Original Version
Rule 58.3-B
58.3-B. Case and Lead wire Clearances
1) Above Ground
a) Lead and bus wires: The clearances
above ground specified in Table 1 are applicable to unprotected lead and
bus wires of transformer installations except as modified by the following
provisions.
Clearances above ground unprotected lead and bus wires of transformer installations
may be less than 25 feet as specified in Table 1, Column E case 3 and 4, but
shall not be less than 22 ½ feet except where a clearance of not less
than 18 feet above ground is permitted by the provisions of Rule 54.4-A2b
in which case the clearance above ground of such lead and bus wires shall
be not less than 18 feet,
Clearances above ground of unprotected lead and bus wires of transformer
installations may be less than 30 feet as specified in Table 1, Column F,
Cases 3 and 4, but shall be not less than 27 feet.
Clearances above ground of unprotected lead and bus wires of transformer
installations on structures of two or more poles may be less than 22 ½
feet or 27 feet as specified above, or less than 25 feet as specified in Table
1, Column F, Case 5 but shall not be less than 20 feet above ground, provided
such lead or bus wires are guarded by transformer platform flooring which
extends not less than 1 foot horizontally outside the vertical planes of
all such lead and bus wires on the structure.
b) Cases: cases of transformers supported on poles or
structures shall not be less than 17 feet above the ground except that in
areas which are not in any way accessible to vehicles, the clearance of cases
above ground shall be effectively grounded.
2) From Buildings: Transformers on poles
shall be so located that normally Unenergized parts clear the surfaces of
buildings by not less than 3 feet horizontally or by not less than 8 feet
vertically. Lead and bus wires carried as unprotected conductors shall
have the clearances from buildings as specified in Table 1, Cases 6 and 7.
In situations where foregoing clearances of cases and
lead bus wires from walls of buildings (not windows, fire escapes, etc.)
are impracticable to obtain, such as the location of transformers on poles
in alleys, these clearances will not be held applicable provided wood barriers
authorized by this Commission are used.
3) Cases from conductor levels above and below: Transformers
shall be so installed that normally Unenergized metal parts clear unprotected
conductors, except the transformer connecting leads by distances specified
in the following provisions:
a) From 0-750 volt conductors
below: The vertical clearance of transformer cases and hangers from the level
of 0-750 volt conductors below (whether such conductors are supported on
crossarms or racks) shall not be less than 10 inches except for certain conductors
as provided in Rule 58.3-B4.
b) From 0-750 volt conductors above: The vertical clearance
of Unenergized metal parts of transformers from 0-750 volt conductors supported
on crossarms above shall be not less than 3 inches or, in lieu of such vertical
clearance, the Unenergized parts of transformers shall not be less than 6
inches horizontally from such conductors. The vertical clearance of
unenergized metal parts of transformers from 0-750 volt conductors supported
on racks above shall be not less than 4 feet.
c) From 750-7500 volt conductors below: The vertical clearance
of Unenergized metal parts of transformers from the level of 750-7500 volt
conductors below shall be not less than 12 inches.
d) From 750-7500 volt conductors above: The clearance
between Unenergized metal parts of transformers and 750-7500 volt conductors
above or alongside shall be not less than 12 inches vertically or 12 inches
horizontally, except that conductors of the circuit to which the transformer
is connected may be less than the 12-inch vertical clearance from such Unenergized
parts but shall be not less than 6 inches vertically from the transformer
case and not less than 3 inches radially from the hanger provided no line
conductor which is less than 12 inches horizontally from the case or hanger
is less than 3 inches (Table 1 Case 9) above the level of the top surface
of the crossarm.
e) From 7500-22,500 Volt conductor Above: The clearance
between unergized metal parts of transformers and 7500-22,500 volt conductors
above shall be not less than 18 inches vertically or 18 inches horizontally
except that the vertical clearance shall be not less than 30 inches from a
conductor at the top of pole as in Rule 54.4-D8b.
