. (See Rules
32.4-A3
, 54.4-C2b
, and 54.7-A
.)
(3) Supply Conductors Of 0-750 Volts, Same Ownership: Where
private communication conductors are supported on the same crossarms with
supply conductors of 0-750 volts, the private communication circuits shall
have strengths and clearances as required for Class C conductors except that
the clearances from supply conductors of the same ownership shall conform
to the requirements for Class L circuits of 0-750 volts. The communication
conductors shall preferably be located in the outer pin positions.
(4) Supply Conductors Of 0-750 Volts, Different Ownership:
Supply circuits of 0-750 volts and private communication circuits of different
ownership may be supported on the same crossarm, provided the two classifications
of circuits are installed on opposite ends of the arm and the nearest conductor
of the two classifications are separated a horizontal distance of not less
than 36 inches. Services direct from such a crossarm are not permitted to
cross conductors of other classification supported on the same crossarm.
(5) Change In Location With Respect To Supply Conductors:
At both ends of any section of private communication circuits supported on
the same crossarms with supply conductors in accordance with Rules
89.2-A1
or 89.2-A2
, suitable equipment shall be provided to pre- vent effectively the transmission,
from one section of the line to another, of voltages exceeding 400 volts
to ground or 750 volts between any two points of the circuit, including voltages
caused under transient or fault conditions, by induction from or contact
with the supply conductors supported on the same arms with the private communication
conductors.