A B C
D E F
G H I J K
L M N
O P Q
R S T U
V W X Y Z
A
Abandoned Lines 31.6
Accepted Good Practice 13
Allowable Obstructions
Climbing Space 54.7–A3 , 54.9–F , 54.10–F3 , 54.11–G , 54.12–F3 , 58.3–A3 , 84.7–E , 88.1
Working Space 54.7–B2
Allowable
Tension-Definition 23.7–A
Alteration or Reconstruction,
Commission
May Order 12.4
Aluminum
Cable, Steel Reinforced Table 23 (Appendix
B
)
American Wire Gage (AWG) 24.2–A
Anchor Guys (See also Guys )
Attachment, Center of Load 56.2 , 66.2 , 86.2 , Appendix F - Parts 2 and 3
Clearances
(See Guy
Clearances )
Definition 56.1 (See Rules 21.5 and 23.5 )
From Transformer Cases 56.4–F
Grounding or Grounded 56.6–D , 66.6 , 86.6–C , 92.4
Location of Insulators 56.7–B , 86.7–B
Marking (Guarding) 56.9 , 66.7 , 86.9
Safety Factor 44 , 44.1 , Table 4 , 49.6–C
Sectionalizing Requirements
56.6 , 86.6
Size 49.6–B , 61.3
Strength 48.4 , Table
24
Use of 47.2
Angle of Deviation
Figure 86 (Appendix
G )
Angle Pole Problem Appendix F - Part
3
Annual Weather Variations, Normal
Table 1 - Note
(ddd)
Apparent Sag-Definition 23.3–B , Figure
4
Applicability of Common Neutral Rules
59.2
Applicability of Rules 11 , 12 , 13
Arching Shields 104 , 114
Arm Guy (See
Guy )
Arms (See
Crossarm )
Arrangement of Lines 32
Arresters, Lightning 22.0 , 33.3–A , 89.2
Attachment of Protective Covering
54.6–I , 84.6–F
Attachment of Conductors
to Bridges, Buildings, etc.
54.4–H2 , 54.4–I , 84.4–F
to Insulators 54.11–B1
to Trolley Span Wires 78.1 , 78.2
Attachment of Conductors to Surface of Poles
Cables
and Messengers, Longitudinal
57.4–F , 84.4–D2 , 87.4–D2
Communication Conductors, Longitudinal
84.4–D2 , 92.1–C , 92.1–D
Communication Service Drops
84.8–B2b
Ground Wires 54.6–B , 84.6–B
Low Voltage, on Racks ( See Rack Construction )
Lateral Runs 54.6–C , 84.6–C
Risers 54.6–E , 84.6–E
Vertical Configuration
54.4–D6b
Vertical Runs 54.6–D , 84.6–D
Without Use of Wood Crossarms
54.11–B
Attachment
to Poles of Span Wires, Foreign 34 , 78.3
Autotransformer 24.1
Avoidance of Conflict 31.3 , 31.4
A B C
D E F
G H I J K
L M N
O P Q
R S T U
V W X Y Z
B
Backbone 77 , 77.6–b
Backup Plate 54.6–E1c
Barriers 51.6–B , 61.6–A , 61.6–B
Bending, Moduli of Rupture in
48.1 , Table
5
Birmingham Wire Gage (BWG)
24.2–B
Bolts, Covered in Climbing Space
54.7–A3 , 58.1–B1
Bonds (or Bonding)
Capacitors
or Regulators 58.4–C
Circuits of 7,500 or Less
53.4–B , 103.1–B , 113.1–B
Circuits of More than 7,500 Volts
53.4–A , 63.4 , 103.1–B , 113.1–B
Common 53.4–A3b
Communication Messengers and Guys
83.4
Covering of Bond Wires 53.4–A , 53.4–B , 83.4
Grounded 33.3–A , 52.4–F , 53.4–A3a , 53.4–A3b
Messengers and Cables 57.8 , 83.4 , 92.4
Phase–to–phase 63.4
Pins and Deadend Hardware
53.4 , 63.4
Separate 53.4–A3a
Separation of Bond Wires 52.4–B , 52.7–C
Transformers 58.1 , 58.2–A3
Wire Size 53.4 , 63.4
Location and Clearance 54.4–G , 58.6 , 84.6–D , 88.1 , 92.1–F
Metal Back
52.7–E , 54.7–A3 , 84.7–B
Requirements for Use 47.2
Separation from Other Hardware and Conductors
52.7–B , 92.3
Cable
87.5
Communication, Open Wire
84.4–Clb
Service Drop, Clearance
54.8–C2 , 84.8–D2
Strength Table 4 (Section
4
)
Trolley 77.6–C
Bridge
Attachment
to 54.4–H2 , 54.4–I , 84.4–F
Clearance of Conductors from Table 1-Cases 6 and 7 , 54.4–H , 54.4–I , 84.4–F
Definition 20.3
Bridled Runs 84.6–D
Clearance,
Modified 64.4–C2
Climbing Space 54.7–A3 , 84.7–B
Definition 21.0–B
Vertical Separation Table 2-Case 14 , 54.4–C2a
Bundle
Conductor-Definition 20.9-A
A B C
D E F
G H I J K
L M N
O P Q
R S T U
V W X Y Z
C
Aluminum, Steel Reinforced
Table 23 (Appendix
B )
Auxiliary 77.6–A5 , 78.3–C
Bonding and Grounding 57.8
Boxes (See Boxes )
Clearance from its Messenger
57.4–D
Clearances (See Conductor )
Covering In Lieu of Guard Arms
57.7 , 87.7
Definition 20.4 , 87.1
Equalizer 74.4–G3
Fastenings Table 4 , 87.5
Guarding Above Trolley Contact Conductors
57.4–B2 , 87.4–B2
Guarding at Pole Attachments
57.4–F , 57.7 , 87.4–C3 , 87.7
Hooks, Location of 84.4–C1c , 84.8–B2b
Lateral and Vertical Runs (See Runs
)
Loading (See also Loading)
49.7-B
Low Voltage, Multiconductor with Bare
Neutral 54.10
Messenger (See Messenger )
Neutral Supported (“Triplex”) Service Drop
54.8–B4b
Protection 54.6–D , 54.6–E , 57.7 , 84.7–D , 84.6–E , 87.7
Risers (See Risers )
Sag 57.9 , 87.8
Terminals 54.6–F , 84.6–D , 88.1
“Triplex” (Neutral Supported Service Drop)
54.8–B4b
Capacitors, Detail of Installation 54.4
Capacitors
58.1–B
Regulators 58.1–B
Switches 54.4–G , 58.6–A
Transformers 58.2–A3
Change in
Grade of Construction 47.4 , 49.3–C2
Circuit (or Circuits)
Definition
20.6
Different Circuits on Same Crossarm
32.4 , 89.2–A
Governmental Agency Control
92.2
Ownership Designation 32.4–A4
Relative Levels 32.2
Class C
Communication Circuit-Definition 20.6–A
Class E Supply Circuit-Definition 20.6–D1
Class H Supply Circuit-Definition
20.6–D2
Class L Supply Circuit-Definition
20.6–D3
Class T Supply Circuit-Definition
20.6–E