4) Transformer Cases from Certain
Conductors Less than 10 inches below the cases
a) Transformer Leads on
Heel Arms: Heel arms shall not used to support lead wires or taps except
where necessary to clear the lower voltage transformer leads from the transformer
case or other conductors.
b) Line conductors less than 10 inches below cases: Where
a transformer case is unusually long, a crossarm supporting line conductors
of 0-750 volts may be used as a heel arm or such conductors on an arm may
be less than 10 inches below the transformer case or the hangers) provided
all of the following conditions are met:
No more than a single transformer with
lower voltage of 0-750 volts is supported on the pole at the same level;
The vertical clearances between conductors on the hanger arm and such line
arm below shall not be less than as specified in Table 2, Cases 9 to 13;
It is not practicable to obtain the clearance of at least 10 inches specified
in Rule 58.3-B3;
Such 0-750 volt conductors clear the transformer case by not less than 15
inches horizontally;
Service drops are not run from the crossarm supporting 0-750 volts conductors
at that location; and
The vertical clearance of 0-750 volt conductors below the lowest point of
the transformer primary leads is not less than
18 inches for primary leads
of 750-7500 volts,
24 inches for primary leads of 7500-20,000 volts,
36 inches for primary leads of 20,000-35,000 volts.
5) From Hardware:
Transformer cases, hangers, and other metal parts in contact therewith shall
clear through bolts, arm braces and other hardware by not less than 1 ½
inches; except that transformer cases and hangers shall clear crossarm braces
and crossarm through bolts by not less than 1-inch air-gap distances and
1 ½ –inch creepage distance.
6) From Guys: Transformer cases and hangers shall be not
less than 4 inches from all portions of guys which are 6 inches or more from
the surface of poles or crossams at the guy attachment. Transformer
cases and hangers shall be not less than 1 ½ inches from all portions
of guys which are within 6 inches of the surface of poles or crossarms at
the guy attachments.
7) Treatment of lead wires: Vertical and lateral leads
between line conductors and transformers shall comply with Rule 54.6 and
54.4-C6; and with the clearances specified in Table 1, Cases 8 and 9; and
Table 2, Cases 15, 16 and 17. Where such leads enter cutouts or switches
Rule 58.5-C shall also apply. Such lead wires may be installed in the
climbing space.
All lead wires shall clear braces, bolts and other line hardware a distance
of not less than 1 ½ inches.
Strikeout
and Underline Version
Rule 58.3-B
58.3-B. Case and Lead wire Clearances
1) Above Ground
a) Lead and bus wires: The clearances above ground specified in Table 1 are applicable
to unprotected lead and bus wires of transformer installations except as
modified by the following provisions.
Clearances above ground unprotected lead and bus wires of transformer installations
may be less than 25 feet as specified in Table 1, Column E case 3 and 4, but
shall not be less than 22 ½ feet except where a clearance of not less
than 18 feet above ground is permitted by the provisions of Rule 54.4-A2b
in which case the clearance above ground of such lead and bus wires shall
be not less than 18 feet,
Clearances above ground of unprotected lead and bus wires of transformer
installations may be less than 30 feet as specified in Table 1, Column F,
Cases 3 and 4, but shall be not less than 27 feet.
Clearances above ground of unprotected lead and bus wires of transformer
installations on structures of two or more poles may be less than 22 ½
feet or 27 feet as specified above, or less than 25 feet as specified in Table
1, Column F, Case 5 but shall not be less than 20 feet above ground, provided
such lead or bus wires are guarded by transformer platform flooring which
extends not less than 1 foot horizontally outside the vertical planes of
all such lead and bus wires on the structure.
b) Cases: cases of transformers supported on poles or
structures shall not be less than 17 feet above the ground except that in
areas which are not in any way accessible to vehicles, the clearance of cases
above ground shall be effectively grounded.
2) From Buildings: Transformers on poles shall be so located
that normally Unenergized parts clear the surfaces of buildings by not less
than 3 feet horizontally or by not less than 8 feet vertically. Lead
and bus wires carried as unprotected conductors shall have the clearances
from buildings as specified in Table 1, Cases 6 and 7.
In situations where foregoing clearances of cases and lead bus wires from
walls of buildings (not windows, fire escapes, etc.) are impracticable to
obtain, such as the location of transformers on poles in alleys, these clearances
will not be held applicable provided wood barriers authorized by this Commission
are used.
