Original
General Order
95
Section
III
Requirements for All Lines
Table 1
Basic Minimum Allowable Vertical Clearance of Wire Above Railroads,
Thoroughfares and Ground; Also clearances from Poles, Buildings, Structures
or Other Objects
(Letter References Denote Modifications of Minimum Clearances as Referred
to in Note Following this Table)
Case No
|
Nature of Clearance
|
Wire or Conductor Concerned |
|||||
A |
B |
C |
D |
E |
F |
||
1 |
25 ft |
25 ft |
22 ft |
25 ft |
28 ft |
34 ft |
|
2 |
26 ft (e) |
30 ft (g) |
34 ft (g) |
||||
3 |
19 ft |
20 ft |
30 ft (o) |
||||
4 |
Above ground along thoroughfares in rural districts or across other areas capable of being transversed by vehicles or agricultural equipment. |
15 ft (k) |
19 ft |
16 ft |
|||
5 |
Vertical ground in areas accessible to pedestrians only. |
7 ft |
19 ft |
12 ft |
17 ft |
25 ft (o) |
|
6 |
Vertical clearance above buildings and bridges (or other structures which do not ordinarily support conductors and on which men can walk) whether attached or unattached. |
8 ft (r) |
8 ft (r) |
8 ft |
8 ft |
12 ft |
12 ft |
7 |
-------------- |
3 ft (u) |
3 ft |
6 ft (v) |
6 ft (v) |
||
8 |
-------------- |
||||||
9 |
-------------- |
¼ pin spacing shown in Table 2 Case 15 (dd) |
(a) Shall not be reduced more than 5% because of temperature
or loading 37
(b) Shall be increased for supply conductors on Suspension
insulators, under certain conditions 37
(c) Special clearances are provided for traffic signal
equipment 58.1-C
(d) Special clearances are provided for street lighting
equipment 58.2-B
(e) Based on trolley pole throw of 26 feet. May be
reduced where suitably protected.
1. Supply Guys 56.4-B2
2. Supply cables and messengers 57.4-B2
3. Communication Guys 86.4-B2
4. Communication cables and messengers 87.4-B2
(f) May be reduced depending on height of trolley contact
conductors.
1. Supply Service Drop 54.8-C5
2. Communication service drops 84.8-D5
(g) May be reduced and shall be increased depending on
trolley throw
1. Supply conductors (except service drops) 54.4-B2
2. Communication conductors (except service drops) 84.4-B2
(h) Shall be increase where freight cars are transported.
1. Trolley contact and feeder conductors 74.4-B1
2. Trolley span wires 77.4-A
(i) May be reduced for trolley contact and span wires in
subways, tunnels and under bridges
1. Trolley contact conductors 74.4-E
2. Trolley span wires 77.4-A
(j) May be reduced at crossings over private thoroughfares and entrances to private property and over private property.
1. Supply Service drops 54.8-B2
2. Supply Guys 56.4-A
3. Communication service drops 84.8-C2
4. Communication guys 86.4-A
(k) May be reduced along thoroughfares where not normally
accessible to vehicles.
(l) May be reduced where within 12 feet of curb line of
public thoroughfares
1. Supply Service drops 54.8-B1
2. Communication service drops 84.8-C1
(m) May be reduced for railways signal cables under special
conditions 84.4-A4
(n) May be reduced in rural districts
1. Supply conductors, 750-20,000 volts, crossing roads or driveways 54.4-A2a
2. Supply conductors, 750-20,000 volts, above agricultural areas and along roads 54.4-A2b
3. Communication conductors along roads 84.4-A2
(o) May be reduced for transformer, regulator or capacitor
leads.
1. Transformer Leads 58.3-B1a
2. Regulator or Capacitor Leads 58.4-B1
(p) May be reduced across arid or mountainous areas
1. Supply Conductors of more than 20, 000 Volts 54.4-A1
2. Communication conductors 84.4-A1
(q) Shall be increased or may be reduced under special
conditions.