Clearance Arm (See Crossarm )
Clearances (See Following Headings)
Conductor Clearances
Case
Clearances
Ground
Wires
Guy
Clearances
Guy
Insulators
Hardware
Lateral
Conductors
Lead
Wire Clearances
Messenger
Clearances
Pole
Risers
Roofs
Runs
Service
Drop Clearances
Sign
Clearances
Span
Wire Clearances
Street
Lighting
Tower
Transformers
Allowable
Obstructions 54.7–A3 , 54.9–F , 54.10–F3 , 54.11–G , 54.12–F3 , 58.3–A3, 84.7–E , 88.1
Buck Arm Construction 54.7–A2 , 84.7–B
Combination Line Arms 54.7–A2
Communication circuits 84.7
Definition 20.7
Joint Poles 93
One Vertical Circuit at Pole Top
54.11–F
Rack Construction 54.9–F
Space Bolts, Dead End, Covered In
54.7–A3
Supply Circuits 54.7
Terminals, Communication, Allowed In
88.1
Through Bolts, Transformer, Covered In
58.1–B3
Trolley Circuits 74.7
Colinear Lines
Definition
22.1–B
Requirements 32.3 , 54.4–D3 , 56.4–C2 , 84.4–D3 , 103.5
Circuits
Permitted 32.4 , 54.4–C2b , 54.7–A3 , 54.8–E
Definition 21.0–A
Marking (See also Marking ) 52.4–C
Common
Neutral System,Requirements for 59
Common Neutral, Tagging of
59.3–F
Communication Requirements
Section VIII
Concrete, Strength of Table 4 , 48.3
Condition, Most Stringent 14
Conditions, Limiting, Specified 14
Conditions, Two or More 14 , 42.1
Conductor (or Conductors)
Arrangement
Without Wood Crossarms
54.11–B2
Attached to Surface of Pole (See Attachment )
Bundle-Definition 20.9–A
Clearances (See Conductor Clearances )
Common Neutral System 59.3
Contact (See Trolley
Contact )
Covering, Weatherproof 54.8–A , 54.9–C1 , 74.4–G3 , 84.8–A , 92.2
Covering, Weather Resistant
20.9–G
Dead Ends (See Dead
Ending )
Definition of Kinds 20.9
Duplex Communication 84.4–C2
Earth as 33.2
Fastenings or Tie Wires
49.3–B3 , 49.3–C1b , 49.3–C2
Fire Alarm and Police 92.2
Ground (See also Ground
Wires )
33.2 , 92.4
Insulated, Suitable-Definition
20.9–G
Lateral (See Lateral Conductors )
Line-Definition 20.9–C
Loading 43 , App. B
Material 49.4–A , 54.11–C , 59.3–A , 6.3,
74.3
Neutral 33.1 , 59.2
Open wire-Definition 20.9–D
Overhead Lighting 61.3–A2 , 103.2 , 113.2
Protected 54.4–H2 , 54.4–I , 54.6–C , 54.6–D , 54.6–E , 84.6–D , 84.6–E
Safety Factor 44 , Table 4
Sag (See Sag )
Service Drop (See Service Drop
)
Size 49.4–B , Table
8 , 59.3–B , 59.4–A , 74.3 , 113.4
Spacing 54.11–D
Splices (See Splices
Conductor )
Strength 49.4–C , App.
B
Suitable Insulation 20.9–G
Suspensions 63
Tensions (See Tension )
Triplex Communication 84.4–C2
Unprotected 20.9–E , 54.6–A , 58.1–B
Vertical (See Vertical Conductors )
Weather Resistant not Suitably Insulated
20.8–G
Above
Ground 37 -Table 1-Cases 1 to 5
Above Swimming Pools 54.4–A3 , 84.4–A5
Above Tracks of Railways 37 - Table 1-Cases 1 and 2
Above Trolley Conductors 38 -Table 2-Case 2
At Points of Failure 49.4–C4 , 74.4–F
At Same Potential 64.4–C2
Basic 37 -Table 1 , 38 -Table 2
Between Conductors 38 -Table 2-Cases 1 to 17, 20
From Bridges, Buildings, etc. 37 - Table 1-Cases 6 and 7
From Crossarms 37 -Table 1 -Case 9 , 54.4–E , 58.3–A2
From Drip Loops 54.4–C7 , Figure
33
From Grounded Metal Boxes
54.4–G , 58.1–B , 92.1–F2
From Guys and Messengers 38 -Table 2-Cases 1, 18, and 19
From Hardware (See Hardware )
From Lead Wires 54.4–C6 , Figure
33
From Poles 37 -Table 1-Cases 8 and 9
From Signs 39 , Table 2–A
From Span Wires 38 -Table 2-Cases 1, 18, and 19
From Street Lights 58.5–B3 , 58.5–E , 92.1–F5
From Transformers 54.4–G , 92.1–F
From Trees 35 , Table 1, Case 13
Height Adjacent to Crossings
101.1 , 111.2
Modification of Basic Clearances Footnotes to Tables 1 and 2
On Insulators without Wood Crossarms 38 -Table 2-Case 20 , 54.11–B1 , 54.11–E
Reduced from Crossarms 54.4–E , 58.3–A2
Service Drop Clearances (See Service Drop Clearances )
Triangular Configuration, Between Conductors 54.4–C1c , 64.4–C1
Unprotected Vertical and Lateral
54.6A
Vertical Configuration, Between Conductors
54.4–C1a , 64.4–C1
Flashover
Voltages 55.3–C -Table
12
Material 55.1 , 65.1 , 85.1
Method of Testing 55.3–C
Safety Factors 44 , Table 4
Strength 49.5–A
Voltage Requirements 55.3 , 65.1
Conductor
Suspensions 63
Conduit (See also Pipe and Protective
Covering
) 20.9–E , 52.7–D , 54.4–H2 , 54.4–I , 54.6–C , 54.6–D , 54.6–E , 54.6–F , 84.4–F
Conflicting Lines-Definition
22.1–A , Section
X
Conflicts, Cooperation to Avoid
31.1 , 31.4
Connections, Electrical
49.4–E , 59.3–C
Constructions and Reconstruction of Lines
12.1 , 44.1
Change
of Grade 47.4
End Supports in Grades A and B
47.5
Grades of 42 , 44.1 , 49.1–B
Control
Circuits, Governmental Agency 92.2
Cooperation to Avoid Conflicts
31.4
Copper Covered Steel Table 22
Copper Wire, Characteristics of Tables 17 to 20 , Appendix
B
Corrosion Resistant (See Galvanizing
)
Cover
Bolt
- Definition 22.8–C
Bolt - in Climbing Space
54.7–A3i , 58.1–B3
Covering
(See Protective Covering )
Cradles or Screens 105 , 115
Crossarm or Arm
Braces
(See Braces )
Brackets (See Brackets )
Buck Arm (See Buck
Arms )
