Original Version
Rule 58.2
58.2 Transformers
A. Grounding or Bonding
(1) Grounding of Windings: Where transformer windings are grounded, they shall be effectively grounded. Where the secondary system is grounded at any point, the grounded conductor shall be run to each service.
(2) Location of Transformer Winding Grounds: Transformer ground connections shall be provided at one of the following locations:
At the transformer pole or
At a pole adjacent to the transformer pole.
Transformer ground connections other than those occurring on common primary and secondary grounded neutral systems shall have an ampacity not less than that of No. 6 AWG copper wire.
Where a common primary and secondary grounded neutral system is used, ground connections shall conform to the requirements of Rule 59.4–A.
(3) Transformer
Case Grounding or Bonding: (See Rule 54.4–G for Grounded Equipment Clearances)
Transformers shall not be supported on metal poles or metal
supports in contact with the ground unless the cases are securely bonded to the
metal poles or parts of structures in contact with the ground and such poles or
structures are effectively grounded. Transformers installed on metal
mounting brackets shall not extend beyond the vertical plane through the
centerline of the pole.
Where transformer cases are bonded, the case bonding system shall
not be electrically connected to any unassociated hardware or to other bonds.
B. Connections between Windings
Any metallic connection between the primary
and secondary windings of a distribution transformer (as in common neutral
systems) shall be made externally and not within the transformer
case.
Strikeout and Underline Version
Rule 58.2
58.2 Transformers
A. Grounding or Bonding
(1) Grounding
of Windings: Transformer windings, providing service not exceeding 300 volts
(except those used exclusively for energizing street lighting systems or used
exclusively for energizing signal and traffic circuits) shall be effectively
grounded. Banked transformers are not required to have each transformer winding
grounded, however, at least one winding shall be effectively grounded .
Where transformer windings are grounded, they shall be effectively grounded. Where
the secondary system is grounded at any point, the grounded conductor shall be
run to each service.
(2) Location of Transformer Winding Grounds: Transformer ground connections shall be provided at one of the following locations:
At the transformer pole or
At a pole adjacent to the transformer pole.
Transformer ground connections other than those occurring on common primary and secondary grounded neutral systems shall have an ampacity not less than that of No. 6 AWG copper wire.
Where a common primary and secondary grounded neutral system is used, ground connections shall conform to the requirements of Rule 59.4–A.
(3) Transformer
Case Grounding or Bonding: (See Rule 54.4–G for Grounded Equipment Clearances)
Transformers shall not be supported on metal poles or metal
supports in contact with the ground unless the cases are securely bonded to the
metal poles or parts of structures in contact with the ground and such poles or
structures are effectively grounded. Transformers installed on metal
mounting brackets shall not extend beyond the vertical plane through the
centerline of the pole.Where transformer cases are bonded, the case bonding system shall
not be electrically connected to any unassociated hardware or to other bonds.
B. Connections between Windings
Any metallic connection between the primary
and secondary windings of a distribution transformer (as in common neutral
systems) shall be made externally and not within the transformer
case.
Final Version
Rule 58.2
58.2 Transformers
A. Grounding or Bonding
(1) Grounding of Windings: Transformer windings, providing service not exceeding 300 volts (except those used exclusively for energizing street lighting systems or used exclusively for energizing signal and traffic circuits) shall be effectively grounded. Banked transformers are not required to have each transformer winding grounded, however, at least one winding shall be effectively grounded. Where the secondary system is grounded at any point, the grounded conductor shall be run to each service.
(2) Location of Transformer Winding Grounds: Transformer ground connections shall be provided at one of the following locations:
At the transformer pole or
At a pole adjacent to the transformer pole.
Transformer ground connections other than those occurring on common primary and secondary grounded neutral systems shall have an ampacity not less than that of No. 6 AWG copper wire.
Where a common primary and secondary grounded neutral system is used, ground connections shall conform to the requirements of Rule 59.4–A.
(3) Transformer
Case Grounding or Bonding: (See Rule 54.4–G for Grounded Equipment Clearances)
Transformers shall not be supported on metal poles or metal
supports in contact with the ground unless the cases are securely bonded to the
metal poles or parts of structures in contact with the ground and such poles or
structures are effectively grounded.
Where transformer cases are bonded, the case bonding system shall
not be electrically connected to any unassociated hardware or to other bonds.
B. Connections between Windings
Any metallic connection between the primary
and secondary windings of a distribution transformer (as in common neutral
systems) shall be made externally and not within the transformer
case.