1. Increased for supply service drops on industrial or commercial premises 54.8-B3a
2. Supply service drops on residential premises 54.8-B3b
3. Communication conductors 84.4-A3
4. Increased for Communication service drops on industrial or commercial premises 84.8-C3a
5. Communication service drops on residential premises 84.8-C3b
(r) May be reduced above roofs of buildings under special
conditions
1. Supply overhead guys 56.4-G
2. Supply service drops 54.8-B4
3. Communication overhead guys 86.4-F
4. Communication conductors and cables 84.4-E
5. Communication service drops 84.8-C4
(s) Also applies at fire escapes, etc.
1. Supply Conductors 54.4-H1
2. Supply service drops on industrial or commercial premises 54.8-B4a
3. Supply service drops on residential premises 54.8-B4b
4. Communication Conductor 84.4-E
(t) Special Clearances where attached to buildings, bridges
or other structures
1. Supply conductors of 750-20,000 volts 54.4-H2
2. Trolley Contact Conductors 74.4-E
3. Communication Conductors 84.4-F
(u) Reduced clearances permitted under special conditions
1. Supply service drops on industrial or commercial premises 54.8-B4a
2. Supply cables, grounded 57.4-G
3. Communication cables beside buildings, etc. 84.4-E
4. Communication conductors under bridges, etc. 84.4-F
5. Communication service drops. 84.8-C4
(v) May be reduced under special conditions.
1. Supply conductors of 750-7500 volts 54.4-H1
2. Supply transformer lead and bus wires where guarded 58.3-B2
(w) May be reduced at angles in lines and transportation
points
1. Supply conductors 54.4-D1
2. Communication Conductors 84.4-D5
(x) May be reduced for suitably protected lateral or vertical
runs.
1. Supply bond wires 53.4
2. Supply ground wires 54.6-B
3. Supply lateral conductors 54.6-C
4. Supply vertical pins 54.6-D
5. Supply risers 54.6-E
6. Communication Ground Wires 84.6-B
7. Communication lateral conductors 84.6-C
8. Communication vertical runs 84.6-D
9. Communication risers 84.6-E
(y) Increased clearances for certain conductors
1. Unattached conductors on colinear lines and crossing lines 32.3
2. Unattached supply conductors 54.4-D3
3. Supply Service drops on clearance crossarms 54.8-C2
4. Supply Service drops on pole top extensions 54.8-C3
5. Unattached Supply service drops 54.8-D
6. Communication lines, collinear, conflicting or crossing 84.4-D3
7. Communication conductors passing supply poles and unattached thereto 84.4-D4
8. Communication service drops on clearance crossarms 84.8-D2
9. Communication service drops on pole top extensions 84.8-D3
10. Unattached Communication service drops 84.8-E
(z) Special provisions for police and fire alarm conductors
require increased clearances 92.2
(aa) May be reduced under special provisions.
1. Supply conductors of 0-750 volts in rack configuration 54.4-D5
2. Supply service drops from racks 54.8-F
3. Supply cables and messengers attached to poles 57.4-F
4. Communication conductors on communication poles 84.4-D
5. Communication conductors on crossarms 84.4-D1
6. Communication conductors attached to poles 84.4-D2
7. Communication service drops attached to poles 84.8-B
8. Communication cables and messengers 87.4-D
9. Supply or communication cables and messengers on jointly used poles 92.1-B
10. Communication service drops on pole top extensions 92.1-C
(bb) May be reduced for Class T conductors of not more
than 750 volts and of the same potential and polarity 74.4-D
(cc) Not applicable to trolley span wires 77.4-E
(dd) Special clearances for pole-top and dead-end construction
1. Conductors dead-ended in vertical configuration on poles 54.4-C4
2. Conductors dead-ended in horizontal configuration 54.4-D7
3. Conductors in pole-top construction 54.4-D8
(ee) Clearance requirements for certain voltage classifications
54.4-D2
(ff) Not applicable to communication conductors
84.4-D
(gg) Clearance from crossarms may be reduced for certain
conductors
1. Suitably insulated leads to protected runs 54.4-E
2. Leads of 0-5000 volts to equipment 54.4-E
3. Leads of 0-5000 volts to cutouts or switches 58.5-C