Clearance Arm, Use of 21.0–C , 32.3 , 54.4–D3 , 54.8–C2 , 84.4–D3 , 84.8–D2
Combination Arm (See Combination Arm
)
Cutout, Marking of 52.4–D
Definition of
Kinds 21.0
Guard Arm (See
Guard Arms )
Heel 58.1–B3
Kicker (Same as Heel )
Material 49.2A , 52.5 , 54.8–C3 , 84.8–D3
Marking 52.4 , 59.3–F
Metal 52.5 , 52.4–E4
Painting (Same as Marking )
Pin and Dead End Spacing 37 - Table 1-Case 8 , 38 -Table 2-Case 15
Pole Top Extension (See Pole Top Extension )
Safety Factor 44 , Table 4
Size 49.2–B
Strength 49.2–C
Crossing
Problem Appendix F - Part 1
Crossings (See Lines Crossing )
Cross Span Wires 77.2
Cutouts (See Switches )
In Working Space 54.7–B2
A B C
D E F
G H I J K
L M N
O P Q
R S T U
V W X Y Z
D
Dead End Assembly
Grounding
of Cable 57.7 , 87.7–B
Insulators (See Conductor Insulators )
Safety Factor 44 , Table 4
Separation of Hardware 52.7–D , 92.3
Spacing 37 -Table 1-Case 8 , 38 -Table 2-Case 15 , 63.3
Strength 57.5 , 87.5
Dead End and
Suspension Spacing 37 -Table 1 , 38 -Table 2 , 63.3
Dead Ending Supply Conductors
At
Top of Pole 54.4–D8
Clearances (See Conductor Clearances )
Messengers (See Messenger Fastenings
)
Space Bolt Covers in Climbing Space
54.7–A3
Typical Problems Appendix F - Part
1
Vertical Configuration
54.4–C4 , 54.4–D6
Decorative
Garlands 34 , 78.3 , 78.3–A2
Decorative Street
Lighting 78.3–A1 , 78.3–B , 78.3–C
Definitions Section II
Deflection, Structures Capable of
56.2 , 66.2 , 86.2
Depth of Setting Wood Poles
49.1–C
Deterioration (See Replacement )
Deviation, Angle of-Illustrated
Figure 86 , Appendix
G , Appendix
F - Part
3
Diagrams Appendix G
Dimensions (See also Size under various items)
Crossarms
49.2–B , Appendix
F
Poles 49.1–B , 82 , Appendix F
Protective Covering 22.8 , Figure
81 , Figure
82 (Appendix
G )
Tower Members 61.3–A1
Towers 22.1–C
Disconnects
(See Switches )
District,
High Fire-Threat 21.2-D, 18-A, 37, 80.1-A, 80.1-B
Districts, Loading 21.2–C , 43.1 , 43.2 , 49.4–C , Appendix
A
District, Rural 21.2–B
District, Urban 21.2–A
Division of Industrial Safety 39 , Table
2A, ref. (b)
Douglas Fir Molding (See Protective Covering, Suitable )
Drainage Coils 89.2
Drip Loops (See Lead
Wires )
Drive Hooks 84.4–C , 84.8–B2b2
Drop Wires, Street Light
54.6–A , 58.5–B3 , 92.1–F5
Duplex Pin Construction 102.1 , 112.1
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
E
Earth as a Conductor
33.2
Effectively Grounded-Definition
21.4–A
Elasticity, Modulus of, for Conductors
Appendix C
Element, Subordinate 12.1–C
End Supports-Grades A or B
47.5
Equalizer Cable, Trolley
74.4–G3
Equipment, Miscellaneous (See Miscellaneous Equipment )
Exceptional Cases, Relative Levels
32.2–G
Exemptions or Modifications 15
Exposed Guy (See Guy )
Experimental Installations
15.2
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
F
Factor of Safety (See Safety Factor )
Fastenings (See Fastenings under various items)
Feeder
Auxiliary
74.3 , 74.4–C , 77.6–A5
Common Neutral 59.3–B , 59.3–D
Span Wire 77.6–A4 , 77.6–A5 , 77.6–C3 , 78.1
Trolley 37 -Table 1–Col. C , 74.3 , 74.4–G3
Fence
Barrier 51.6–B , 61.6–B
Substation 61.6–B
Third Rail Enclosure 79.4
Fiber
Conduit 54.8–C2 , 77.6–A6 , 84.8–D2
Fire Alarm Circuits 20.6–A , 54.8–C1 , 92.2
Fittings, Terminal Fixtures
54.6–F , 84.6–D
Decorative
Lighting 34 , 78.3
Street Lighting 58.5–B , 58.5–D , 92.1–F5
Traffic Signal 58.4
Footings and
Foundations 45 , 46 , 48.5
Foreign Attachments 34 , 78.3
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
G
Gains, Pole 49.1–D
Gages, Kinds 24.2
Galvanizing or Corrosion Resisting
49.2–A2 , 49.3–A , 49.6–A , 49.7–A , 49.8 , 61.3–A1
Garlands, Decorative 78.3 , 78.3–A2
Governmental Agency Control Circuits
92.2
Grades of Construction (See also Pole, Dimensions ) 42 , Table 3 , 42.1 , 42.2 , 42.3 , 49.1–B
Greater Sag Permitted 37 , Appendix F
As
a Conductor 33.2
Connection, Grounded 21.3 , 33.3
Resistance 21.4 , 59.4–B2
Separation from Hardware
52.7–C
Wires and Neutrals 33.1 , 54.6–B , 61.3–A2 , 84.6–B
Grounded
Effectively
21.4–A , 33.3–A , 61.3–A2
Guys (See Guy )
Independently 33.3–B
Marking of Grounded Condition
58.3–C , 59.3–F
Metal Boxes and Equipment
54.4–G , 54.6–F , 58.6–C
Permanently 21.4–B
Securely 21.4–C
Grounding, Requirements for
Airbreak Switches
58.3–D4
Cables and Messengers 57.8 , 92.4
Capacitors 54.4–G
Common Neutral System 59
Guys (See Guy )
Hardware (See Hardware )
Metal Crossarms 52.5 , 54.4–G
Overhead Guys (See Overhead Guys
)
Regulators 54.4–G
Risers 54.6–E , 84.6–E
Switch Airbreak
58.3–D4
Transformer Cases 54.4–G , 58.2–A3
Transformer Windings 58.2–A1 , 58.2–A2
Vertical Run Conduit 54.6–D , 84.6–D
Clearance
from Hardware 52.7–B , 52.7–C , 54.6–B , 54.6–H
Common Neutral 59.3–C , 59.4
Conductivity 54.6–B
Covering-Definition 22.8–A , 54.6–B , 84.6–B
Location 54.6–B , 84.6–B
Material 49.4–A , 61.3–A2 , 84.6–B
Mechanical Strength 54.6–B , 59.4 , 61.3–A2 , 84.6–B
Definition
21.0–D
Material and Size 49.2–A , 49.2–B , 57.7
On Joint Poles 92.1–A to F1 incl.