3) Cases from conductor levels above and below: Transformers
shall be so installed that normally Unenergized metal parts clear unprotected
conductors, except the transformer connecting leads by distances specified
in the following provisions:
a)
From 0-750 volt conductors below: The vertical clearance of transformer cases
and hangers from the level of 0-750 volt conductors below (whether such conductors
are supported on crossarms or racks) shall not be less than 10 inches except
for certain conductors as provided in Rule 58.3-B4.
b) From 0-750 volt conductors above: The vertical clearance
of Unenergized metal parts of transformers from 0-750 volt conductors supported
on crossarms above shall be not less than 3 inches or, in lieu of such vertical
clearance, the Unenergized parts of transformers shall not be less than 6
inches horizontally from such conductors. The vertical clearance of
unenergized metal parts of transformers from 0-750 volt conductors supported
on racks above shall be not less than 4 feet.
c) From 750-7500 volt conductors below: The vertical clearance
of Unenergized metal parts of transformers from the level of 750-7500 volt
conductors below shall be not less than 12 inches.
d) From 750-7500 volt conductors above: The clearance
between Unenergized metal parts of transformers and 750-7500 volt conductors
above or alongside shall be not less than 12 inches vertically or 12 inches
horizontally, except that conductors of the circuit to which the transformer
is connected may be less than the 12-inch vertical clearance from such Unenergized
parts but shall be not less than 6 inches vertically from the transformer
case and not less than 3 inches radially from the hanger provided no line
conductor which is less than 12 inches horizontally from the case or hanger
is less than 3 inches (Table 1 Case 9) above the level of the top surface
of the crossarm.
e) From 7500-22,500 Volt conductor Above: The clearance
between unergized metal parts of transformers and 7500-22,500 volt conductors
above shall be not less than 18 inches vertically or 18 inches horizontally
except that the vertical clearance shall be not less than 30 inches from a
conductor at the top of pole as in Rule 54.4-D8b.
4) Transformer Cases from Certain Conductors Less than
10 inches below the cases
a) Transformer Leads on Heel Arms: Heel arms shall not
used to support lead wires or taps except where necessary to clear the lower
voltage transformer leads from the transformer case or other conductors.
b) Line conductors less than 10 inches below cases: Where
a transformer case is unusually long, a crossarm supporting line conductors
of 0-750 volts may be used as a heel arm or such conductors on an arm may
be less than 10 inches below the transformer case or the hangers) provided
all of the following conditions are met:
No more than a single transformer with lower voltage of 0-750 volts is supported
on the pole at the same level;
The vertical clearances between conductors on the hanger arm and such line
arm below shall not be less than as specified in Table 2, Cases 9 to 13;
It is not practicable to obtain the clearance of at least 10 inches specified
in Rule 58.3-B3;
Such 0-750 volt conductors clear the transformer case by not less than 15
inches horizontally;
Service drops are not run from the crossarm supporting 0-750 volts conductors
at that location; and
The vertical clearance of 0-750 volt conductors below the lowest point of
the transformer primary leads is not less than
18 inches for primary leads of 750-7500 volts,
24 inches for primary leads of 7500-20,000 volts,
36 inches for primary leads of 20,000-35,000 volts.
5) From Hardware: Transformer cases, hangers, and other
metal parts in contact therewith shall clear through bolts, arm braces and
other hardware by not less than 1 ½ inches; except that transformer
cases and hangers shall clear crossarm braces and crossarm through bolts by
not less than 1-inch air-gap distances and 1 ½ –inch creepage distance.
The minimum clearance of 1 ½ inches need not apply to through bolts
in metallic contact with transformer cases or metal parts thereof nor to through
bolts supporting heel arms, provided the portion of such through bolts extending
into the climbing space is covered with a suitable protective covering, and
provided that such coverings are made of seasoned Douglas Fir and are installed
in a workmanlike manner, or in the alternative, with a suitable nonconducting
shield or covering having the insulation efficiency and mechanical strength
of impregnated fiber 5/16 inches thick.
6) From Guys: Transformer cases and hangers shall be not
less than 4 inches from all portions of guys which are 6 inches or more from
the surface of poles or crossams at the guy attachment. Transformer
cases and hangers shall be not less than 1 ½ inches from all portions
of guys which are within 6 inches of the surface of poles or crossarms at
the guy attachments.
