Original Version
Rule: 54.6-C4
54.6-C4) Extent Of Run: The wood moulding, fiber conduit, or plastic pipe required for protection by this Rule 54.6C shall extend on the bottom surface of crossarm to within three inches the outer position of any conductor in the run and in no case shall the covering be terminated from center line of pole less than specified for conductors in Table 1, Case 8.
Strikeout and Underline Version
Rule 54.6-C4
54.6-C4) Extent Of Run: The Suitable Protective
covering (see Rule 22.2) required for protection by this Rule 54.6C shall extend on the bottom
surface of crossarm The wood moulding, fiber conduit, or plastic
pipe and in no case shall the covering be terminated from center line of pole less than specified for conductors in Table 1, Case 8.to within three inches the outer position of any
conductor in the run
Final Version
Rule 54.6-C4
54.6-C4) Extent Of Run: The Suitable Protective covering (see Rule 22.2) required for protection by this Rule 54.6-C shall extend on the bottom surface of crossarm and in no case shall the covering be terminated from center line of pole less than specified for conductors in Table 1, Case 8.
Information Only