Strength 49.2–C , 54.9–E1
Use with Cable and Messenger
57.4–F , 57.7 , 87.4–C3 , 87.7–B
Use with Grounded Equipment
54.6–F , 58.6–B
Use with Low Voltage Racks
54.9–E1 , 54.9–E2
Guarding
Latticed
Steel Poles 51.6–B
Messengers (See Messenger, Guarding )
Third Rail 79.2 , 79.3
Towers 61.6–B
Anchor
(See Anchor
Guy )
Arm 56.7–A , Figure
56–7
Attached to Grounded Structures
66.6
Attachment, Center of Load
56.2 , 66.2 , 86.2
Branched or Bridle 56.7–A , Figure
56–7
Bonding 83.4 , 92.4
Definition of 21.5
Exposed-Definition 21.5–C , 86
Fastenings, Hooks, Shims and Thimbles
56.5 , 66.5 , 86.5
Grounding or Grounded 56.6–D , 56.6–E , 66.6 , 86.6 , 92.4
Guarding where Clearance Reduced to Messengers
56.4–C4 , 86.4–C4
In Climbing Space 52.7–D , 54.7–A3 , 84.7–E
In Proximity-Definition 21.5–D , 56.6 , 86.6 , Figures 56–2
to 56–10
Lead of Guy, Illustrated
Figure 86 (Appendix
G )
Location of Sectionalizing Insulators
56.7 , 86.7
Markers (Guards) 56.9 , 66.7 , 86.9
Material 49.6–A
On Poles Set Shallow 49.1–C
Overhead (See Overhead
Guys )
Protection of, above Trolley Contact Conductors
56.4–B2 , 86.4–B2
Safety Factor 44 , Table 4
Sectionalizing Requirements
56.6 , 66.6 , 86.6
Sidewalk 56.7–B , 86.7–B , Figure
51
Size 49.6–B , 61.3–A3
Span 21.5–A
Strength 49.6–C , Table
9 ; 61.3–A2 , Table
24
Taut 56.2 , 66.2 , 86.2
Truss 56.7–C , 86.7–C , Figure
56–10
Use of 47.2 , 56.2 , 66.2 , 86.2
Above
Ground and Tracks of Railroads 37 - Table 1–Col. A
Above Swimming Pools
56.4–A3 , 86.4–A3
From Buildings, etc. 37 - Table 1
From Conductors, Guys and Span Wires 38 -Table 2–Col. A
From Insulators 56.4–D3 , 86.4–D3
From Poles 56.4–E , 86.4–E
From Transformer Cases 56.4–F
High Voltage, Not Decreased
66.4
Clearance
from Guys 56.4–D3 , 86.4–D3
Flashover Voltages 56.8–C -Table
13 , 86.8–C -Table
16
Location of Sectionalizing
56.7 , 77.6 , 86.7
Material 56.8–A , 86.8–A
Method of Testing 56.8–C , 86.8–C
Strength 49.5–B
Safety Factors 44 , Table 4
Voltage Requirement 56.8–C , 86.8–C
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
H
Hanger Arms (See Crossarms )
Hardware
Bonding
53.4
Clearances from Conductors
52.7–C , 54.6–B , 58.3–A2 , 92.3
Clearances from Ground Wires (See Ground Wires )
Construction Without Wood Crossarms
54.11–B1
Grounding 52.5, 52.7–B , 52.7–F , 91.4
Insulating Material Provide Clearance
54.6–H
Material 49.2–A2 , 49.3–A , 49.8 , 61.3–A
Safety Factor 44 , Table 4
Separation from Other Hardware
52.7–D , 53.4–A2 , 53.4–B , 54.6–H , 58.1–B3 , 91.4 , 92.3
Strength 57.5 , 77.5 , 87.5
Hardwood
Molding (See Protective Covering, Suitable )
Head Guys (See Overhead Guys
)
Heavy Loading 43.1
Heel Arms (See also Crossarms ) 58.1–B3
Height of Guy Figure 86 (Appendix
G )
High
Fire-Threat District 18-A, 21.2-D, 37, 80.1-A, 80.1-B
High Voltage Signs (See Marking )
Hooks, Guy 86.5
Hooks, Location of (See Cable
Hooks )
Horizontal Insulator-Definition
54.11–A
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
I
Ice Loading 43.1–B
Incidental Pole Wiring 38 -Table 2-Cases 16 and 17
Indicating Switches 58.3–B
Induced Voltage, Protection Against
89.2 , 92.4–B
Inductive Interference 90
Inductive Parallels-Avoidance of Conflict
31.3 , 31.4
Insulated-Definition 21.6
Insulators without the Use of Wood Crossarms
Attachment
54.11–B2
Clearances 54.11–B1 , 54.11–E
Climbing Space 54.11–F
Conductor Arrangement
54.11–B2
Conductor Spacing 38 -Table 2-Case 20 , 54.11–D
Hardware 54.11–B1
Horizontal Position-Definition
54.11–A
Triangular Configuration
54.11–B2
Vertical Clearance Between Levels 38 -Table 2 , 54.11–E
Vertical Position-Definition
54.11–A
Illustrative Diagrams
Appendix G
Inspection
of Lines 31.2
of Third Rail 79.6
Insulation,
Suitable 20.9–G
Insulators (See also Conductor
Insulators and Guy
Insulators )
Service
Drop with Bare Neutral
49.4–C7a , 54.8–A
Span Wire and Backbone 77.6
Street Lighting, Lowering Ropes In
58.5–D
Strength of 46 , 49.5
Suspension 63
Trolley Suspension 77.6–A3 , 77.6–C1
Intent to
Construct, Notice of 31.4
Intermediate Loading District (See Modified Loading
District
)
Isolated-Definition 21.7
Isolating of Exposed Guys
92.4–A , 92.4–B
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
Consideration
by All Interested Parties
31.5 , 91.1
Construction Requirement Section IX
Definition 21.8
Not Allowed on Non–climbable
Partial Underground 31.5 , 91.1
Jumpers (See Lead Wires )
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
K
Kicker Arm (Same as Heel
Arm )
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
Clearances
from Poles and Crossarms 37 - Table 1-Cases 8 and 9 , 54.4–E , 54.6–C , 84.6–C
Definition 20.9–B
Insulation 54.6–C , 54.8–C2 , 84.6–C , 84.8–D2
Protective Covering 54.6–C , 84.6–C , 87.7–A
Runs of (See Runs )
Unprotected 54.6–A
Guarding
51.6–B
Marking 51.6–A , 52.4–B
Safety
Factor 44 , Table 4
