Rule 92.1-F
92.1-F(2) Cable
Terminals or Metal Boxes: On
jointly used poles metal communication cable terminals, metal boxes or similar
equipment which are less than 8 inches from centerline of pole or are attached
to surface of pole shall be placed not less than 6 feet vertically below or 3
feet above the level of the nearest unprotected supply conductor.
All parts of such metal terminals, boxes or similar
equipment which are 8 inches or more from center line of pole shall have
vertical clearances from open wire conductors not less than the clearance
specified in Table 2, Col. C, Cases 8 to 13 inclusive.
EXCEPTION: The minimum vertical distance between all parts of such metal terminals, boxes or similar equipment which are 8 inches or more from the center line of pole and are supported by cable and/or messenger alone can be reduced to not less than 1 inch by mutual agreement between the affected owners (see Rule 38, Table 2, Case 8, Column C)
For clearance between street light drop wires and cables, other conductors, and metal boxes see Rules 58.5-B3 and 92.1-F5.
Strikeout and Underline Version
Rule 92.1
92.1-F(2) Cable
Terminals or Metal Boxes: On
jointly used poles metal communication cable terminals, metal boxes or similar
equipment which are less than 8 inches from centerline of pole or are attached
to surface of pole shall be placed not less than 6 feet vertically below or 3
feet above the level of the nearest unprotected supply conductor.
All parts of such metal terminals, boxes or similar
equipment which are 8 inches or more from center line of pole shall have
vertical clearances from open wire conductors not less than the clearance
specified in Table 2, Col. C, Cases 8 to 13 inclusive.
EXCEPTION: The minimum vertical distance between all parts of such metal terminals, boxes or similar equipment which are 8 inches or more from the center line of pole and are supported by cable and/or messenger alone can be reduced to not less than 1 inch by mutual agreement between the affected owners (see Rule 38, Table 2, Case 8, Column C)
For clearance between street light drop wires and cables, other conductors, and metal boxes see Rules 58.5-B3 and 92.1-F5.
For clearances between Antennas and supplyor communication lines see Rule 38, Table 2, Case 21 and Rule 94.4.
Final Version
Rule 92.1
92.1-F(2) Cable
Terminals or Metal Boxes: On
jointly used poles metal communication cable terminals, metal boxes or similar
equipment which are less than 8 inches from centerline of pole or are attached
to surface of pole shall be placed not less than 6 feet vertically below or 3
feet above the level of the nearest unprotected supply conductor.
All parts of such metal terminals, boxes or similar
equipment which are 8 inches or more from center line of pole shall have
vertical clearances from open wire conductors not less than the clearance
specified in Table 2, Col. C, Cases 8 to 13 inclusive.
EXCEPTION: The minimum vertical distance between all parts of such metal terminals, boxes or similar equipment which are 8 inches or more from the center line of pole and are supported by cable and/or messenger alone can be reduced to not less than 1 inch by mutual agreement between the affected owners (see Rule 38, Table 2, Case 8, Column C)
For clearance between street light drop wires and cables, other conductors, and metal boxes see Rules 58.5-B3 and 92.1-F5.
For clearances between Antennas and supplyor communication lines see Rule 38, Table 2, Case 21 and Rule 94.4.