7) Treatment of lead wires: Vertical and lateral leads
between line conductors and transformers shall comply with Rule 54.6 and
54.4-C6; and with the clearances specified in Table 1, Cases 8 and 9; and
Table 2, Cases 15, 16 and 17. Where such leads enter cutouts or switches
Rule 58.5-C shall also apply. Such lead wires may be installed in the
climbing space.
The clearances specified in Table 1, Case 8, Column D and E need not apply
to apparatus installed on poles consisting of single pole structures or on
crossarms attached thereto provided that terminals and lead wires are not
less than 6 inches from surface of pole instead of 3 inches specified in Table
1, Case 9, Columns D and E, and have as much possible of the clearance specified
in Table 1, Case 8 Columns D and E, is permitted for interconnection wiring
of polyphase installations nor to connection wiring of polyphase installations
nor to any lead wire passing between pole apparatus.
All lead wires shall clear braces, bolts and other line hardware a distance
of not less than 1 ½ inches.
Final Version
Rule 58.3-B
58.3-B. Case and Lead wire Clearances
1) Above Ground
a) Lead and bus wires: The clearances above
ground specified in Table 1 are applicable to unprotected lead and bus wires of
transformer installations except as modified by the following provisions.
Clearances
above ground unprotected lead and bus wires of transformer installations may be
less than 25 feet as specified in Table 1, Column E case 3 and 4, but shall not
be less than 22 ½ feet except where a clearance of not less than 18 feet above
ground is permitted by the provisions of Rule 54.4-A2b in which case the
clearance above ground of such lead and bus wires shall be not less than 18
feet,
Clearances
above ground of unprotected lead and bus wires of transformer installations may
be less than 30 feet as specified in Table 1, Column F, Cases 3 and 4, but
shall be not less than 27 feet.
Clearances
above ground of unprotected lead and bus wires of transformer installations on
structures of two or more poles may be less than 22 ½ feet or 27 feet as
specified above, or less than 25 feet as specified in Table 1, Column F, Case 5
but shall not be less than 20 feet above ground, provided such lead or bus
wires are guarded by transformer platform flooring which extends not less than
1 foot horizontally outside the vertical planes of all such lead and bus wires
on the structure.
b) Cases: cases of transformers supported on poles or
structures shall not be less than 17 feet above the ground except that in
areas which are not in any way accessible to vehicles, the clearance of cases
above ground shall be effectively grounded.
2) From Buildings: Transformers on poles shall be so located
that normally Unenergized parts clear the surfaces of buildings by not less
than 3 feet horizontally or by not less than 8 feet vertically. Lead
and bus wires carried as unprotected conductors shall have the clearances
from buildings as specified in Table 1, Cases 6 and 7.
In situations where foregoing clearances of cases and lead bus wires from
walls of buildings (not windows, fire escapes, etc.) are impracticable to
obtain, such as the location of transformers on poles in alleys, these clearances
will not be held applicable provided wood barriers authorized by this Commission
are used.
3) Cases from conductor levels above and below: Transformers
shall be so installed that normally Unenergized metal parts clear unprotected
conductors, except the transformer connecting leads by distances specified
in the following provisions:
a) From 0-750 volt conductors below: The vertical clearance
of transformer cases and hangers from the level of 0-750 volt conductors below
(whether such conductors are supported on crossarms or racks) shall not be
less than 10 inches except for certain conductors as provided in Rule 58.3-B4.
b) From 0-750 volt conductors above: The vertical clearance
of Unenergized metal parts of transformers from 0-750 volt conductors supported
on crossarms above shall be not less than 3 inches or, in lieu of such vertical
clearance, the Unenergized parts of transformers shall not be less than 6
inches horizontally from such conductors. The vertical clearance of
unenergized metal parts of transformers from 0-750 volt conductors supported
on racks above shall be not less than 4 feet.
c) From 750-7500 volt conductors below: The vertical clearance
of Unenergized metal parts of transformers from the level of 750-7500 volt
conductors below shall be not less than 12 inches.