Stepping 51.7
Strength 45 , 46 , 48.2
Lead of
Guy-Illustrated Figure 86 (Appendix
G
)
Lead Wire Clearances
Above
Ground 37 -Table 1-Cases 1 to 5 , 58.1–B1
From Cases 58.1 , Table
58–2
From Hardware (See Hardware )
From Other Conductors 38 -Table 2-Cases 16 and 17 , 54.4–C6 , 58.5
From Poles and Crossarms 37 - Table 1-Cases 8 and 9
Lift Span
Definition
22.1–A
Trolley Construction 77.6–C2 , 77.6–C3
Lighting
(See Street Lighting )
Lightning Arresters-Definition
22.0
Lightning Protection Wires
61.3–A2 , 103.2 , 113.2
Limiting Conditions Specified 14
Line (or Lines)
Abandoned
31.6
Arrangement of 32
Clearances (See Conductor Clearances )
Colinear 22.1–B , 32.3
Conductor-Definition 20.9–C
Conflicts 22.1–A , 31.3 , 31.4 , Section
X
Construction of 12.1 , 31.1
Cutouts (See Switches )
Definition 22.1
Design 31.1
Grades of Construction 42
Inspection of 31.2
Maintenance of 12.2 , 31.1
Reconstruction of 12.1
Switches (See Switches )
Highways
37 -Table 1-Cases 3 and 4 , 49.4–C4
Other lines 38 -Table 2 , 42.2 , 42.3 , Section
X , Appendix
F
Railroads 37 -Table 1-Cases 1 and 2 , Section
XI
Typical Problems Appendix F
Loading
Districts 21.2–C , 43 , 43.1 , 43.2 , 49.4–C , Appendix
A
Loads
Balanced
49.2–C1 , 49.3–C1
Unbalanced 47.3 , 49.2–C2 , 49.3–C2
Wind 43.1–A , 43.2–A , 49.1–C
Longitudinal
Strength 47
Low Voltage Racks (See Rack Construction )
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
M
Maintenance
Major Railways 22.9–B
Marking
Common
Neutral, Designation 59.3–F
Guy Marker 56.9 , 66.7 , 86.9
Latticed Steel Poles 51.6–A
Less Than 750 Volts 52.4–C
Ownership, More Than 750
Volts 32.4–A4
Third Rail 79.1, 79.3, 79.4
Towers and Structures 61.6–A
Marking, High Voltage
Methods
51.6–A , 61.6–A
Requirements for Crossarms
51.6–A , 54.4–I
Requirements for Poles 51.6–A
Requirements for Towers and Structures
61.6–A
Material,
Strength of (See Strength of
Material
)
Material, Tower Members
61.3–A1
Maximum Allowable Tension-Definition
23.7–A
Maximum Limiting Conditions 14
Maximum Working Tension-Definition
23.7–B
Clearances
(See Messenger Clearances )
Bonding 83.4 , 92.4
Definition 23.7
Fastenings, Hooks, Shims and Thimbles
57.5 , 77.5 , 87.5
Grounding 92.4
Messenger (or Messengers) (See also Span Wires )
Guarding
Above Trolley Contact Conductors
57.4–B2 , 87.4–B2
Guarding Where Attached to Poles
57.4–F , 57.7 , 87.4–C3 , 87.7
Guarding Where Clearance Reduced to Guys
56.4–C4 , 86.4–C4
Material 49.7–A
Requirements for Use 57.2 , 87.2 , 89.4 , 103.4 , 113.4
Safety Factor 44 , Table 4
Sectionalizing of 57.6 , 77.6 ,
87.6
Strength 49.7–B , Table
24 (Appendix
B )
Supports 49.7–C
Above
Ground and Tracks of Railways 37 - Table 1–Col. A
Between Cables and Messengers 38 -Table 2–Col. A and C
Between Messengers 38 -Table 2–Col. A and C
From Buildings 37 -Table 1–Col. A
From Cables Supported 57.4–D
From Guys or Span Wires 38 -Table 2–Col. A and C
From Poles 57.4–F , 87.4–D
Messenger Insulators (See Guy
Insulators )
Metal Crossarm 49.2–A2 , 52.4–E4, 52.5
Metal Back Braces 52.7–E , 82.4–B
Metal Boxes (See Boxes )
Metal Poles 52.4–E3
Meters, Located on Pole
58.6
Meter Pole (See Service and Meter Pole )
Minimum Limiting Conditions 14
Minor Railway-Definition
22.9–A
Miscellaneous Equipment
52.4–D , 58 , 88
(See also Following headings)
Cable Terminals
Capacitors
Disconnects
Line
Switches
Metal
Boxes
Meters
Street
Lighting
Time
Switches
Traffic
Signals
Transformers
Voltage
Regulators
Modifications or Exemptions 15
Modified Loading District
43
Modulus of Elasticity for Conductors
Appendix C
Modulus of Rupture of Wood
48.1 , Table
5
Most Stringent Condition 14
Moulding (See Protective Covering )
Multiconductor Bare Neutral Construction
54.10
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
N
Neutral, Common (See Common Neutral )
Neutral Conductors
Classification
of 33.1
Grounding of 33.2 , 33.3 , 59.4–B
Interconnection of 33.3–B , 59.2
Neutral Grid
System 59.4–B
New British Standard Wire Gage (NBS)
24.2–C
Non–Walkable-Definition 22.4
Normal Annual Weather Variations
Table 1 -
Note (ddd)
Normal Conditions 35
Normal Sag 23.3–A
Notice of Intention to Construct
31.4
Notification 15.3
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
O
Obstructions, Allowable
In
Climbing Space 54.7–A3 , 54.9–F , 54.10–F3 , 54.11–G , 54.12–F3 , 58.3–A3 , 84.8–E
In Working Space
54.7–B2
Open
Wire-Definition 20.9–D
Overbuilds 22.1–B ; Figs. 2 and 3 (Appendix
G
)
Overhead Ground Wire 61.3–A2 , 103.2 , 113.2
Definition
21.5–A
Fastenings, Hooks and Shims
56.5 , 66.5 , 86.5
From Transformer Cases 56.4–F
Grounding 56.6–D , 56.6–E , 66.6 , 86.6–C , 86.6–D , 92.4
In Climbing Space 52.8–D ,
54.7–A3 , 84.7–E
Location of Sectionalizing Insulators
56.7 , 86.7
Material 49.6–A , 66.3
Protection above Trolley Contact Conductors
56.4–B2 , 86.4–B2
