Original Version
Rule 58.4-B6
58.4-B6) Treatment of Lead Wires: Vertical and lateral leads between
line conductors and capacitors or regulators shall comply with Rules 54.6
and 54.4-C6; and with the clearances specified in Table 1, Cases 8 and 9;
and Table 2, Cases 15, 16, and 17. Where such leads enter cutouts or
switches, Rule 58.5-C shall also apply. Such lead wires may be installed
in the working space but shall not be installed in the climbing space.
All lead wires shall clear braces, bolts and other line hardware a distance
of not less than 1 ½ inches.
Strikeout and Underline Version
Rule 58.4-B6
58.4-B6) Treatment of Lead Wires: Vertical and lateral leads between
line conductors and capacitors or regulators shall comply with Rules 54.6
and 54.4-C6; and with the clearances specified in Table 1, Cases 8 and 9;
and Table 2, Cases 15, 16, and 17. Where such leads enter cutouts or
switches, Rule 58.5-C shall also apply. Vertical and lateral leads
between cutouts or fuse holders and regulator bushings, or leads directly
between line conductors and such bushings may clearances less than those
specified in Table 1, Case 8 Columns E and F, but not less than 6 inches
from the surface of the pole; such leads shall not be over 12 inches in length.
Such lead wires may be installed in the working space but shall not be installed
in the climbing space.
The clearances specified in Table 1, Case 8, Columns D and E, need not apply
to apparatus installed on poles consisting of single-pole structures or on
crossarms attached thereto provided that terminals and lead wires are not
less than 6 inches from surface of pole instead of 3 inches specified in
Table 1, Case 9 Columns D and E, and have as mush possible of the clearances
specified in Table 1, Case 8, Columns D and E. No reduction of the
clearances specified in Table 1, Case 8, Columns D and E is permitted for
interconnection wiring of polyphase installations nor to any lead wire passing
between pole and apparatus.
All lead wires shall clear braces, bolts and other line hardware a distance
of not less than 1 ½ inches.
Final Version
Rule 58.4-B6
58.4-B6) Treatment of Lead Wires: Vertical and lateral leads between
line conductors and capacitors or regulators shall comply with Rules 54.6 and 54.4-C6; and with the clearances specified in Table 2, Cases 15, 16 and 17. Where such leads enter cutouts or switches
Rule 58.5-C
shall also apply. Vertical and lateral leads
between cutouts or fuse holders and regulator bushings, or leads directly
between line conductors and such bushings may clearances less than those
specified in Table 1, Cases 8,
Column E and F, but not less than 6 inches
from the surface of the pole; such leads shall not be over 12 inches in length.
Such lead wires may be installed in the working space but shall not be installed
in the climbing space.
The clearances specified in Table 1, Cases 8,
Column D and E, need not apply
to apparatus installed on poles consisting of single-pole structures or on
crossarms attached thereto provided that terminals and lead wires are not
less than 6 inches from surface of pole instead of 3 inches specified in
Table 1, Cases
9,
Column D and E, and have as mush possible of the clearances
specified in Table 1, Cases 8,
Column D and E. No reduction of the
clearances specified in Table 1, Cases 8,
Column D and E is permitted for
interconnection wiring of polyphase installations nor to any lead wire passing
between pole and apparatus.
All lead wires shall clear braces, bolts and other line hardware a distance
of not less than 1 ½ inches.