d) From 750-7500 volt conductors above: The clearance
between Unenergized metal parts of transformers and 750-7500 volt conductors
above or alongside shall be not less than 12 inches vertically or 12 inches
horizontally, except that conductors of the circuit to which the transformer
is connected may be less than the 12-inch vertical clearance from such Unenergized
parts but shall be not less than 6 inches vertically from the transformer
case and not less than 3 inches radially from the hanger provided no line
conductor which is less than 12 inches horizontally from the case or hanger
is less than 3 inches (Table 1 Case 9) above the level of the top surface
of the crossarm.
e) From 7500-22,500 Volt conductor Above: The clearance
between unergized metal parts of transformers and 7500-22,500 volt conductors
above shall be not less than 18 inches vertically or 18 inches horizontally
except that the vertical clearance shall be not less than 30 inches from a
conductor at the top of pole as in Rule 54.4-D8b..
4) Transformer Cases from Certain Conductors Less than
10 inches below the cases
a) Transformer Leads on Heel Arms: Heel arms shall not
used to support lead wires or taps except where necessary to clear the lower
voltage transformer leads from the transformer case or other conductors.
b) Line conductors less than 10 inches below cases: Where
a transformer case is unusually long, a crossarm supporting line conductors
of 0-750 volts may be used as a heel arm or such conductors on an arm may
be less than 10 inches below the transformer case or the hangers) provided
all of the following conditions are met:
No more than a single transformer with lower voltage of 0-750 volts is supported
on the pole at the same level;
The vertical clearances between conductors on the hanger arm and such line
arm below shall not be less than as specified in Table 2, Cases 9 to 13;
It is not practicable to obtain
the clearance of at least 10 inches specified in Rule 58.3-B3;
Such 0-750 volt conductors clear the transformer case by not less than 15
inches horizontally;
Service drops are not run from the crossarm supporting 0-750 volts conductors
at that location; and
The vertical clearance of 0-750 volt conductors below the lowest point of
the transformer primary leads is not less than
18 inches for primary leads of 750-7500 volts,
24 inches for primary leads of 7500-20,000 volts,
36 inches for primary leads of 20,000-35,000 volts.
5) From Hardware: Transformer cases, hangers, and other
metal parts in contact therewith shall clear through bolts, arm braces and
other hardware by not less than 1 ½ inches; except that transformer
cases and hangers shall clear crossarm braces and crossarm through bolts by
not less than 1-inch air-gap distances and 1 ½ –inch creepage distance.
The minimum clearance of 1 ½ inches need not apply to through bolts
in metallic contact with transformer cases or metal parts thereof nor to through
bolts supporting heel arms, provided the portion of such through bolts extending
into the climbing space is covered with a suitable protective covering, and
provided that such coverings are made of seasoned Douglas Fir and are installed
in a workmanlike manner, or in the alternative, with a suitable nonconducting
shield or covering having the insulation efficiency and mechanical strength
of impregnated fiber 5/16 inches thick.
6) From Guys: Transformer cases and hangers shall be not
less than 4 inches from all portions of guys which are 6 inches or more from
the surface of poles or crossams at the guy attachment. Transformer
cases and hangers shall be not less than 1 ½ inches from all portions
of guys which are within 6 inches of the surface of poles or crossarms at
the guy attachments.
7) Vertical and lateral leads
between line conductors and transformers shall comply with Rule 54.6 and 54.4-C6; and with the clearances
specified in Table 1, Cases 8 and 9; and Table 2, Cases 15, 16 and 17. Where such leads enter cutouts or switches
Rule 58.5-C shall also apply. Such lead wires may be installed in the
climbing space.
The clearances specified in Table 1, Cases 8,
Column D and E need not apply
to apparatus installed on poles consisting of single pole structures or on
crossarms attached thereto provided that terminals and lead wires are not
less than 6 inches from surface of pole instead of 3 inches specified in Table 1, Cases 9,
Column D and E, and have as much possible of the clearance specified
in Table 1, Cases 8,
Column D and E, is permitted for interconnection wiring
of polyphase installations nor to connection wiring of polyphase installations
nor to any lead wire passing between pole apparatus.
All lead wires shall clear braces, bolts and other line hardware a distance
of not less than 1 ½ inches.