Sectionalizing Requirements
56.6 , 86.6
Size 49.6–B , 61.3–A3a
Strength 48.4 , 49.6–C , 66.3 , Table
24 (Appendix
B )
Use of 47.2 , 56.2 , 66.2 , 86.2
Overhead Line Structures-Definition
22.1–D
Overhead Guys 21.5-A
P
Painting (Same as Marking )
Partial Underground Distribution
Climbing
and Working Space 54.7
Conductor Clearances 54.4–C4c , 54.4–D2 , 54.4–D6c , Figure
54–2, Figure 54–3
Definition 22.5
Joint Use of Poles 31.5 , 91.1
Terminals of Risers 54.6–F
Transformers 58.2–A3
Voltage Requirements 55.3–D
Permanently
Grounded-Definition 21.4–B
Permitted Sag Appendix C , Appendix
F
Pins
Bonding
53.4
Duplex 102.1 , 112,1
Grounded at Crossing 104
Grounding (See hardware
Grounding )
Material 49.3–A
Safety Factor 44 , Table 4
Separation from Hardware
52.7–D
Size 49.3–B1 , 49.3–B2
Spaces, Vacant 54.4–C2b
Spacing 37 -Table 1-Case 8 , 38 -Table 2-Case 15
Strength 49.3–C
Uplift On 101.1 , 111.2
Pipe
(See also Conduit and Protective
Covering
)
Plastic (See Plastic
Pipe )
Plastic Moulding
Use
and Attachment 54.6–D , 54.6–I , 84.6–F , Figure
82 (Appendix
G
)
U–Shaped-Definition 22.8–B
U–Shaped, Ground Wire-Definition
22.8–A
Plastic Pipe (See also Conduit and Protective Covering )
Definition 22.8–B
Acting
as Strut 49.1–A , 56.2 , 66.2 , 86.2
Angle Problem Appendix F
Clearances from Railroad Tracks 36 , Appendix
E
Clearances of Conductors from (See Conductor Clearances )
Concrete 44 , Table 4 , 48.3
Deadend Problem Appendix
F
Definition 22.6
Depth of Setting 49.1–C , Table
6
Dimensions, Minimum Top
49.1–B
Gains 49.1–D
Inspection 31.2
Maintenance 11 , 12.2 , 31.1 , 35 , 44
Marking (See Marking )
Metal 52.4–E3
Metallic Service and
Meter 48.6
Nonclimbable-Definition
22.6–D
Replacement or Reinforcement Requirements
44.2
Safety Factor 44 , Table 4
Service and Meter-Definition
22.6–E
Setting Depths 49.1–C , Table
6
Spliced Poles 22.6–B , 49.1 , 101.2 , 111.3
Steel (See Latticed Steel Poles )
Steel, Tubular 44 , Table 4
Steps (See Stepping )
Strength 48.1 , Table 5 , 49.1–A
Stub Reinforced-Definition
22.6–C
Poles,
Jointly Used ( See Joint Use of Poles )
Pole Top Extension
Definition
22.6–A
Strength 49.1
Supporting Service Drops
54.8–C3 , 84.8–D3 , Figure
41 (Appendix
G
)
Transformers on, Prohibited
58.1–A2
Police and
Fire Alarm Circuits 20.6–A , 54.8–C1 , 84.8–D1 , 92.2
Pool, Swimming-Definition 23.6
Pothead 20.9–H , 54.6–F
Practicable 22.7 , 35 , 54.4–C1a , 54.4-C1b , 54.4–C6 , 54.4–G , 54.8–B , Table 10, 56.2 , 56.4–D3 , 56.7–A , 56.7–B , 66.2 , 84.8–C5 , 86.2 , 86.4–D3 , 86.7–B
Practice, Accepted Good 13
Private Communication Circuits
Attachment
to Trolley Span Wires 78.2
Construction Details 89.2
Definition 20.6–B
On Same Arm as Supply Circuits
32.4–C , 89.2
Private
Thoroughfare-Definition 24.0–B
Problems, Typical Appendix F
Protection
Against
Induced Voltages 90 , 92.4
Anchor Guys 56.9 , 66.7 , 86.9
Cables (See Cable )
Ground Wires 22.8–A , 54.6–B , 84.6–B , Figures 81 - 82 (Appendix
G )
Messengers (See Messengers,
Guarding )
Third Rail 79.2 , 79.3
Attachment
to Pole 54.6–I , 84.6–F , Figure
81 (Appendix
G
)
Definition 22.8
Douglas Fir, 1/2–in. Ground Wire Molding
22.8–A1 , Figure
81 (Appendix
G )
Hardwood Ground Wire Molding
22.8–A1 , Figure
81 (Appendix
G )
Requirements for Use 53.4 , 54.6–C , 54.6–D , 54.6–E , 54.8–C2 , 83.4 , 84.6–C , 84.6–D , 84.6–E , 84.8–D2
Rigid U–Shaped Plastic Molding (See Plastic Molding )
Proximity
(See Guys
, In Proximity )
Public Thoroughfare
Definition 24.0–A
Pull–offs 77.6–B
Puncture Voltage 55.3 , 56.8–C , 86.8–C
Purpose of Rules 11
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
Q
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
Between
Conductor Levels 54.9–E
From Poles 54.9–B1
On Joint Poles 92.1–A , 92.1–B
Climbing
Space 54.9–F
Conductor Arrangement 54.9–B2
Conductor Material 54.9–C
Conductor Spacing and Span Length
54.9–D
Radial Separation
Between
Guys and Conductors 38 -Table 2-Cases 18, 19
Of Conductors, Same Support 38 -Table 2-Cases 16, 17
Of Conductors, Where Colinear or
Approaching Crossings 38 -Table 2-Cases 1 – 7
Railways
Conductor
Clearances Above (See Conductor Clearances )
Crossing of Section XI , Appendix
F
Definitions, Major, Minor, Street
22.9
Pole Clearances from 36 , Appendix E
Reconstruction
Definition
23.0
Notification of 31.4
Of Lines 12.1
Or Alteration, Commission May Order
12.4
Safety Factors for 44.1
Regulators,
Voltage 58.1
Reinforcement Safety Factor
44.2
Related Buck Arm (See also Buck Arm
) 21.0–B
Relative Levels 32.2 , 92.2
Replacement
Circumference
of Grade “F” Poles Tables 25 and 27 (Appendix D )
Safety Factors 44.2
Resistance
of Grounds 21.4–A1 , 59.4–B2
Risers
Clearances
54.6–E , 54.6–H , 87.7–D
Covering 54.6–E , 54.6–I , 84.6–F , 87.7–D
Definition 23.1
Terminals 23.8 , 54.6–F , 54.7–A3
Roofs
(See Clearances from Buildings Under Various Items)
Rules
Applicability
of 11 , 12 , 31
Exemptions from or Modification to 15
Limiting Conditions 14
Purpose of 11
Saving Clause 16
Scope of 13
Bridled
84.6–D
Clearances 54.6–H
Covering 22.8 , 54.6–I , 84.6–F
Definition 23.2
Lateral 54.6–C , 84.6–C
Terminals 54.6–F
Vertical 54.4–D9 , 54.6–D , 84.6–D , 92.3
Rural District-Definition 21.2–B
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
For
Various Grades of Construction 44 , Table 4
General 44
Installation and Reconstruction
44.1
Replacement or Reinforcement
44.2
Additional
Allowance for Temperature 37
Charts of Sag for Copper Conductors Charts 1 to 9 inclusive (Appendix
C )
Communication Conductors, Suggested
Table 24 (Appendix
C )
Definition of Apparent and Normal
23.3 , Figs. 4 and 5 (Appendix
G )
For Cables and Messenger 57.9 , 87.8
For Conductors 54.5 , 74.5 , 84.5 , Appendices C and F
Permitted, Greater Appendix F
Sags and
Tensions Appendix F
Saving Clause 16
Scope of Rules 13
Screens or Cradles 105 , 115
Securely Grounded-Definition
21.4–C
Service and Meter Pole
Above
Ground 37 -Table1–Col. B
Above Private Property
54.8–B2
Above Swimming Pools 54.8–B5 , 84.8–C5
From Buildings 37 -Table 1-Cases 6 and 7 , 54.8–B4 , Table
10 , 84.8–C4
From Cables and Messengers
54.8–C1 , Figure
42
From Guys 38 -Table 2-Cases 18 and 19
From Line Conductors 38 -Table 2–Col. C and E , 54.8–C , 84.4–D1
From Poles 38 -Table 1-Cases 8 and 9 , 32.3 , 54.4–D , 54.8–D , 84.4–D4 , 84.8–E
From Other Service Drops
54.8–C4 , 84.8–D4
From Supply Conductors on
Combination Arms 54.8–E
On Clearance Arms 54.8–C2 , 84.8–D2
On Pole Top Extensions
54.8–C3 , 84.8–D3 , Figure
41 (Appendix
G )
Attachment
with Bare Neutral 49.4–C7a , 54.8–A
Covering, Weather–resistant
49.4–C7a , 54.8–A , 84.8–A
Definition 23.4
Material and Size 49.4–B , Table
8 , 49.4–C7 , 54.8–A , 84.8–A
Multiple Conductor, Supply
49.4–C7a , 54.8–A
Relative Levels 32.2–E , 32.2–F
Setting of
Poles, Depth of 49.1–C , Table
6
Shims (See Guy or Messenger Fastenings)
Sidewalk Anchor 56.7–B , 86.7–B
Sign Clearances 39 , Table
2–A
Sign Marking Common Neutral
59.3–F
Sign, Warning 54.4–I , 79.4
Signal Circuits, Railway
20.6–C
Signals, Traffic 58.4 , Figure
58–4
Size of Poles, Minimum 49.1–B
Space
Climbing
(See Climbing Space )
Working (See Working
Space )
Space Bolts,
Dead End, Covering 54.7–A3
Spacing, Pin 38 -Table 2-Case 15
Spacing, Dead End and Suspension 37 -Tables 1 and 2 , 63.3
Span Guy 21.5–A
Span Wire Clearances
Above
Ground 37 -Table 1 –Columns A and C
Above Railways 37 -Table 1 -Cases 1 and 2
From Conductors 38 -Table 2-Cases 1 to 7, 19
From Guys and Span Wires 38 -Table 2-Cases 1 and 18
From Poles and Structures 37 -Table 1 -Cases 8 and 9
Under Bridges 77.4–B
Attachment
to 78.2 , 78.3–A , 78.3–C
Definition 23.5
Fastenings 77.5
Lift Span - Definition 23.5–A
Location of Insulators 56.7 , 77.6
Span Wire Clearances continued
Material and Strength 49.7 , Table
24 (Appendix
B )
Protection above Trolley Contact
Conductors 56.4–B2 , 86.4–B2
Sectionalizing Requirements
56.6 , 77.6
Spans
Crossing,
Length of 103.3 , 113.3
Crossing Problem
Appendix F - Part 1
Normal 103.3 , 113.3
Strength of Conductors in
49.4–C
Spliced Poles
Definition 22.6–B
Use in Line Crossing, Conflicts 101.2
Use in Railway Crossing 111.3
Location
of 103.1–A , 113.1–A
Strength of 49.4–C6
Spreader
Brackets 54.12–D2
Steel Poles (See Latticed Steel Poles )
Steel, Poles, Tubular 44 , Table 4
Steel, Structural 48.2
Steel Wire, Characteristics of Table 21 (Appendix
B )
Steel Wire, Copper Covered
Table 22 (Appendix
B )
Stepping
Poles
51.7 , 81.6 , 84.7–E , 91.3
Towers 61.7
Strain
Insulators (See Insulators )
Street Lighting
Circuit
Voltage 58.5–A
Classification of Supply Circuits
20.6–D
Clearance from Metal Boxes
58.5–B3a , 92.1–F5
Clearances 58.5–B , 92.1–F5
Decorative (See Decorative Street Lighting )
Drop Wires 54.6–A , 58.5–B3a , 92.1–F5
Exceptions 58.5–F
Requirements 58.5
Street
Railway-Definition 22.9–C
Strength of Materials, Ultimate
Concrete,
Prestressed
48.3–B
Concrete, Reinforced 48.3–A
Conductors 48.5 , Tables 17 to 23 (Appendix
B )
Steel Strand 48.5 , Table
24 (Appendix
B )
Structural Steel 48.2
Tower or Pole Foundations
48.6
Wood 48.1 , Table 5
Strength Requirements
All
Lines Section IV
Detailed 49
Longitudinal Loads 47
Transverse Loads 45 , 45.1
Tower or Pole Foundations
48.6
Ultimate 48
Vertical Loads 46
Stringent
Condition, Most 14
Structural Material Other Than Wood
48.2
Structural Steel 48.2
Strut, Pole Acting As 49.1–A , 45.2, 66.2 , 86.2
Stub–Reinforced Pole 22.6–C , 101.2 , 111.3
Substation 61.6–B
Supply Circuits
Clearances
(See Conductor
Clearances )
Construction Requirements
12.1 , 31.1 , 40 , 50 , 60 , 70 , 80 , 90 , 100 , 110
Definition of Classes 20.6–D
Relative Levels 32.2 , 92.2
Suspension
Insulators (See also Insulators
) 63
Swimming Pool-Definition 23.6
Switches, Cutouts, Disconnects
Capacitor
58.1
Grounding of 52.7
Indicating Position 58.3–B
Lead Wires 58.1 , 58.3
Line 58.3
Operating Mechanism 58.3
Regulator 58.1
Street Lighting 58.4
Time 58.6
Transformer 58.1 , 58.2
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
T
Tables, List of
Tag, Common
Neutral 59.3–F
Taps, Wire (See Lead Wires )
Telephone Instruments on Poles or Structures
89.3
Temperature 43 , 43.1–C , 43.2–C
Tension
Maximum
Allowable-Definition 23.7–A
Maximum Working-Definition
23.7–B
Tensions and Sags Appendix F
Terminals
(See Riser
Terminals and Cable
Terminals )
Tests (See Insulator Tests)
Thermal Expansion, for Conductors
Appendix C
Third Rail, Requirements for 79
Thoroughfare-Definition 24.0
Through Bolts, Transformer Covering
58.1–B3
Tie Wires 49.3–A2 , 49.3–B3 , Table
7 , 49.3–Clb
, 49.3–C2
Time Switches (See Switches )
Tower
Clearances
from Railroad Tracks 36 , Appendix E
Crossings 60
Lines-Definition 22.1-C
Materials 61.3–A1
Marking 61.6–A
Safety Factor 44 , Table 4
Stepping 61.7
Strength 48.2
V–type 22.1-C
Y–type 22.1-C
Traffic
Signals 58.4 , Figure
58–4
Transformers
Autotransformers
24.1
Case Clearances 58.1–B
Case Grounding or Bonding
58.2–A3
Cutouts and Disconnects 58.3
Grounding of Windings 58.2–A
Insulating 89.2
Lead and Bus Wire, Clearances Above Grounds
58.1–B , Table
58–1
Platforms 58.1–B , Table
58–1
Position on Pole 58.1–A1 , 58.2–A3
Through Bolt Covers in Climbing Space
58.1–B3
Transposition,
Points of 38
Transposition Wires 21.9
Transverse Strength Requirements 45
Tree Trimming 35 , Appendix E
Triangular Configuration of Conductors On Pole Mounted Insulators
53.4–A1 , 54.4–C1c , 54.4–D8a , 54.11–B2
Trolley
Attachments
to Poles 78.3–B , 78.3–C
Attachments to Span Wires
77.5 , 78.2 , 78.3–A
Backbones 77 , 77.6–B
Brackets or Bracket Arms
77.6–C
Contact Conductor, Material and Strength
74.3
Contact Conductor Clearances
74.4
Details of Construction 70
Equalizer Cables 74.4–G3
Feeders 74.4–G3 , 77.6–A4 , 77.6–A5 , 77.6–C3 , 78.1
Lift Spans 77.6–C2 , 77.6–C3
Messengers 77 , 77.6–D
Pull–Offs 77.6–B
Span Wires 77.6–A
Truss
Guys 21.5–B , 56.7–C , 86.7–C , Figure
51 , (Appendix
G )
Tubular Steel Pole, Safety Factor of 44 , Table 4
Two or More Conditions 42.1
Two or More Systems, Arrangements
32.1
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
U
U–Shaped Plastic Moulding (See Plastic Moulding )
Ultimate Strength of Materials 48 , Appendix
F
Underground Distribution Partial (See Partial Underground )
Unprotected Conductors-Definition
20.9–E
Uplift on Foundations 48.6
Uplift on Pin 101.1 , 111.2
Urban District-Definition
21.2–A
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
V
V–Type Support Structures 22.1–C
Vacant Pin Spaces 54.4–C2b , 54.8–E2b
Vertical Conductors-Definitions
20.9–F
Risers
(See Risers )
Runs (See Runs)
Unprotected 54.4–D9 , 54.6–A
Vertical Configuration
54.4–C1c , 54.4–C4 , 54.4–D6 , 54.7–A1 , 54.9
On
Pole Mounted Insulators
54.11–E , 54.11–F
Vertical Mount
Insulators-Definition 54.11–A
Vertical Strength Requirements 46
Voltage or Volts-Definition
24.1
Voltage-Communication Conductors
20.6–A , 20.6–C
Voltage Classification-Supply Circuits
20.6-D , 20.6–E
Voltage Regulators
58.1
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
Wall, Barrier 51.6–B2 , 61.6–B2
Warning Signs
Bridges,
Viaducts 54.4–I
High Voltage (See Marking , High
Voltage
)
For Latticed Steel Poles (See Marking
)
Third Rail 79.4
Weatherproof
Copper Wire, Characteristics and Loading Tables 19 and 20 (Appendix
B
)
Weatherproofing or Weather–resistant Covering
Not
Suitable for Insulation 20.9–G
Police and Fire Alarm Conductors
92.2
Rack Conductors 54.9–C
Service Drops 54.8–A , 84.8–A
Weather
Records 43
Weather Variations, Normal Annual
Table 1 - Note
(ddd)
Wind Loading 43.1–A , 43.2–A , 49.1–C
Wire
Aluminum,
Steel Reinforced Table 23 (Appendix
B )
Copper Tables 17 to 20 incl. (Appendix B )
Copper Covered Steel Table 22 (Appendix
B )
Corrosion–resisting 49.4–A
Gages-Wire 24.2
Ground (See Ground
Wires )
Iron and Steel Table 21 (Appendix
B )
Lightning Protection 61.3–A2
Lead (See
Lead Wires )
Overhead Ground 61.3–A2
Sags (See Sag )
Tension (See Tension )
Tie (See Tie
Wires )
Transposition 21.9
Wood
Block
Protection 54.6–F5
Molding 22.8 , Figure
81 (Appendix
G
)
Poles, Requirement for Treatment
49.1–B
Strength 48.l , Table 5
Allowable
Obstructions in 54.4–D6b , 54.7–B2 , 58.1–B1 , 58.3
Definition 24.3
Dimensions 54.7–B1
Working Tension (See Tension )
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
X
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
Y
Y–Type Support Structures
22.1–C
Yield Point of Steel 48.2
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z
Z
A B C D
E F G
H I J K
L M N
O P Q
R S T U
V W X Y Z